China Suin SA2200 Class a Multi-Functional Power Quality Harmonics Analyzer, Find details about China Power Meter, Power Analyzer from Suin SA2200 Class a Multi-Functional Power Quality Harmonics Analyzer
Overview
The critical importance of electrical power in today's society necessitates daily maintenance and management to ensure that problem's don't occur. When they do, for example due to an equipment failure or abrupt surge in demand, engineers face the need to analyze the cause quickly.
The Suin SA2100 and SA2200 help troubleshoot power quality problems in three- and single-phase power distribution systems. Especially the SA2200 can conduct tests according to the international IEC 61000-4-30 Class A standard.
Advance function interface
1. Track harmonics up to 100th
2. Phase Diagram
3. Powerful logger function
4. Data analyze in PC software
Product Shows
Channel(Voltage/Current) | 4/4 | |||
Voltage Range | 1-1000Vrms, 6000V transient voltage | |||
Current Range | depends on supplied current clamp | |||
PC software analysis | Yes | |||
Micro SD card(bulid-in) | 32GB | |||
Battery | Lithium ion, 5200mAh/>8h | |||
Time Synchronization | GPS/Beidou(option) | |||
interface | USB Host, LAN, WIFI | |||
WIFI App | (option) | |||
Screen | 5.6' TFT LCD with resolution640*480(SA2200) | |||
Language | 14-Chinese, English, French, German, Italian, Japanese, Korean, Polish, Portuguese(Brazil/Portugal), Russian, Spanish (Latin/Spain), Turkish | |||
Dimension/Weight | 270*190*66mm/2.0kg | |||
Wire Combinatios | 1Ø+NEUTRAL,1Ø SPLIT PHASE,1Ø IT NO NEUTRAL,3Ø WYE, 3Ø DELTA, 3Ø IT, 3Ø HIGH LEG, 3Ø OPEN LEG, 2-ELEMENT, 2 1/2-ELEMENT | |||
Electrical Safety | IEC61010-1 ,Safety Degree: 600V CAT IV 1000V CAT III | |||
Measurement | ||||
Voltage/Current/Frequency | Measurement Range | Resolution | Accuracy | |
Vrms(AC+DC) | 1 ~ 120Vrms | 0.001Vrms | ±0.1% of nominal voltage | |
120Vrms~400Vrms | 0.01Vrms | |||
400Vrms~1000Vrms | 0.1Vrms | |||
Vpk | 1 ~ 1400Vpk | 0.01Vpk | ±0.5% of nominal voltage | |
V(Crest Factor) | 1.0 ~ >2.8 | 0.01 | ±5% | |
Arms(AC) | 10mV/A | 0~150A | 0.01A | ±0.1%±0.1A |
1mV/A | 1~2000A | 0.01A | ±0.1%±0.1A | |
65mV/1000A | 10~6000A | 0.01A | ±0.1%±0.2A | |
A(Crest Factor) | 1 ~ 10 | 0.01 | ±5% | |
Frequency | 42.5~57.5(50Hz nominal) | 0.01Hz | ±0.01Hz | |
51~69(60Hz nominal) | 0.01Hz | ±0.01Hz | ||
320~480(400Hz nominal) | 0.01Hz | ±0.01Hz | ||
Dips & Swells | ||||
Vrms1/2 | 0 ~ 200% of nominal voltage | 0.01Vrms | ±0.2% | |
Arms1/2 | depends on current clamps | 0.01A | ±1% | |
Harmonic (IEC61000-4-7) | ||||
Harmonic Number | 1 ~ 100(50/60Hz) (IEC61000-4-7) 1~12(400Hz) | |||
Harmonic Voltage %f | 0.0 ~ 100.0% | 0.01% | ±0.1% ± nx0.1% | |
Harmonic Current %f | 0.0 ~ 100.0% | 0.01% | ±0.1% ± nx0.1% | |
THD | 0.0 ~ 100.0% | 0.01% | ±2.5% | |
Phase | -180° ~180° | 0.1° | ± nx0.1° | |
Power and Energy | ||||
P, S, Q1 | Max. 6000MW | 0.1kW | ±1%±10 digits | |
PF & cosФ | 0 ~ 1 | 0.01 | ±0.01 | |
kWh, kVAh, kvarh | depends on nominal voltage and current clamps | ±1%±10 digits | ||
Flicker (IEC61000-4-15) | ||||
Pst(10min)/Plt (2 hrs) | 0.00 ~ 20.00 | 0.01 | ±5% | |
Unbalance | ||||
Voltage | 0.0 ~ 20.0% | 0.10% | ±0.1% | |
Current | 0.0 ~ 20.0% | 0.10% | ±1% | |
Voltage Phase | -360° ~ 0° | 0.1° | ±0.1° | |
Current Phase | -360° ~ 0° | 0.1° | ±0.5° | |
Voltage Transient | ||||
Vpk | ±6000Vpk | 0.01V | ±15% | |
Vrms | 10 ~ 1000Vrms | 0.01V | ±2.5% | |
Min. Test Time | 5us | |||
Inrush Current | ||||
Arms | depends on current clamps | 0.01A | ±1% ± 5digits | |
Inrush Duration | 1 ~ 32min selectable | 10ms | ±20ms | |
Mains Signaling | ||||
Signaling Frequency | 60-3000Hz | 0.1Hz | ||
Relative V% | 0%-100% | 0.10% | ±0.4% | |
Absolute V3s (3s average) | 0.0-1000V | 0.1V | ±5% of Nominal voltage | |
Logger | ||||
Recording | user-defined parameters for 4 phases at the same time | |||
Memory | Data stored in Micro SD card, 32GB | |||
Duration Time | 2 hrs to 1 year, depends on the recording items and time interval | |||
Interval | 1s to 60 minutes | |||
Monitor | ||||
Support EN50160 in default or user-defined standard |