Voltage regulation | Around ± 0.5 % |
Supply range | 85 to 139 V |
Potentiometer for voltage setting | 1000Ω /0.5W min. setting range ±5% |
Operating at 50 Hz | Threshold at 48 Hz without LAM forimpactsbetween 30 and 40% of the rated Load |
Threshold at 48 Hz with LAM 13% forimpacts between 40 and 70% of the rated Load. | |
Threshold at 48 Hz with LAM 25% for impacts > 70% of the rated load | |
Operating at 60 Hz | Threshold at 58 Hz without LAM forimpacts between 30 and 40% of the Rated load |
Threshold at 58Hz with LAM 13% for impacts 40 and 70% of the rated load | |
Threshold at 58Hz with LAM 25% for impacts > 70% of the rated load | |
Specific operating | Threshold at 57Hz without LAM for speed variations at a steady state > 2 Hz |
Threshold at 65Hz without LAM for speed and tractelec / gearlec (U/F gradient) | |
Special: the factory setting 48Hz 2U/F gradient; a special programme is Possible on request. | |
Threshold at 47.5 Hz without LAM for speed variations at a steady state > 2 Hz |