China Replacement One AVR R230 for Leroy Somer Alternator Automatic Voltage Regulator AVR Original R230, Find details about China Generator AVR R230, AVR R230 from China Replacement One AVR R230 for Leroy Somer Alternator Automatic Voltage Regulator AVR Original R230
Sensing Input | Voltage :85 to 139 V |
Frequency :50/60 Hz | |
Output | Voltage:max 75 V dc at 100V ac input |
Current: Continuous 4A dc; Intermittent 8A | |
Resistance :15 ohms minimum | |
P1 potentiometer (AVR voltage adjustment) | fully anti-clockwise |
Remote voltage adjustment potentiometer | centre position |
Voltage Regulation | around +/-0.5% |
Rapid response time (500 ms) for a transient voltage variation amplitude of ± 20% | |
Very simple in design,the alternator with shunt excitation has no sustaining short-circuit capacity | |
The regulator monitors the exciter excitation current as a function of the alternator output voltage | |
Turn the AVR voltage adjustment potentiometer P1 slowly until the output voltage rated value is obtained. |
220V voltage regulator AVR R230 for power generator | |
Magnetic field output | |
Voltage | Max 100VDC at 120VCD input, |
Current | Continous 8A,intermittent 10A-10S |
Power input | 120(90-140)VAC,1 phase 2 wires, |
Voltage Regulation | <±1% RMS with 4% engine governing |