China Fair Price Newly High Precision Three Phase Power Quality Analyzer, Find details about China Elecnova Sfere 720c Power Quality Analyzer, Fluke 1735 Power Analyzer Voltech Pm300 from Fair Price Newly High Precision Three Phase Power Quality Analyzer
Influence factor | Test item | Base condition | Working condition |
Environment temperature | All parameters | (23±2)°C | -10°C~ 40°C |
Relative humidity | All parameters | 40%~ 60% | <80% |
Phase-to-neutral voltage | All parameters | (100±1%)V | 1.0V~ 1000V |
Phase-to-phase voltage | True RMS phase-to-phase voltage | (200±1%)V | 1.0V~ 2000V |
Current | True RMS current | (5±1%)A | 10mA~ 1000A |
Network frequency | All parameters | 50Hz±0.1Hz | 40Hz~ 70Hz |
Phase shift | Active power and active energy | Cosφ=1 | Cosφ: 0.2~ 1.0 |
Reactive power and reactive energy | Sinφ=1 | Sinφ: 0.2~ 1.0 | |
Harmonic | All parameters | <0.1% | 0.0%~ 100% |
Voltage unbalance | All parameters | <10% | 0.0%~ 100% |
Working voltage of device | All parameters | DC9.8V±0.1V | DC9.5V~ 10.5V |
External electric field, magnetic field | All parameters | Should be avoided | |
Test position | Measured related parameters of current | Tested wire at the center of clamp. |
Power supply | Rechargeable lithium-ion battery pack 9.6V, backup charger. |
Battery indicator | Battery symbol shows dump energy. When the voltage is too low, automatic shutdown after the 1 minute. |
Power consumption | Current consumption of normal test 490 mA, continuous working for 8 hours. |
Display mode | LCD color screen, 640dots×480dots, 5.6 inches, display domain: 116mm×88mm. |
Size of clamp | 10Asmall sharp current clamp: 7.5mm×13mm; 100A circle current clamp: 35mm×40mm; 1000Acircle current clamp: 68mm×68mm. |
Instrument dimensions | L×W×H: 240mm×170mm×68 mm. |
Number of channels | 4U/4I. |
Phase-to phase voltage | 1.0V~2000V. |
Phase-to-neutral voltage | 1.0V~1000V. |
Current | 10Acurrent clamp: 10mA~10.0A; 100A current clamp: 0.10A~100A; 1000Acurrent clamp: 1.0A~1000A; Optional current transformer: instrument input current 1mA~500mA. |
Frequency | 40Hz~70Hz. |
Parameters of electricity | W, VA, Var, PF, DPF, cosφ, tanφ. |
Energy parameters | Wh, Varh, Vah. |
Harmonic | Order 0~50. |
Total harmonic distortion | Order 0~50, each phase. |
Expert mode | Yes. |
Number of Transient records | 150 sets. |
Voltage flicker | Yes. |
Starting current mode | Yes, 100 seconds. |
3 phases unbalance | Yes. |
Record | 300 days(simultaneous recording 20 parameters, record one point every 5 seconds). |
Min/Max recorded value | Measurement of maximum and minimum values over a period of time. |
Alarm | 40 different types of parameter selections, 12,800 sets alarm logs. |
Peak | Yes. |
Phasor diagram display | Automatically. |
Capacity of snapshots | 60. |
Menu language | English/Chinese. |
Communication | USB. |
Automatic switching off | When an alarm campaign is initiated or a search for transients, an inrush current capture, or a trend recording is pending or in progress, the device is not automatic switching off. |
In other test mode, 15 minutes without keystrokes, automatic shutdown after prompt 1 minute. | |
Backlight function | Yes, suitable for use at night and dark place. |
Weight | Host: 1.6kg (with battery). |
10Asmall sharp current clamp: 170g×4; | |
100A circle current clamp: 190g×4; | |
1000Acircle current clamp: 510g×4; | |
Test wires and power adapter: 900g; | |
Total weight: about 7.8kg (with packaging). | |
Length of voltage test wire | 3m. |
Length of current sensor wire | 2m. |
Working temperature and humidity | -10°C~40°C; below 80%Rh. |
Storage temperature and humidity | -10°C~60°C; below 70%Rh. |
Input impedance | Input impedance of test voltage: 1MΩ. |
Withstand voltage | Withstand 3700V/50Hz sinusoidal AC voltage for 1 minute between instrument wiring and shell. |
Insulation | Between instrument wiring and shell ≥10MΩ. |
Structure | Double insulation, with insulation vibration-proof sheath. |
Safely rules | IEC 61010 1000V Cat III / 600V CAT IV, IEC61010-031, IEC61326, Pollution degree: 2. |