China Networking Application and on-Line Type UPS Backup, Find details about China UPS, Power Supply from Networking Application and on-Line Type UPS Backup
odel | RM | RM | RM | RM | RM 6KR (L) | RM 10KR (L) | |||
1K (L) | 1.5K (L) | 2K (L) | -3K (L) | ||||||
PHASE | Single phase with ground | ||||||||
CAPACITY | 1000 VA / 800 W | 1500 VA / 1200W | 2000 VA / 1600 W | 3000 VA / 2400 W | 6000 VA / 4800 W | 10000 VA / 8000 VA | |||
INPUT | |||||||||
Nominal Voltage | 100/110/115/120/127 VAC or 200/208/220/230/240VAC | 208/220/230/240 VAC | |||||||
Voltage Range | 55-150 VAC ± 5 % or 110-300 VAC ± 5 % at 50% load | 110-300 VAC at 50% load | |||||||
80-150 VAC ± 5 % or 160-300 VAC ± 5 % at 100% load | 176-300 VAC at 100% load | ||||||||
Frequency Range | 45Hz ~ 55 Hz or 56Hz ~ 65 Hz | 46~54 Hz or 56~64 Hz | |||||||
Power Factor | >= 0.99 @ Nominal Voltage (100% Load) | >= 0.99 @ 100% load | |||||||
OUTPUT | |||||||||
Output Voltage | 100/110/115/120/127 VAC or 200/208/220/230/240VAC | 208/220/230/240 VAC | |||||||
AC Voltage Regulation (Batt. Mode) | ± 1% | ± 1% | |||||||
Frequency Range (Synchronized Range) | 40 Hz ~ 70 Hz | 46~54 Hz or 56~64 Hz | |||||||
Frequency Range (Batt. Mode) | 50 Hz ± 0.2 Hz or 60Hz ± 0.2 Hz | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | |||||||
Current Crest Ratio | 3:01 | 3:01 | |||||||
Harmonic Distortion | <= 3 % THD (Linear Load), | <= 3 % THD (Linear Load), | |||||||
<= 6 % THD (Non-Linear load) | <= 6 % THD (Non-linear Load) | ||||||||
Transfer Time | AC Mode to Batt. Mode | Zero | |||||||
Inverter to Bypass | 4 ms (Typical) | Zero | |||||||
Waveform (Batt. Mode) | Pure Sinewave | ||||||||
EFFICIENCY | |||||||||
AC Mode | 86% | 87% | 87% | 88% | 89% | ||||
Battery Mode | 84% | 85% | 85% | 86% | 88% | ||||
BATTERY | |||||||||
Standard Model | Battery Type | 12 V / 9 Ah | 12 V / 7 Ah | 12 V / 9 Ah | 12 V / 9 Ah | 12 V / 7 Ah | 12 V / 9 Ah | 12 V / 7 Ah | 12 V / 9 Ah |
Numbers | 2 | 3* | 3 | 4 | 6* | 6 | 20 | 20 | |
Typical Recharge Time | 4 hours recover to 90% capacity | 3 hours recover to 90% capacity | 4 hours recover to 90% capacity | ||||||
Charging Current (Max.) | 1.0 A | 2.0 A | |||||||
Charging Voltage | 27.4 VDC ± 1% | 41.1 VDC | 41.1 VDC ± 1% | 54.8 VDC | 82.1 VDC | 82.1 VDC ±1% | 273.0 VDC ±1% | ||
± 1% | ± 1% | ± 1% | |||||||
Long-run Model | Battery Type | Depending on the capacity of external batteries | Depending on applications | ||||||
Numbers | 18-20 | ||||||||
Charging Current (Max.) | 8.0 A | 2.0 A | |||||||
Charging Voltage | 27.4 VDC ± 1% | 41.1 VDC | 41.1 VDC ± 1% | 54.8 VDC | 82.1 VDC | 82.1 VDC ±1% | 273.0 VDC ±1% | ||
± 1% | ± 1% | ± 1% | |||||||
INDICATORS | |||||||||
LCD Display | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions | ||||||||
ALARM | |||||||||
Battery Mode | Sounding every 4 seconds | ||||||||
Low Battery | Sounding every second | ||||||||
Overload | Sounding twice every second | ||||||||
Fault | Continuously sounding | ||||||||
PHYSICAL | |||||||||
Standard Model | Dimension, DxWxH (mm) | 380 x 438 x 88 [2U] | 480 x 438 x 88 [2U] | 480 x 438 x 88 [2U] | 480 x 438 x 88 [2U] | 600 x 438 x 88 [2U] | 600 x 438 x 88 [2U] | UPS Unit : | UPS Unit: |
580 x 438 x133 [3U] | 668 x 438 x 133 [3U] | ||||||||
Battery Pack : | Battery Pack : | ||||||||
580 x 438 x 133 [3U] | 580 x438 x 133 [3U] | ||||||||
Net Weight (kgs) | 13.2 | 18.4 | 18.5 | 20.6 | 25.7 | 29 | UPS Unit : 17 | UPS Unit : 20 | |
Battery Pack : 57 | Battery Pack : 63 | ||||||||
Long-run Model | Dimension, DxWxH (mm) | 380 x 438 x | 480 x 438 x | 480 x 438 x 88 [2U] | 480 x 438 x | 600 x 438 x | 600 x 438 x 88 [2U] | 580 x 438 x 133 [3U] | 668 x 438 x 133 [3U] |
88 [2U] | 88 [2U] | 88 [2U] | 88 [2U | ||||||
Net Weight (kgs) | 9.1 | 11.3 | 10.7 | 11.3 | 14.6 | 14.8 | 17 | 20 | |
ENVIRONMENT | |||||||||
Humidity | 20-90 % RH @ 0- 40°C (Non-condensing) | ||||||||
Noise Level | Less than 50dB @ 1 Meter | Less than 55dBA @ 1 Meter | Less than 58dBA @ 1 Meter |