Good Insulation Solid Winding Iron Core Transformer - Sg Series

China Good Insulation Solid Winding Iron Core Transformer

Model NO.
SG
Usage
Power Transformer, Distribution Transformer
Frequency Characteristics
Power Frequency
Brand
Nce
Vector-Group
Dyn11 / Yyn0
Trademark
NCE
Transport Package
Export Standard Package
Specification
30kVA~2500kVA
Origin
Jiangsu, China
HS Code
8504210000
Model NO.
SG
Usage
Power Transformer, Distribution Transformer
Frequency Characteristics
Power Frequency
Brand
Nce
Vector-Group
Dyn11 / Yyn0
Trademark
NCE
Transport Package
Export Standard Package
Specification
30kVA~2500kVA
Origin
Jiangsu, China
HS Code
8504210000
Good Insulation Solid Winding Iron Core Transformer - SG Series

Model Description
Good Insulation Solid Winding Iron Core Transformer - Sg SeriesGood Insulation Solid Winding Iron Core Transformer - Sg SeriesGood Insulation Solid Winding Iron Core Transformer - Sg SeriesGood Insulation Solid Winding Iron Core Transformer - Sg SeriesGood Insulation Solid Winding Iron Core Transformer - Sg SeriesGood Insulation Solid Winding Iron Core Transformer - Sg SeriesGood Insulation Solid Winding Iron Core Transformer - Sg SeriesGood Insulation Solid Winding Iron Core Transformer - Sg SeriesGood Insulation Solid Winding Iron Core Transformer - Sg SeriesGood Insulation Solid Winding Iron Core Transformer - Sg SeriesGood Insulation Solid Winding Iron Core Transformer - Sg SeriesGood Insulation Solid Winding Iron Core Transformer - Sg Series
Product Use

The product has the following features: good insulation properties, high mechanical strength, moisture resistant, pollution-free, easy to install, and almost no need for maintenance. Can be applied for high rise buildings, wind power generation, solar energy, hospital, hotel, tunnel, station, wharf, airport, subway, petroleum, chemical industry, laboratory, combined power plant, shopping mall and other important places etc.

Product Usage Condition

(1).Altitude
Not more than 1000m;
(2).Cooling air temperature
Max. Temp.: 40
ºC
Max. monthly mean temp.: 30ºC
Max. annual mean temp.: 20ºC
lowest temp.: -25ºC ( suitable for outdoor transformer )
lowest temp.: -5
ºC ( suitable for indoor transformer )
(3).Humidity
Ambient air relative humidity should be less than 93%, no water drop on the coil surface. If usage condition exceeds above requirements, should adjust running parameters (e.g. output current etc.) properly and adopt proper protecting measures to ensure the product service life and safety reliability.

Product Structure Characteristic

(1) Iron core
Key part of solid winding iron core transformer is solid winding iron core. The entire core is pieced by three completely same single frames, arranged in an equilateral triangle. Each single frame is continuously winded by numbers of trapezoid strips, the intersecting surface of the winded single frame looks like semicircle, the pieced intersecting surface of three single frames is a quasi-polygon which looks quite like an entire circle. The entire magnetic circuit winds tightly, void-free. High magnetic direction of silicon strip is completely same with the magnetic circuit direction, small magnetic resistance. Three phase magnetic circuit are same in length, thus the three phase are balanced, can reduce the transformer third harmonic etc., save material, improve performance, reduce loss, no-load current and operation noise etc.
(2) Coil
Low voltage coil adopts double cylinder or foil winding, solid triangle low voltage balanced outlet. High voltage winding adopts continuous structure, has big air contact area and good thermal ventilation performance.
(3) Base
According to users' requirements, base steel channel or trolley is equipped.
(4) Terminal
Low voltage connection adopts nickel plated steel with connection holes welded to coil terminal, fix to the clamps by insulator, convenient to connect; high voltage terminal adopts pre-buried copper nut coupling.
(5) IP grade
IP00 is not equipped with protective cover, suitable for box power station, and power distribution cabinet etc.;IP20 is equipped with metal mesh protective cover, can protect 12mm foreign matter from entering, and installed inside.IP23 is equipped with louver protective cover,can protect from rain, snow, and insects etc.,but need to reduce 5% of the capacity when using this kind of cover.
(6) Transformer cooling method
For transformers whose capacity is 125kVA and less than 125Kva, cooling method is AN, can output 100% rated capacity continuously meanwhile. For transformers whose capacity is 160kVA and more than 160Kva, cooling method is AF, may not open draught fan under certain capacity, but when more than 70% of the rated capacity, need to open the draught fan.
(7) Temperature control
Automatic temperature control system is used, features like temperature display, data scanning, open and close draught fan, over temperature alarm, hopscotch, computer communication interface etc. can be realized according to users' requirement.

Installation and Maintenance

Installation site should be dry, ventilative, can ensure the transformer to dissipate heat fully. The ground should be flat,no water entrance and risk of burning. Check whether there is dirt or condensation on the transformer surface before operation. Generally, blow with vacuum cleaner or compressed air, drying treatment, then check the insulation resistance and power-frequency voltage -withstand test, if qualified, can put the transformer int0 use.
Transformer is delivered with protective cover, except power cable, nothing can be put on the cover. Except installing the cable according to relative diagram, no devices or attachments that not provided or approved by supplier can be installed into the cover; otherwise, responsibility is conceited. Fixed point in transformer iron core or winding is not permitted in any case. All the distances between charged bodies should meet corresponding national standards.
Solid winding iron core transformer breaks the structural frame of traditional laminated iron core. Thanks to the structural improvement, it makes a qualitative leap for distribution transformer which is particularly significant nowadays when demand for electricity is growing rapidly for all industries. Solid winding iron core transformer will surely have great market judging from environmental protection, energy saving, operation safety and reliability etc.


Performance Parameter Table
Product Type Rated Capacity
(KVA)
Voltage CombinedVector- groupNo-load Loss (w)load Loss (w)
120ºC
No-load
current (%)
Short- circuit
impedance (%)
Noise
(dB)
  HV(KV)Tapping RangesLV(KV)      
SG10-30/10306
6.3
6.6
10
10.5
11
±5%
±2×2.5%
0.4Dyn11
or
Yyn0
1907600.94.050
SG10-50/1050    27010700.9 50
SG10-80/1080    37014800.9 50
SG10-100/10100    40016900.6 50
SG10-125/10125    47019800.6 50
SGB10-160/10160    54022800.6 50
SGB10-200/10200    62027100.5 50
SGB10-250/10250    72029600.5 50
SGB10-315/10315    88037300.5 50
SGB10-400/10400    98042800.4 50
SGB10-500/10500    116052300.4 50
SGB10-530/10530    134062900.3 55
SGB10-600/10630    130064000.36.055
SGB10-800/10800    152074600.3 55
SGB10-1000/101000    177087600.3 55
SGB10-1250/101250    2090103000.25 55
SGB10-1600/101600    2450125000.25 55
SGB10-2000/102000    3050155000.2 55
SGB10-2500/102500    3600184000.2 55

FAQ For You
 
Q: What certificates and standard does your company have?
A: Our factory has ISO9001:2008, ISO14001:2004, OHSAS18001:2007 certificates.
We can send products to appointed laboratories for testing if necessary.
Q: How long is your delivery time?
A:For 10KV distribution transformer, the production cycle of our factory is 20~25 days.
Q: What is your service?
A: we have quick response in before sales period help you got order, and excellent service in production time let you know each step we made.
Q: What is the guarantee?
A: Generall 1-2 years, when the guarantee period ends up, we are responsible for life-long maintenance and would charge some fees concerning costs.
Q: What is the standard of package? 
A: Export standard package or special package according to customer requirement
Q:What is your payment term?
A:All terms of payment is acceptable.