China Telecom Cabinet Heat Exchanger, Match with Hrv, Air Conditioner, Find details about China Telecom Cabinet Heat Exchanger, Heat Exchanger Cabinet from Telecom Cabinet Heat Exchanger, Match with Hrv, Air Conditioner
No. | Parameters | Default | Setting range |
00 | ON temperature of heat exchanger | 27 | 0 |
01 | OFF temperature of heat exchanger | 24 | 0 |
02 | Temperature difference between indoor and outdoor | 3 | 0 |
03 | Running time of heat exchanger | 30seconds | 0second-88 minutes |
04 | ON temperature of air cooling | 30 | 0 |
05 | OFF temperature of air cooling | 28 | 0 |
06 | ON temperature of air heating | 12 | 0 |
07 | OFF temperature of air heating | 15 | 0 |
08 | Running time of air conditioner | 10minutes | 0-99minutes |
09 | Temperature of over heating alarm | 35 | 0 |
10 | Delay time of fans | 30 | 0-99seconds |
11 | Opening time of air valve | 0 | 0-99seconds |
12 | Local address | 1 | 0-99 |
13 | Humidity protection | 85 | 0-99 |
14 | Filter monitor(Optional) | 0 | 0-99(days) |