12kv Indoor High Voltage Air-Compression Load Break Switch (VACF12-12D)

China 12kv Indoor High Voltage Air-Compression Load Break Switch (VACF12-12D), Find details about China Switch, Load Break Switch from 12kv Indoor High Voltage Air-Compression Load Break Switch (VACF12-12D)

Model NO.
VACF12-12D/T630-20
Rated Dynamic Stability Current
50ka
Rated Cable Charged Current
10A
Power Voltage of Motor Operation
AC/DC 220V
Trademark
VACEM
Origin
Wenzhou, China
Model NO.
VACF12-12D/T630-20
Rated Dynamic Stability Current
50ka
Rated Cable Charged Current
10A
Power Voltage of Motor Operation
AC/DC 220V
Trademark
VACEM
Origin
Wenzhou, China
1.General description
     VACF12-12D/T630-20KA type indoor AC M.V. switch equipment with rated voltage of 12kv,rated frequency tri-phase 50Hz, for the closing and opening load current,loop current,air containing transformers and cable charging current,short circuit current of the closing.Equipped with earthing switch,load switch can withstand short-circuit current.
2.Main technical parameter
ItemUnitVACF12-12DT630-20
Rated voltagekV12
Rated frequencyHz50
Rated currentA630
1 min power frequency withstand voltagekVPhase to phase,to earth 42;isolating fracture 48
Lightning impulse withstand voltagekVPhase to phase,to earth 75;isolating fracture 85
Rated thermal stability currentkA20(4s)
Rated dynamic stability currentkA50
Rated making current(peak)kA50
Max,breaking currentkA1.8
Breaking no-load transformer capacitykVA1250
Rated cable charged currentA10
Breaking times of rated power load currenttimes6000
Thermal stability current of earth switchkA20(2s)
Dynamic stability current of earth switch(peak)kA50
Power voltage of motor operationVAC/DC 220
 
ItemUnitData
VACF12-12D/T630-20
Moving contact travelmm200(+8,-2)
Inter-phase center distance(before mechanism stored energy)mm210±1.5
Moving contact opening distancemm40±2
Opening clearance between auxiliary contactmm≥150
Tri-phase closing/opening asynchronousms≤3
Just off speedm/s≥2.8
Just on speedm/s≥3.8
Distance between metal value to conduct tubemm≥125
Fracture distance of earth switchmm≥150
Main loop resistanceμΩ≤120
Max operating torqueN.m≤160
Note:1.Measure the distance between moving and fixed auxiliary contact,may measure the fixed arc contact after to conduct tube ejector nozzle end surface to add 24mm thickness.
2.While measuring main loop resistance of VFKRN12A-12D combination electrical appliance,fuse can be replaced by conduct rod whose resistance can be ignored.
3.International fairs
12kv Indoor High Voltage Air-Compression Load Break Switch (VACF12-12D)
4. Company show12kv Indoor High Voltage Air-Compression Load Break Switch (VACF12-12D)12kv Indoor High Voltage Air-Compression Load Break Switch (VACF12-12D)12kv Indoor High Voltage Air-Compression Load Break Switch (VACF12-12D)12kv Indoor High Voltage Air-Compression Load Break Switch (VACF12-12D)12kv Indoor High Voltage Air-Compression Load Break Switch (VACF12-12D)