China 10ka Polymeric Hoursed Metal-Oxide Surge Arrester Lightning Arrester, Find details about China Surge Arrester, Lightning Protector from 10ka Polymeric Hoursed Metal-Oxide Surge Arrester Lightning Arrester
Model | Rated Voltage | Max continous operation voltage | residual voltage under 8/20μs lightning impulse current | residual voltage under 30/60μs operation impulse current | 2ms rectangular wave flow capacity withstand (A) | 4/10μs high current impulse withstand (kA) |
kV(r.m.s) | ≮kV | |||||
HY10W-3 | 3 | 2.55 | 8 | 8.1 | 250 | 100 |
HY10W-6 | 6 | 5.1 | 16 | 15.5 | 250 | 100 |
HY10W-9 | 9 | 7.65 | 25 | 22 | 250 | 100 |
HY10W-10 | 10 | 8.4 | 27 | 24 | 250 | 100 |
HY10W-11 | 11 | 9.4 | 30 | 27.5 | 250 | 100 |
HY10W-12 | 12 | 10.2 | 33 | 29 | 250 | 100 |
HY10W-15 | 15 | 12.7 | 41 | 35 | 250 | 100 |
HY10W-18 | 18 | 15.3 | 49 | 42.5 | 250 | 100 |
HY10W-21 | 21 | 17 | 57 | 49.5 | 250 | 100 |
HY10W-24 | 24 | 19.5 | 65 | 56 | 250 | 100 |
HY10W-27 | 27 | 22 | 74 | 63.5 | 250 | 100 |
HY10W-30 | 30 | 24.4 | 82 | 72 | 250 | 100 |
HY10W-33 | 33 | 27.5 | 90 | 79 | 250 | 100 |
HY10W-36 | 36 | 29 | 98 | 84 | 250 | 100 |
HY10W-39 | 39 | 31.5 | 103 | 94 | 250 | 100 |
HY10W-42 | 42 | 33.6 | 111 | 101 | 250 | 100 |
HY10W-45 | 45 | 36.5 | 119 | 105 | 250 | 100 |
HY10W-48 | 48 | 39 | 127 | 110 | 250 | 100 |
HY10W-51 | 51 | 40.8 | 134 | 115 | 250 | 100 |
HY10W-54 | 54 | 42 | 143 | 119 | 250 | 100 |
HY10W-60 | 60 | 48 | 159 | 132 | 250 | 100 |