CT PT Analysis Instrument Current and Potential Transformer Analyzer Characteristics Comprehensive Tester
Item Name | GDVA-405 CE Certificate Automatic Current Transformer CT and PT Potentional Transformer Tester | |
Test Standards | IEC60044-1, IEC60044-6, IEC60044-2, IEC60044-5, C57.13 | |
Power Supply | AC220V±10%, 50/60Hz±10% | |
Voltage Output | 0.1~180V (AC) | |
Current Output | 0.001~5A(RMS) | |
Power Output | 500VA | |
Max. Knee Voltage Measurement | 45KV | |
Current Measurement | Range | 0~10A (automatically change range in 0.1/0.4/2/10A) |
Error | <±0.1%+0.01%FS | |
Voltage Measurement | Range | 0~200V (automatically change range in 1V/10V/70V/200V) |
Error | < ±0.1%+0.01%FS | |
Turns ratio measurement Range | 1~35000 | |
1~2000, error<0.05% | ||
2000~5000,error<0.1% | ||
5000~35000,error<0.2% | ||
Phase Measurement | Error | ±2min |
Resolution | 0.01min | |
Winding Resistance Measurement | Range | 0~8kΩ (automatically change range in 2 Ohm/20 Ohm/80 Ohm/800 Ohm/8k Ohm) |
Error | < 0.2%RDG+0.02%FS | |
Maximum Resolution : 0.1mΩ | ||
Temperature Measurement | -50~100 Celsius degree; error<3 Celsius degree | |
CT Secondary Burden | Range | 0~160ohm (automatically change range in 2 Ohm/20 Ohm/80 Ohm/160 Ohm) |
Error | <0.2%RDG+0.02%FS | |
Maximum Resolution : 0.001ohm | ||
PT Secondary Burden | Error | 0~80k Ohm (automatically change range in 800 Ohm/8k Ohm/80k Ohm) |
Maximum | <0.2%RDG+0.02%FS | |
Resolution | 0.1ohm | |
PT Ratio Measurement | Range | 1~35000, |
1~10000 error<0.1%, | ||
10000~35000 error<0.2% | ||
PT Ratio Error Measurement :Typical Error<0.05%, Maximum Error<0.1% | ||
PT Phase Angle Measurement Maximum Error < 3min | ||
Make evaluation for test results according to selected standards | ||
Make word report for test result | ||
Make word reports one time for multi-group test records on the PC | ||
Calculate the ratio errors and phase angle errors at rated burden and working burden in one time test | ||
Compare excitation curves with saved excitation curves in the same window | ||
Memory Capacity | >1000 groups test results | |
Working Condition Temperature | -10ºC~50ºC; moist ≤90% |