China Jdzc-10 High Voltage Potential Transformer, Find details about China Outdoor High-Voltage Transformer, Voltage Transformer from Jdzc-10 High Voltage Potential Transformer
Technical Data: | IEC61869-1,61869-3 |
Power factor of load:COSΦ=0.8(lagging); | |
Rated frequency:50Hz or 60Hz; | |
Anti-Pollution grade:Class II; | |
Ambient temperature:-25ºC-40ºC,daily average temperature not more than 30ºC; | |
Altitude:≤2000M; |
Type | Rated Primary voltage | Rated Secondary voltage | Auxiliary winding voltage | Rated output | Thermal limitiong output | rated insulating level | |||||||
0.2 | 0.5 | 6P | |||||||||||
JDZW-10R | 3000/√3 | 100/√3 | 100/3 | 30 | 50 | 120 | 800 | 3.6/25/40 | |||||
6000/√3 | 100/√3 | 100/3 | 30 | 50 | 120 | 7.2/32/60 | |||||||
100/√3/100/√3 | 30 | 50 | 800 | ||||||||||
10000/√3 | 100/√3 | 100/3 | 30 | 50 | 120 | 800 | 12/42/75 | ||||||
100/√3/100/√3 | 15 | 15 | 800 |