China Current and Potential Transformer Characteristics Comprehensive Vt CT PT Tester, Find details about China Testing Equipment, Test Equipment from Current and Potential Transformer Characteristics Comprehensive Vt CT PT Tester
Operational Power Supply: | AC220V±20V, 50~60Hz | |
Equipment Output Waveform: | 0 ~ 2500Vrms, 5ARMS (20A peak) Note: 0 ~ 5A is the true value, and greater than 5A ~ 20A is the calculated value | |
Large-current output | 0~1000A | |
Excitation precision | ≤0.5% (0.2%* reading +0.3%* range) | |
Secondary winding Resistance measurement | Range: | 0.1~300Ω |
Accuracy: | ≤0.5% (0.2%* reading +0.3%* range) | |
Secondary actual Load measurement | Range: | 5~1000VA |
Accuracy: | ≤0.5% (0.2%* reading +0.3%* range) ±0.1VA | |
Phase measuring (Angle difference) | Accuracy: | ±4min |
Resolution: | 0.1min | |
Ratio error | Accuracy: | 0.05% |
CT ratio measurement | Range: | 5~10000A/5A(5000A/1A) |
Accuracy: | ≤0.5% | |
PT ratio measurement range | Range: | ≤500KV |
Accuracy: | ≤0.5% | |
Operating Temperature: | -10ºC~+40ºC | |
Relative Humidity: | <90RH% | |
Altitude | ≤1000m | |
Overall Dimension(Length×Width×Height): | 410 *260 * 340(mm) | |
Weight: | ≤22 Kg |