China Suntree Brand Sw8 (DW45) Good Quantity 630-6300A Air Circuit Breaker Acb 3p/4p CE Switchgear Circuit Breaker Draw out Type Acb 3 Pole Acb 1000A 2000A, Find details about China Electrical Switch, Air Circuit Breaker from Suntree Brand Sw8 (DW45) Good Quantity 630-6300A Air Circuit Breaker Acb 3p/4p CE Switchgear Circuit Breaker Draw out Type Acb 3 Pole Acb 1000A 2000A
Model | SW8-1000 | SW8-2000 | SW8-3200 | SW8-4000 | SW8-6300 | ||||||||||||||
IEC60947-2 GB/T14048.2 | |||||||||||||||||||
Shell frame level current | Inm(A) | 1000 | 2000 | 3200 | 4000 | 6300 | |||||||||||||
Electrical Performance | |||||||||||||||||||
Number of poles | 3P | 4P | 3P | 4P | 3P | 4P | 3P | 4P | 3P | 4P | |||||||||
Operating frequency | (Hz) | 50 | 50 | 50 | 50 | 50 | |||||||||||||
Rated working voltage | Ue(V) | 400/690 | 400/690 | 400/690 | 400/690 | 400/690 | |||||||||||||
Rated current +40ºC | In(A) | 2,004,006,308,001,000 | 6,308,001,000,125,010,000,000 | 200,025,003,200 | 320,036,004,000 | 400,050,006,300 | |||||||||||||
Rated insulation voltage | Ui(V) | 800 | 1000 | 1000 | 1000 | 1000 | |||||||||||||
Rated impulse withstand voltage | Uimp(kV) | 8 | 12 | 12 | 12 | 12 | |||||||||||||
Pole N rated current | In(A) | 100% | 100% | 100% | 100% | 100% | |||||||||||||
Breaking type | - | M | H | - | - | ||||||||||||||
Rated ultimate short-circuit segmentation capability | Icu(kA) | 400V | 50 | 85 | 100 | 100 | 120 | ||||||||||||
690V | 30 | 50 | 65 | 65 | 80 | ||||||||||||||
Rated running short-circuit segmentation capability | Ics(kA) | 400V | 35 | 50 | 65 | 65 | 65 | 80 | |||||||||||
690V | 25 | 40 | 50 | 50 | 70 | ||||||||||||||
Rated short-time withstand current(effective value) | Icw(kA) | 400V | 35(1s) | 50(1S) | 65(1S) | 65(1S) | 65(1S) | 85(1S) | |||||||||||
690V | 25(1S) | 40(1S) | 50(1S) | 50(1S) | 65(1S) | ||||||||||||||
Operating time | (ms) | Disjunction | 23~32 | 23~32 | 23-32 | 23-32 | 23-32 | ||||||||||||
Switch off | <70 | <70 | <70 | <70 | <70 | ||||||||||||||
Flashover distance | (mm) | 0 | 0 | 0 | 0 | 0 | |||||||||||||
Service life | for mechanical | Free of maintenance | 15000 | 10000 | 5000 | 5000 | 3000 | ||||||||||||
service life(times) | Maintained | 30000 | 20000 | 10000 | 10000 | 6000 | |||||||||||||
Electrical life (times) | 400V | 6000 | 6500 | 3000 | 1500 | 500 | |||||||||||||
900V | 3000 | 3000 | 1500 | 750 | 300 | ||||||||||||||
Separating function (drawer type) | O | O | O | O | O | ||||||||||||||
Protection: | |||||||||||||||||||
Intelligent controller | O | O | O | O | O | ||||||||||||||
Pole N protection capability (only 4P and 3P+N) | O | O | O | O | O | ||||||||||||||
Connection And Installation: | |||||||||||||||||||
Utilization category | B | B | B | B | B | ||||||||||||||
Installation category | Circuit breaker(including the primary lateral line circle) | IV | IV | IV | IV | IV | |||||||||||||
Auxiliary circuit (except for primary coil RB) | III | III | III | III | III | ||||||||||||||
Pollution degree | 3 | 3 | 3 | 3 | 3 | ||||||||||||||
Connection mode Horizontal | Vertical/Horizontal | Vertical/Horizontal | Vertical/Horizontal | Vertical/Horizontal | Vertical/Horizontal | ||||||||||||||
Incoming line method | Up/Down | Up/Down | Up/Down | Up/Down | Up/Down | ||||||||||||||
Installation Method | Fixed Type (3/4) | Drawer Type(3/4) | Fixed Type (3/4) | Drawer Type(3/4) | Fixed Type (3/4) | Drawer Type(3/4) | Fixed Type (3) | Drawer Type(3/4) | Fixed Type (3/4) | Drawer Type(3) | |||||||||
Outline Dimension | Width(W) | 274/344 | 284/354 | 362/457 | 407/500 | 422/537 | 435/550 | 537 | 550/790 | 813/928 | 928 | ||||||||
Depth(D) | 289 | 373 | 373 | 461 | 363 | 494 | 424 | 494/504 | 504 | 504 | |||||||||
Height(H) | 315 | 362 | 402 | 432 | 402 | 432 | 402 | 432/452 | 433 | 433 | |||||||||
O Standard Configuration | O Optional | -None |
1.With drawable-breaker; | 2.Fixed-breaker | 3.Intelligent controller; | 4.Operating mechanism; | 5.Auxiliary contact |
6.Locking-device | 7.Arc chute; | 8.Secondary connecting part; | 9.Wire-cable mechanical interlock; | 10.Connecting-rod type mechanical interlock; |
11.Shunt release; | 12.Closing electromagnet; | 13.Under-voltage release | 14.Motor-driven energy-storage mechanism; | 15.Handle; |
16.Fixed plate. |