China Three Phase Duplex Winding Distribution Transformer, Find details about China Power Transformer, Electric Transformer from Three Phase Duplex Winding Distribution Transformer
Rated capacity (kVA) | High voltage(kV) | Tap range | Low voltage (kV) | connected group label | No-load loss(w) | Load loss (75ºC)(W) | No-load current(%) | Impedance voltage(%) | Sound power level(dB) | Exterior size (L*W*H) Install4-Φ18 | Total weight(kg) |
30 | 6 6.3 6.6 10 10.5 11 | ±2*2.5 ±5 | 0.4 | Dyn11 Yyn0 Yzn11 | 80 | 505/480 | 0.3 | 4 | 48 | 800*500*850 | 330 |
50 | 100 | 730/695 | 0.24 | 48 | 820*550*850 | 380 | |||||
63 | 110 | 870/830 | 0.23 | 48 | 835*580*850 | 410 | |||||
80 | 130 | 1050/1000 | 0.22 | 49 | 840*600*880 | 430 | |||||
100 | 150 | 1260/1200 | 0.21 | 49 | 860*600*890 | 460 | |||||
125 | 170 | 1510/1440 | 0.2 | 50 | 1020*660*880 | 590 | |||||
160 | 200 | 1850/1760 | 0.19 | 50 | 1035*660*950 | 650 | |||||
200 | 240 | 2180/2080 | 0.18 | 52 | 1040*680*980 | 710 | |||||
250 | 290 | 2560/2440 | 0.17 | 52 | 1140*740*1010 | 850 | |||||
315 | 340 | 3060/2920 | 0.16 | 54 | 1160*760*1150 | 970 | |||||
400 | 410 | 3610/3440 | 0.16 | 54 | 1230*800*1200 | 1130 | |||||
500 | 480 | 4330/4120 | 0.16 | 56 | 1320*900*1200 | 1335 | |||||
630 | Dyn11 Yyn0 | 570 | 4960 | 0.15 | 4.5 | 56 | 1420*920*1230 | 1630 | |||
800 | 700 | 6000 | 0.15 | 58 | 1480*1000*1285 | 1950 | |||||
1000 | 830 | 8240 | 0.14 | 58 | 1600*1100*1330 | 2205 | |||||
1250 | 970 | 9600 | 0.13 | 60 | 1655*1135*1375 | 2565 | |||||
1600 | 1170 | 11600 | 0.12 | 60 | 1815*1260*1450 | 3100 | |||||
2000 | 1550 | 14600 | 0.11 | 5 | 62 | 1920*1305*1510 | 3785 | ||||
2500 | 1830 | 16900 | 0.11 | 62 | 2120*1430*1575 | 4570 |