China Lightning Protection Zinc Oxide Varistors Lightning Arrester with Porcelain Insulator, Find details about China Surge Arrester, Bushing Insulator from Lightning Protection Zinc Oxide Varistors Lightning Arrester with Porcelain Insulator
echnical Parameters:
Type | Y10W5-120/313 | ||
Rated voltage---------kV | 120 | 4/10µS High current impulse kA | 100 |
MOCV ----------------kV | 98 | Lightning impulse withstand -----------------------kV | 550 |
Nominal Current-------kV | 10 | Power frequency voltage withstand(dry/wet)kV | 230 |
Residual voltage of steep impulse----at 5kA(kV) | 360 | 0.1S TOV--------------kV | 144 |
8/20µS Residual voltage of lightning impulse current kV(Peak value)-----at 5kA(kV) | 304 | 1S TOV----------------kV | 138 |
Residual voltage of switching impulse current kV (peak value)----at 1kA (kV) | 239 | 10S TOV---------------kV | 132 |
1mA D.C reference voltage (kV) | 174 | 1200S TOV-------------kV | 120 |
Line discharge level | 3 | Creepage distance ----mm | 3906 |
2mS long duration impulse current A | 850 | Material employed in series non-linear resistor | Zinc Oxide |