TECHNICAL SPECIFICATIONS CIRCUIT BREAKER | ||||
ITEM | CHARACTERISTICS | UNIT | TOTORAS (1) ESMERALDAS (1) PORTOVIEJO(1) | OFFERED TECHNICAL SPECIFICATIONS |
TYPE - C | ||||
1 | TYPE OF CIRCUIT BREAKER REQUIRED | |||
1.1 | Type (similar to) | 170 MHM-20 C | LW-170 | |
1.2 | Detail type | Tank Live, Single-Phase in SF6 | Tank Live, Single-Phase in SF6 | |
1.3 | Use | GeneraL | GeneraL | |
1.4 | Opening | Single-Phase | Single-Phase | |
1.5 | Arc extinguishing medium | SF6 | SF6 | |
2 | REQUIRED QUANTITY | 3 | 3 | |
3 | INSTALLATION | Outdoor | Outdoor | |
4 | CHARACTERISTICS OF CIRCUIT BREAKER | |||
4.1 | Number of Poles | 3 | 3 | |
4.2 | Nominal voltage | kV | 170 | 170 |
4.3 | Dielectric strength and atmospheric impulse at sea level | kVpic | 750 | 750 |
4.4 | Industrial frequency dielectric, a minute at sea level | kV | 325 | 325 |
4.5 | Minimum distance of contouring (pollution level III) | mm | 3625 | 3625 |
4.6 | Nominal frequency | Hz | 60 | 60 |
4.7 | Rated normal current | A | 1250 | 1250 |
4.8 | Nominal current interruption of line vacuum | A | 63 | 63 |
4.9 | Nominal current interruption of cable in vacuum | A | 160 | 160 |
4.10 | Rated short circuit interruption | |||
-Effective value of the alternating component | kArms | 20 | 20 | |
4.11 | Opening of the first polo factor | 1.3 | 1.3 | |
4.12 | Reason for increase of the recovery voltage to 100% of the rated breakig capacity | kV/us | 2 | 2 |
4.13 | Nominal capacity of closing short | kA | 104 | 104 |
4.14 | Rated operating sequence | O- 0.3"/CO- 3'-CO | O- 0.3"/CO- 3'-CO | |
4.15 | Rated duration of short circuit | s | 1 | 1 |
4.16 | Rated interruption in discordance of Poles | kA | 10 | 10 |
4.17 | Maximum total interrupt time | ms | 50 | 50 |
4.18 | Mechanism of operation (closing - Shooting) | Engine - Spring | Engine - Spring | |
4.19 | Drive mechanism | Single-Phase | Single-Phase | |
4.20 | Number of circuits independent of firing 125 Vdc | 2 | 2 | |
4.21 | Mechanical strength (standard IEC 62271-100) class | M2 | M2 | |
4.22 | Kind of electrical resistance (standard IEC 62271-100) | E2 | E2 | |
4.23 | Voltage control and engine | VDC | 125 | 125 |
4.24 | Voltage of auxiliary services | VAC | 120 | 120 |
4.25 | Terminal connector for AAC 1033 kcmil conductor | YES/NO | Yes | Yes |
4.26 | Insulators material | Porcelain | Porcelain | |
4.27 | Metal support structure | YES/NO | Yes | Yes |