DC96V Double Conversion Online UPS 15kVA

China DC96V Double Conversion Online UPS 15kVA, Find details about China 15kva Ups, Low Frequency Ups from DC96V Double Conversion Online UPS 15kVA

Model NO.
MD-A15KL
Power Factor
0.8
Display
LCD
CE
Yes
ISO
Yes
Warranty
1 Year
Plug/Socket
Terminal Block
DC
48/192V
Trademark
MUST
Specification
CE/iso
Origin
China
HS Code
8504402000
Model NO.
MD-A15KL
Power Factor
0.8
Display
LCD
CE
Yes
ISO
Yes
Warranty
1 Year
Plug/Socket
Terminal Block
DC
48/192V
Trademark
MUST
Specification
CE/iso
Origin
China
HS Code
8504402000
Features:

1. True on-line double conversion(AC/DC, DC/AC) UPS
2. Extremely wide input voltage range and ultra-strong capability against overload
3. IGBT mosfet and SPWM modulation technologies applied
4. Built-in isolated transformer and static switch
5. Built-in battery charger
6. User-friendly digital LED/LCD for system information available at a glance
7. Strong self-diagnosis and low battery voltage, over heat and circiut short protection functions
8. Smart RS232 port for computer monitoring
9. Can cold-start directly and smart operation for users
10. Audible alarm system for faults
Model 1KL 2KL 3KL 6KL 8KL 10KL 15KL 20KL
VA rating 1KVA 2KVA 3KVA 6KVA 8KVA 10KVA 15KVA 20KVA
Working mode and principle
True on–line
AC input
Phase L + N + G
Voltage 110/120 or 220/230/240VAC ± 25%
Frequency 50/60Hz ± 5%
Power factor 0.92 (with input filter)
Soft start 0 – 100%  5 s (non-shock current)
Bypass input
Phase Single phase
Voltage 110/120V or 220/230/240VAC ± 20%
Frequency 50/60Hz ± 5%
Transfer time 0 UPS, Inverter / bypass (overload)
DC system
DC voltage 48V 192V (rated voltage)
42V 168V (end voltage)
AC output
Phase Single phase
Voltage 110/120V or 220/230/240VAC ± 1%(stable load),110V/120V or 220/230/240VAC ± 5%(load fluctuation)
Frequency 50/60Hz ± 0.05% (battery mode)
Power factor 0.8
Wave form Pure sine wave
Harmonic distortion Less than 3%(linear load), less than 5%(non-linear load)
Dynamic Dynamic load voltage instantaneous change(0-100%)   ± 5%
Time Instantaneous recover time  less than 10 mS
Overload 125% for 10 min; 150% for 1min,200% for 100S
Cooling Force ventilation
System
Efficiency 85% 86% 90% 92% 93% 93% 93% 95%
Communication RS232,RS485,SNMP (options)
Temperature 0-40c (working)
Humidity 30-90%
Working height Less than 1000m (1% power reduce per 100 m height rising, Max. 4000m)
Noise(db) 40-55 45-60 50-65
Dimension(mm) 210×500×530 220x560x610 305×585×740 380×680×950
N.W.(kgs) 42.5 49  56 56.4 63.2 93 145.8 172.8
G.W.(kgs) 50.5 57 64 66.2  73 106.3 165 186.2