Factory Price for Programmable Logic Controller HMI PLC (Programmable Relay PR- 12AC Starter Kit)

China Factory Price for Programmable Logic Controller HMI PLC (Programmable Relay PR-12AC Starter Kit), Find details about China Programmable Logic Controller, HMI from Factory Price for Programmable Logic Controller HMI PLC (Programmable Relay PR-12AC Starter Kit)

Model NO.
PR-12AC Starter Kit
Material
Fr-ABS
Inputs
8 Digital Inputs
Outputs
4 Relays(10A)
Trademark
RIEVTECH
Transport Package
Standard Export Carton
Specification
CE, RoHs, SGS
Origin
Nanjing, China
HS Code
8537101190
Model NO.
PR-12AC Starter Kit
Material
Fr-ABS
Inputs
8 Digital Inputs
Outputs
4 Relays(10A)
Trademark
RIEVTECH
Transport Package
Standard Export Carton
Specification
CE, RoHs, SGS
Origin
Nanjing, China
HS Code
8537101190

PR-12 Series highlights at a glance

*Customizable Start-up page / screen 
*4-line, 16-character configurable backlight display 
*Modify parameters via Keypad panel without downloading new program
*Various blocks' different parameters can be displayed on one screen / page simultaneously
*Randomly specify a specific page to display the IO status of the CPU
*Alarm page can record and display the exact alarm occurrence time 
*Programmable up to 64 (user defined) screens / pages 
*Modbus RTU &ASCII protocol supported. 
*Unit Size allows for DIN-rail mounting together with commonly used breakers in building automation applications. 
*Retentive memory capability standard feature on the PR-12 model. 
*It's optional for xLogic to act as slave or master in Modbus RTU communication network.
*Extra large program capacity (512 function blocks available) 
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
GENERAL SPECIFICATIONS
Timers  : 512
Counters  : 512
Function Blocks : 512
Operation  temp.: -20 °C -55 °C
Storage :-40 °C -70 °C
Protection : IP20(Non-waterproof) 
RTC accuracy : MAX ±2S/day
RTC Backup at 25 °C : 20 days
Program and settings Backup :10 years
Data Power-off retentivity : 10 years
Dimensions :  72*90*61 (Unit, mm)
Certificate : CE
Installation : 35mm-DIN rail or screw for installation
Modify parameters via keypad LCD:  yes
Expansion capacity : NO 
Password protection : 4-digit number password protection or disable program upload function
Communication interface : 1 Program/RS232 port ( TTL interface)
Communication protocol : Modbus RTU/ASCII
It's optional for xLogic to be either slave or master in Modbus network.

Technical Index
 
Power supply:
Nominal voltageAC110V-240V
Operating limits AC85 - 265 V
The main frequency range 47-63Hz
Max. absorbed power48.5mA (85V ac) ; 35mA (265V ac)
Isolation voltage1780V AC
Protection against polarity inversionsYes
Input parameters:
Input No8 ( I1-I8 )
Digital input 8 ( I1-I8 )
Analogue input None
Input voltageAC110-240V
Input signal0 AC0-40V ;<0.03mA
Input signal1 AC79-240V; >0.06mA
Input Response TimeDelay time at 0 to 1:
120V AC :Typ. 50 ms
240V AC :Typ. 30 ms
Delay time at 1 to 0:
120V AC :Typ. 90 ms 
240V AC :Typ.100 ms
Maximum counting frequencyTyp. 4Hz
Sensor typeContact or 3-wire PNP
Isolation between power supply and inputsNone
Isolation between inputsNone
Protection against polarity inversionsYes
Output parameters:
Output No.4 (Q1-Q4)
Output type Relay output 
Continuous currentResistive load 10A/Inductive load 2A
Max. breaking voltageAC 250 V
DC 110 V
Max. Allowable Power Force1250VA 
300W
Electrical durability Expectancy105 Operations at Rated Resistive Load
Mechanical life107 Operations at No Load condition
Response timeOperate Time : 15 mSec. Max.
Release Time : 10 mSec. Max.
Built-in protectionsAgainst short-circuits: None
Against overvoltages and overloads: None
Switch frequency:
Mechanism 10Hz
Resistor/light load 2Hz
Sensitive load 0.5Hz
Other parameters:
WeightApprox.300g

Technical Index 
 
Power supply:
Nominal voltageAC110V-240V
Operating limits AC85 - 265 V
The main frequency range 47-63Hz
Max. absorbed power48.5mA (85V ac) ; 35mA (265V ac)
Isolation voltage1780V AC
Protection against polarity inversionsYes
Input parameters:
Input No8 ( I1-I8 )
Digital input 8 ( I1-I8 )
Analogue input None
Input voltageAC110-240V
Input signal0 AC0-40V ;<0.03mA
Input signal1 AC79-240V; >0.06mA
Input Response TimeDelay time at 0 to 1:
120V AC :Typ. 50 ms
240V AC :Typ. 30 ms
Delay time at 1 to 0:
120V AC :Typ. 90 ms 
240V AC :Typ.100 ms
Maximum counting frequencyTyp. 4Hz
Sensor typeContact or 3-wire PNP
Isolation between power supply and inputsNone
Isolation between inputsNone
Protection against polarity inversionsYes
Output parameters:
Output No.4 (Q1-Q4)
Output type Relay output 
Continuous currentResistive load 10A/Inductive load 2A
Max. breaking voltageAC 250 V
DC 110 V
Max. Allowable Power Force1250VA 
300W
Electrical durability Expectancy10Operations at Rated Resistive Load
Mechanical life107 Operations at No Load condition
Response timeOperate Time : 15 mSec. Max.
Release Time : 10 mSec. Max.
Built-in protectionsAgainst short-circuits: None
Against overvoltages and overloads: None
Switch frequency:
Mechanism 10Hz
Resistor/light load 2Hz
Sensitive load 0.5Hz
Other parameters:
WeightApprox.300g
Factory Price for Programmable Logic Controller HMI PLC (Programmable Relay PR-12AC Starter Kit)
Factory Price for Programmable Logic Controller HMI PLC (Programmable Relay PR-12AC Starter Kit)
Factory Price for Programmable Logic Controller HMI PLC (Programmable Relay PR-12AC Starter Kit)