High Voltage Circuit Breaker with Line Protection Relay 33kv

China High Voltage Circuit Breaker with Line Protection Relay 33kv, Find details about China Recloser, Reclosurer from High Voltage Circuit Breaker with Line Protection Relay 33kv

Model NO.
RCW38N
Poles Number
3
Type
Circuit Breaker
Function
Overcurrent Protection, Circuit-Breaker Failure P
Certification
ISO9001-2000
Trademark
Rockwill
Transport Package
Wooden
Specification
IEC
Origin
China
HS Code
85352100
Model NO.
RCW38N
Poles Number
3
Type
Circuit Breaker
Function
Overcurrent Protection, Circuit-Breaker Failure P
Certification
ISO9001-2000
Trademark
Rockwill
Transport Package
Wooden
Specification
IEC
Origin
China
HS Code
85352100
RCW38M type pole mounted circuit recloser

RCW38M is patented type recloser by Rockwill ELectric.Which has innovation design for magnetic actuator and addtional manual closing for prevent defect of auxiliary power outage moreove the circuit breaker in opening situation case.

RCW38M series recloser is very relieable products, suitable for important position performance.

The main difference between RCW38M and RCW38N:
Type
Close energy
Open energy
Mechanical life
RCW38M
By capacitor charging, fast within 1 S
Need By capacitor release
More than 60,000 times
RCW38N
By motor charging spring, long time 7S~15S
No need capacitor
10,000 times

++++General:

     Rockwill Electric strives to bring our customers the latest technology and competitive pricing and best service for distribution automatic.

The RCW series automatic circuit reclosers can use on overhead distribution lines as well as distribution substation applications for all voltage classes 11kV up to 38kV at 50/60HZ power system. and its rated current can reach 1250A.

The RCW series automatic circuit reclosers integrates the functions of control, protection, measurement, communication, fault detection, on-line monitoring of closing or opening.

++++Service environment:

   a) Air temperature: Maximum temperature: +85ºC; Minimum temperature:-45ºC
   b) Humidity: Monthly average humidity 95%; Daily average humidity 90% .
   c) Altitude above sea level: Maximum installation altitude:2500mor more higher.
   d) Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.
   e) No frequent violent shake

Main technical data

 
No.itemunitdata
1Rated voltagekV152738
2Rated currentA6301250800
3Rated frequencyHz50/60
4Power frequency 1 minDrykV506585
WetkV455575
5Lightning impulse withstand voltage(peak value) alternate, opposite/fracturekV100125/150170
6Rated short circuit breaking currentkA2016/2512.5
7Rated short current switching current(peak value)kA5040/6331.5
8Rated peak value withstand currentkA5040/6331.5
94S short time withstand currentkA2016/2512.5
10Rated operating circulate O-T1-CO-12s-CO-12s-CO-12s-CO
11Breaking current frequency under rated short circuittimes30
12Mechanism lifetimes10000
13Secondary loop 1 min power frequency withstand voltage 2
High Voltage Circuit Breaker with Line Protection Relay 33kv
High Voltage Circuit Breaker with Line Protection Relay 33kvHigh Voltage Circuit Breaker with Line Protection Relay 33kv
High Voltage Circuit Breaker with Line Protection Relay 33kv
 
High Voltage Circuit Breaker with Line Protection Relay 33kv
High Voltage Circuit Breaker with Line Protection Relay 33kv
High Voltage Circuit Breaker with Line Protection Relay 33kv
High Voltage Circuit Breaker with Line Protection Relay 33kv
High Voltage Circuit Breaker with Line Protection Relay 33kv