China Cotrust Cth200 Basic PLC H224 14di/10do Relay Output Ethernet Port, Find details about China PLC, Ethernet Port from Cotrust Cth200 Basic PLC H224 14di/10do Relay Output Ethernet Port
Order Data
Specification | Order No. |
CPU H224 basic:12KB program memory/8KB data memory,220VAC power supply,14DI*10DO relay output,2A,1*PPI,1*FPORT,1*Ethernet port,expansion module and expansion board are not supported. | CTH2 214-1BA33-0X24 |
Performance Parameters
Physical Features | |
Dimension(W×H×D) | 137×80×62mm |
Power dissipation | 7W |
Memory Features | |
Program memory | 8KB+4KB |
Data memory | 8KB |
General Features | |
Timers total 1ms 10ms 100ms | 256 4 16 236 |
Counters total | 256 |
Internal memory bits | 256 |
Stored permanently on power down | Data permanent stored |
Sequential control relay (S) | 256 |
Time Interrupts | 2 with 1ms resolution |
Edge Interrupts | 4 rising edges and/ or 4 falling edges |
Analog adjustment | Non |
Boolean execution speed | 0.22µs |
Float execution speed | 12µs |
Clock | embedded ,precision ±120s/m |
BD expansion board interface number | 1 |
System indicator | 3,STOP,RUN,SF |
RUN/STOP dial code | Yes,2 |
Programming card | Support |
Memory card | Non Support |
Rated input voltage | 24VDC |
Power supply Native and extended bus+5V +24V | 660mA 200mA |
Integrated Communication Function | |
Communication Interface | 2 communication ports ,PORT0:PPI/Free port,RS485;FPORT0:PPI/Free port,RS485 |
PPI baud rates(baud) | 9.6k,19.2k and 187.5k |
Freeport baud rates(baud) | 1.2k ~ 115.2k |
Maximum cable length Isolated repeater applied Isolated repeater unapplied | When it is 1000 m, baud rate is 187.5k; when it is 1200 m, 38.4k. 50m |
Maximum number of stations | 32 stations per segment,126 stations per network |
Maximum number of masters | 32 |
Physical interface | 2 RS485 port |
Isolation | Non |
Ethernet Function | |
Communication port | 1 Ethernet port |
Communication standard | IEEE802.3 standard |
Communication speed | 10Mbps and 100Mbps self-adaption |
Adaptive cross connection | Non support |
Interface to industrial Ethernet(10/100Mbps) | RJ45 port |
Protocol type | UDP/TCP protocol Support MICO Ethernet programming, support Ethernet communication between PLC. |
Collocation method | Support the upper computer through the Ethernet port search PLC, support the mouth download system configuration. |
Max Connections | Each PLC supports up to 8 UDP connections and up to 4 TCP connections. |
The maximum number of IT connections | 8 UDP_PPI connections, with 4 master stations and 4 slave stations. 4 ModBus_TCP connections, 2 master stations and 2 slave stations. |
User data number | Up to 200 bytes are used for TCP/IP transmission. Up to 240 bytes are used for ModBus_TCP transport. |
Port | local:1~65535 remote server:8888 |
Boot time or restart time after reset | 3 seconds |
Indicator lamp | Green RMC indicator: on: remote control in effect, off: remote control out Green Ethernet indicator: on: connection, flicker: transmission; out: not connected |
Maximum cable length | 100m |
Isolation | Communication port isolation |
I/O Features | |
Number of integrated digital inputs | 14 |
Input type | Sink/Source |
Number of integrated digital outputs | 10 |
Output type | Relay dry connect |
Digital I/O mapping domain | 128DI/1280DQ |
Analog I/O mapping domain | 32AI/32AQ |
Maximum number of expandable I/O module | 7 |
Maximum digital I/O configuration | IO:256(128DI/128DO) |
Maximum analog I/O configuration | 64(32AI/32AQ) |
Pulse catch inputs | 14 |
High-speed counters Total Uniphase counters Bi-phase counters | 4 4×50KHz 1×30KHz |
Digital Input Features | |
Number of integrated digital input | 14 |
Input type | Sink/ Source |
Rated voltage | 24V DC |
Input voltage range | 20.4-28.8V DC |
Surge voltage | 35V DC,continuously 0.5s |
Logical 1 Signal (minimum) Logical 0 Signal (Maximum) | 15 VDC,2.5mA 5 VDC,1mA |
Allowable leakage current | 1mA |
Input filter | 3.4ms and 6.4ms |
Isolation(field side to logical circuit) | 500V AC,1min |
Simultaneous input | 14 |
Maximum cable length Shielded Unshielded | 500 M(standard input) 50 M(high-speed counters input) 300 M(standard input) |
Digital Output Features | |
Number of integrated digital output | 10 |
Output type | Relay dry connect |
Rated voltage | 24VDC or 110V/220VAC |
Output voltage range | 5~30VDC:5~250VAC |
Logical 1 Signal (minimum) | - |
Logical 0 Signal (Maximum) | - |
Rated current per point | 2A |
Rated current for each common point | 8A |
Leakage current (maximum) | - |
Surge current(Maximum) | 7A |
Lamp load (maximum) | 30W DC/200W AC |
On resistance (contact) | 0.2Ω |
Isolation(field side to logical circuit) | - |
Delay | Off to on:- on to off:- |
Contact life at rated load | 100000 times on and off |
Simultaneous input | All output point |
Parallel output | Non |
Maximum cable length Shielded Unshielded | 500m 150m |
RS485 communication port definition
Connector | PIN | PORT0(RS485) | FPORT0(RS485) |
| 1 | Shell Grounded | Shell Grounded |
2 | logically | logically | |
3 | RS485+signal B | RS485+signal B | |
4 | Send the application RTS | Send the application RTS | |
5 | logically | logically | |
6 | +5V, series connection 100 Ω resistance | +5V, series connection 100 Ω resistance | |
7 | +24V | +24V | |
8 | RS485-signal A | RS485-signal A | |
9 | NC | NC | |
shell | Shell Grounded | Shell Grounded |