2021 R404 Heat Pump Air Cooled Screw Chiller

China 2020 R404 Heat Pump Air Cooled Screw Chiller, Find details about China Chiller, Air Chiller from 2020 R404 Heat Pump Air Cooled Screw Chiller

Model NO.
DSA-720D
Application Fields
Food Processing
Application Machine
Precision Machine Tool
Certification
ISO, CE
Condition
New
Size(mm)
6280*2160*2400
Weight(Kg)
7600
Trademark
DASEN
Transport Package
Standard Wooden Package
Specification
SGS, CE, ISO9001
Origin
Shanghai, China
HS Code
8418692090
Model NO.
DSA-720D
Application Fields
Food Processing
Application Machine
Precision Machine Tool
Certification
ISO, CE
Condition
New
Size(mm)
6280*2160*2400
Weight(Kg)
7600
Trademark
DASEN
Transport Package
Standard Wooden Package
Specification
SGS, CE, ISO9001
Origin
Shanghai, China
HS Code
8418692090
INDUSTRIAL  APPROVED AIR/WATER COOLED CHILLER

1. Our factory in Shanghai-15000 square meters
2020 R404 Heat Pump Air Cooled Screw Chiller


2. Festures for air cooled screw chiller

1) Cooling capacity: 180kw~1520kw

2) Cooling conditions: Chilled water inlet temperature is 12 degrees, outlet temperature is 7 degrees Ambient temperature is 35 degrees

3) Input power: 3P-380V-50Hz, Allowable fluctuate voltage: ± 10%, allowable voltage difference in phase: ± 2%.

4) Measuring noise spot: 2m ahead and 1.5m high in front of chiller with average measurement on four dimensions.

5) Semi-closed 5: 6 asymmetric twin-screw compressor from world-renowned brand, trouble-free operation over 100000hours.

6) Eight stages volume control or 0%-100% automatic regulation.

7) Fluoride-resistant high-performance motor from French.

8) Use PLC microcomputer control from Germany Siemens LCD touch screen, both English and Chinese human-machine interface.

9) Wide range of variable chilled water temperature to meet the industrial requirements throughout whole year.

10) Friendly choose to use environmentally R407C or R134A refrigerant.

11) Free step-down triangle stars starter

12. Dual refrigeration circuits to each other back-up

3. Pictures reference for air cooled screw chiller
2020 R404 Heat Pump Air Cooled Screw Chiller
2020 R404 Heat Pump Air Cooled Screw Chiller
2020 R404 Heat Pump Air Cooled Screw Chiller
2020 R404 Heat Pump Air Cooled Screw Chiller
2020 R404 Heat Pump Air Cooled Screw Chiller
2020 R404 Heat Pump Air Cooled Screw Chiller



4. DASEN Chiller Model List
 
DSA-
Type350S420S445S490S525S545S635S700S745S840S

Nominal cooling capacity
kW350.0420.0445.0490.0525.0545.0635.0700.0745.0840.0
104kcal/h30.136.138.342.145.246.954.660.264.172.2

Nominal heating capacity
kW400.0470.0500.0550.0590.0610.0710.0780.0830.0940.0
104kcal/h34.440.443.047.350.752.561.167.171.480.8
Run controlPLC Use PLC microcomputer control
Power Supply380V/3N/50HZ
Startup typeY-△
(kW) Machine power118.5139.0146.0158.0168.5175.5201.0223.5239.5265.0
(A) Machine operating current212.0248.5261.0282.5301.0314.0359.0400.0428.0473.0
CompressorType5:6 Semi-closed 5:6 asymmetric twin-screw compressor
(kW) Refrigeration power105.0122.0129.0140.0150.5155.0179.0198.5211.0237.0
(A) Refrigeration current177.0205.5217.0235.0253.0261.0301.0334.0354.0398.5
(kW) Heating power 101.0117.0123.5134.0144.0148.5171.5190.0202.0227.0
(A) Heating current170.0197.0208.0225.0242.5250.0288.0320.0334.0382.0
Energy regulation0-25%-50%-75%-100%
EvaporatorTypePipe dry high efficiency heat exchanger
(m3/h) Flow60.172.276.584.290.293.6109.1120.3128.0144.3
(kPa) Water pressure drop52.055.055.058.060.060.062.070.075.080.0
(mm) Interface sizeDN125DN150DN150
CondenserTypeEfficiency copper pipe and aluminum foil wing heat exchanger
Quantity of fans 8101010101212121616
Stand-alone power 1.71.71.71.81.81.71.81.81.81.8
RefrigerantTypeR22
(kg) Refrigerant volume70.085.090.0100.0105.0110.0130.0140.0150.0170.0

Overall dimensions
(mm) Length4200450050005800580060006200650080008000
(mm) Width2200220022002200220022002200220022002200
(mm) Height2250230023502350235023502450245023502450
weight(kg) Machine weight4350455048505300550058006250655073507500
(kg) Operating weight4650485051505600580061006550685076507800