Model | CX1K | CX1KL | CX2K | CX2KL | CX3K | CX3KL | ||
Capacity | VA/W | 1000VA/800W | 1000VA/800W | 2000VA/1600W | 2000VA/1600W | 3000VA/2400W | 3000VA/2400W | |
Input | Nominal Voltage | 200/208/220/230/240VAC | ||||||
Voltage Range | 115~300VAC | |||||||
Harmonic Distortion | <10% (Nonlinear load) | |||||||
Power Factor | 0.98 | 0.98 | 0.98 | 0.98 | 0.98 | 0.98 | ||
Frequency Range | 50Hz: 46~54Hz;60Hz: 56~64Hz | |||||||
Output | Voltage | 200/ 208/ 220/ 230/ 240* (1±1%)VAC | ||||||
Frequency | 50/60Hz (Adjustable); 50Hz AC Mode: Follow AC Mode (AC Range 46~54Hz); Battery Mode: 50Hz (1±0.2%) 60Hz AC Mode: Follow AC Mode (AC Range 56~64Hz); Battery Mode: 60Hz (1±0.2%) | |||||||
Wave Form | Pure sine wave | |||||||
Power Factor | 0.8 | 0.8 | 0.8 | 0.8 | 0.8 | 0.8 | ||
Harmonic Distortion | ≤4% (Linear load); ≤7% (Nonlinear load) | |||||||
Overload Capacity | 105%~150% 45S~25S; 150%~200% 25s~300ms; ≥200% 200ms | |||||||
Current Crest Ratio | 3:1 | |||||||
Connections | IEC320*4 | IEC320*4 | IEC320*6 | IEC320*6 | IEC320*3& Terminal block | IEC320*3&Terminal block | ||
Efficiency | Battery Mode | 81% | 83% | 83% | 83% | 83% | ||
AC Mode | 85% | 87% | 87% | 87% | 87% | |||
Battery | Type | Sealed free maintenance lead acid battery | ||||||
Nominal DC voltage | 24VDC | 36VDC | 48VDC | 72VDC | 72VDC | 96VDC | ||
Quantity | 12VDC×2 | 12VDC×3 | 12VDC×4 | 12VDC×6 | 12VDC×6 | 12VDC×8 | ||
Backup Time (Full Load) | >2.5min (Built in batteries 12V 7AH) | Depends on requested Back-up time | >5min (Built in batteries 12V 7AH) | Depends on requested Back-up time | >4.5min (Built in batteries 12V 7AH) | Depends on requested Back-up time | ||
Charge Current (Max) | 1A | 5A | 1A | 5A | 1A | 5A | ||
Charge Voltage (VDC) | 27.4V±0.2VDC | 41.1V±0.2VDC | 54.8V±0.4VDC | 82.2V±0.6VDC | 82.2V±0.6VDC | 110±0.6VDC | ||
Recharge Time | 5 hours filling to 90% (standard) | |||||||
Bypass | Automatic Transfer | On overload and UPS failure | ||||||
Before UPS Power-on | Default "ON" user adjustable to "YES" | |||||||
Transfer Time | 0 ms; Less than 4ms from inverter to bypass and vice versa | |||||||
indicators | LCD Display | UPS status, Battery capacity, loading, Fault code (LCD: I/P&O/P voltage&frequency, Battery voltage) | ||||||
Audible | Bypass, On battery mode, Battery low, Overload, Fault | |||||||
Acoustic Noise | At 1 Meter Distance | <50dB | ||||||
Communications | Intelligent RS232 serial port | Software support Windows family software, Linux, Sun network operating system,IBM Aix, Compaq True64 SGI IRIX, FreeBSD, HP-UX and MAC | ||||||
SNMP (Optional) | Remote control UPS through SNMP management and Internet | |||||||
USB (Optional) | Windows family software and Mac OS | |||||||
Environmental | Operating Temperature | 0~40ºC | ||||||
Operating Humidity | 20~90% (No condensing) | |||||||
Physical Parameter | L*W*H (mm) | 373*145*219 | 373*145*219 | 448*192*341 | 448*192*341 | 448*192*341 | 448*192*341 | |
Net Weight (kg) | 9.50 | 5.00 | 17.50 | 9.50 | 22.00 | 10.00 |