China 18 Seer Condensing Units Air Handler Air Conditioner Heat Pump 36000BTU, Find details and Price about China Air Handler, Air Conditioner from 18 Seer Condensing Units Air Handler Air Conditioner Heat Pump 36000BTU
Model | - | UCHA-12HDCH | UCHA-18HDCH | UCHA-24HDCH | UCHA-30HDCH | UCHA-36HDCH | UCHA-42HDCH |
Type | - | Air Handler | Air Handler | Air Handler | Air Handler | Air Handler | Air Handler |
Cooling Capacity | Btu/h | 12000 | 18000 | 24000 | 30000 | 36000 | 42000 |
Heating Capacity | Btu/h | 14000 | 22000 | 32850 | 36730 | 39890 | 47000 |
Air flow volume(H-M-L) | m3/h | 680/442/272 | 1003/680/476 | 1325/1042/770 | 1692/1339/1172 | 2143/1641/1392 | 2341/2017/1699 |
Standard Static Pressure | Pa | 120 | 120 | 120 | 120 | 120 | 120 |
Max. Static Pressure | Pa | 200 | 200 | 200 | 200 | 200 | 200 |
Sound Pressure Level (H-M-L) | dB(A) | 40/38/35 | 42/40/37 | 46/45/44 | 48/47/44 | 49/47/45 | 51/50/47 |
Dehumidifying Volume | L/h | 2.9 | 3.6 | 4.2 | 4.5 | 4.8 | 5.9 |
Rated Voltage | V | 208/230 | 208/230 | 208/230 | 208/230 | 208/230 | 208/230 |
Rated Frequency | Hz | 60 | 60 | 60 | 60 | 60 | 60 |
Phases | - | 1 | 1 | 1 | 1 | 1 | 1 |
Min/Max Voltage | V | 187/253 | 187/253 | 187/253 | 187/253 | 187/253 | 187/253 |
Cooling Power Input | kW | 0.92 | 1.41 | 1.88 | 2.39 | 2.88 | 3.50 |
Heating Power Input | kW | 1.15 | 1.75 | 2.63 | 2.94 | 3.19 | 4.01 |
Cooling Current Input | A | 4.18 | 6.39 | 8.54 | 10.85 | 13.09 | 15.91 |
Heating Current Input | A | 5.23 | 7.94 | 11.94 | 13.35 | 14.50 | 18.23 |
Gas Pipe(to indoor unit) | inch | 1/2 | 1/2 | 5/8 | 5/8 | 5/8 | 5/8 |
Liquid pipe | inch | 1/4 | 1/4 | 3/8 | 3/8 | 3/8 | 3/8 |
Dimension of Outline(W*D*H) | mm | 460*520*1050 | 500*550*1180 | 500*550*1180 | 500*550*1180 | 560*610*1385 | 560*610*1385 |
Dimension of Outline(W*D*H) | inch | 18.2*20.5*41.3 | 19.7*21.7*46.5 | 19.7*21.7*46.5 | 19.7*21.7*46.5 | 22*24*54.5 | 22*24*54.5 |
Net Weight | kg / lb | 47/103.6 | 72/158.6 | 72.8/160.5 | 73.5/162.1 | 76.7/169 | 77.6/171 |