China Single Core 630mm2 XLPE Insulation PVC Sheath Yjv Power Cable, Find details about China XLPE Power Cable, 120mm2 XLPE Power Cable from Single Core 630mm2 XLPE Insulation PVC Sheath Yjv Power Cable
Chinese Type(General Type) | Description | Application | |
Cu | Al | ||
YJV (CU/XLPE/PVC) | YJLV (AL/XLPE/PVC) | Cu conductor(Al conductor)XLPE insulated PVC sheathed power cable | Laying indoors, in tunnel, fixed on the bracket, pipe and buried in the soil, the cable cannot bear external mechanical forces. |
YJY (CU/XLPE/PE) | YJLY (AL/XLPE/PE) | Cu conductor(Al conductor)XLPE insulated PE sheathed power cable | |
YJV22 (CU/XLPE/STA/PVC) | YJLV22 (AL/XLPE/STA/PVC) | Cu conductor(Al conductor)XLPE insulated double of steel-tape armored PVC sheathed power cable | For laying indoors, in tunnel, cable trench, or direct in ground, able to bear external mechanical forces, but unable to bear large pulling force. |
YJV23 (CU/XLPE/STA/PE) | YJLV23 (AL/XLPE/STA/PE) | Cu conductor(Al conductor)XLPE insulated double of steel-tape armored PE sheathed power cable | |
YJV62 (CU/XLPE/ATA/PVC) | YJLV62 (AL/XLPE/ATA/PVC) | Cu conductor(Al conductor)XLPE insulated double of aluminium-tape armored PVC sheathed power cable | |
YJV32 (CU/XLPE/SWA/PVC) | YJLV32 (AL/XLPE/SWA/PVC) | Cu conductor(Al conductor)XLPE insulated steel-wire armored PVC sheathed power cable | For laying indoors, in tunnel, cable trench, well or direct in ground, able to bear external mechanical forces and certain pulling force |
YJV33 (CU/XLPE/SWA/PE) | YJLV33 (AL/XLPE/SWA/PE) | Cu conductor(Al conductor)XLPE insulated steel-wire armored PE sheathed power cable | |
YJV72 (CU/XLPE/AWA/PVC) | YJLV72 (AL/XLPE/AWA/PVC) | Cu conductor(Al conductor)XLPE insulated aluminium-wire armored PE sheathed power cable |
Nominal section area (mm2) | Copper conductor (Ω/km) | Aluminum conductor (Ω/km) |
1.5 | 12.1 | - |
2.5 | 7.41 | 12.1 |
4 | 4.61 | 7.41 |
6 | 3.08 | 4.61 |
10 | 1.83 | 3.08 |
16 | 1.15 | 1.91 |
25 | 0.727 | 1.20 |
35 | 0.524 | 0.868 |
50 | 0.387 | 0.641 |
70 | 0.268 | 0.443 |
95 | 0.193 | 0.320 |
120 | 0.153 | 0.253 |
150 | 0.124 | 0.206 |
185 | 0.0991 | 0.164 |
240 | 0.0754 | 0.125 |
300 | 0.0601 | 0.100 |
400 | 0.0470 | 0.0778 |
500 | 0.0366 | 0.0605 |
Ambient temperature | 20ºC | 25ºC | 30ºC | 35ºC | 40ºC | 45ºC | 50ºC |
Rating factors | 1.18 | 1.14 | 1.10 | 1.05 | 1.0 | 0.95 | 0.89 |
Type | Specification | Outer diameter of conductor | Nominal thickness of insulation | Nominal sheath thickness | Approx.outer diameter of cable | Approx. Weight of cable | Ampacity of cable | ||||
Air | Soil | ||||||||||
CU | AL | Cu | Al | Cu | Al | ||||||
YJV CU/XLPE/PVC YJLV AL/XLPE/PVC | mm2 | mm | mm | mm | mm | kg/km | kg/km | A | A | A | A |
1×4 RE | 2.24 | 0.7 | 1.4 | 6.5 | 73.7 | 49.0 | 45 | 35 | 60 | 50 | |
1×6 RE | 2.76 | 0.7 | 1.4 | 7.0 | 95.8 | 58.7 | 55 | 45 | 70 | 50 | |
1×10 CC | 3.8 | 0.7 | 1.4 | 8.0 | 140.1 | 78.2 | 75 | 60 | 95 | 75 | |
1×16 CC | 4.8 | 0.7 | 1.4 | 9.0 | 201.8 | 102.8 | 100 | 80 | 125 | 100 | |
1×25 CC | 6.0 | 0.9 | 1.4 | 10.6 | 298.9 | 144.2 | 140 | 115 | 160 | 130 | |
1×35 CC | 7.0 | 0.9 | 1.4 | 11.6 | 396.7 | 180.2 | 175 | 140 | 190 | 150 | |
1×50 CC | 8.4 | 1.0 | 1.4 | 13.1 | 543.9 | 234.6 | 210 | 170 | 225 | 180 | |
1×70 CC | 10.0 | 1.1 | 1.4 | 15.0 | 744.7 | 311.6 | 270 | 215 | 280 | 225 | |
1×95 CC | 11.5 | 1.1 | 1.5 | 16.6 | 985.6 | 397.8 | 340 | 275 | 335 | 270 | |
1×120 CC | 13.0 | 1.2 | 1.5 | 18.4 | 1233.0 | 490.6 | 400 | 320 | 380 | 305 | |
1×150 CC | 14.5 | 1.4 | 1.6 | 20.5 | 1533.8 | 605.8 | 460 | 370 | 425 | 340 | |
1×185 CC | 16.2 | 1.6 | 1.6 | 22.7 | 1884.9 | 740.3 | 530 | 415 | 480 | 375 | |
1×240 CC | 18.4 | 1.7 | 1.7 | 25.3 | 2418.0 | 933.1 | 625 | 490 | 555 | 435 | |
1×300 CC | 20.5 | 1.8 | 1.8 | 27.7 | 2996.5 | 1140.4 | 720 | 565 | 630 | 495 | |
1×400 CC | 23.5 | 2.0 | 1.9 | 31.4 | 3962.3 | 1487.5 | 815 | 640 | 705 | 555 | |
1×500 CC | 26.5 | 2.2 | 2.0 | 35.0 | 4933.0 | 1839.5 | 855 | 680 | 765 | 595 | |
1×630 CC | 30.0 | 2.4 | 2.2 | 39.1 | 6188.8 | 2291.0 | 980 | 790 | 860 | 680 |