China Aluminum Conductor Material and PVC Jacket Aluminum Power Cable 3c 240mm2, Find details about China XLPE Power Cable, 120mm2 XLPE Power Cable from Aluminum Conductor Material and PVC Jacket Aluminum Power Cable 3c 240mm2
Chinese Type(General Type) | Description | Application | |
Cu | Al | ||
YJV (CU/XLPE/PVC) | YJLV (AL/XLPE/PVC) | Cu conductor(Al conductor)XLPE insulated PVC sheathed power cable | Laying indoors, in tunnel, fixed on the bracket, pipe and buried in the soil, the cable cannot bear external mechanical forces. |
YJY (CU/XLPE/PE) | YJLY (AL/XLPE/PE) | Cu conductor(Al conductor)XLPE insulated PE sheathed power cable | |
YJV22 (CU/XLPE/STA/PVC) | YJLV22 (AL/XLPE/STA/PVC) | Cu conductor(Al conductor)XLPE insulated double of steel-tape armored PVC sheathed power cable | For laying indoors, in tunnel, cable trench, or direct in ground, able to bear external mechanical forces, but unable to bear large pulling force. |
YJV23 (CU/XLPE/STA/PE) | YJLV23 (AL/XLPE/STA/PE) | Cu conductor(Al conductor)XLPE insulated double of steel-tape armored PE sheathed power cable | |
YJV62 (CU/XLPE/ATA/PVC) | YJLV62 (AL/XLPE/ATA/PVC) | Cu conductor(Al conductor)XLPE insulated double of aluminium-tape armored PVC sheathed power cable | |
YJV32 (CU/XLPE/SWA/PVC) | YJLV32 (AL/XLPE/SWA/PVC) | Cu conductor(Al conductor)XLPE insulated steel-wire armored PVC sheathed power cable | For laying indoors, in tunnel, cable trench, well or direct in ground, able to bear external mechanical forces and certain pulling force |
YJV33 (CU/XLPE/SWA/PE) | YJLV33 (AL/XLPE/SWA/PE) | Cu conductor(Al conductor)XLPE insulated steel-wire armored PE sheathed power cable | |
YJV72 (CU/XLPE/AWA/PVC) | YJLV72 (AL/XLPE/AWA/PVC) | Cu conductor(Al conductor)XLPE insulated aluminium-wire armored PE sheathed power cable |
Nominal section area (mm2) | Copper conductor (Ω/km) | Aluminum conductor (Ω/km) |
1.5 | 12.1 | - |
2.5 | 7.41 | 12.1 |
4 | 4.61 | 7.41 |
6 | 3.08 | 4.61 |
10 | 1.83 | 3.08 |
16 | 1.15 | 1.91 |
25 | 0.727 | 1.20 |
35 | 0.524 | 0.868 |
50 | 0.387 | 0.641 |
70 | 0.268 | 0.443 |
95 | 0.193 | 0.320 |
120 | 0.153 | 0.253 |
150 | 0.124 | 0.206 |
185 | 0.0991 | 0.164 |
240 | 0.0754 | 0.125 |
300 | 0.0601 | 0.100 |
400 | 0.0470 | 0.0778 |
500 | 0.0366 | 0.0605 |
Type | Specification | Outer diameter | Nominal thickness of insulation | Diameter of steel wire | Nominal sheath thickness | Approx. Outer diameter of cable | Approx. Weight of cable | Ampacity of cable | ||||
Air | Soil | |||||||||||
CU | AL | Cu | Al | Cu | Al | |||||||
YJV32 YJLV32 | mm2 | mm | mm | mm | mm | mm | kg/km | kg/km | A | A | A | A |
3×4 RE | 2.24 | 0.7 | 1.25 | 1.8 | 17.1 | 621 | 546 | 37 | 28 | 46 | 35 | |
3×6 RE | 2.76 | 0.7 | 1.25 | 1.8 | 17.8 | 700 | 591 | 47 | 37 | 56 | 46 | |
3×10 CC | 3.8 | 0.7 | 1.6 | 1.8 | 19.5 | 885 | 695 | 64 | 47 | 76 | 56 | |
3×16 CC | 4.8 | 0.7 | 1.6 | 1.8 | 21.5 | 1141 | 840 | 84 | 64 | 98 | 76 | |
3×25 CC | 6.0 | 0.9 | 1.6 | 1.8 | 26.6 | 1670 | 1201 | 115 | 84 | 126 | 98 | |
3×35 CC | 7.0 | 0.9 | 1.6 | 1.8 | 28.8 | 2033 | 1384 | 141 | 115 | 152 | 126 | |
3×50 SM | 8.0 | 1.0 | 1.6 | 1.8 | 31.8 | 2513 | 1635 | 172 | 141 | 181 | 152 | |
3×70 SM | 9.5 | 1.1 | 2.0 | 2.0 | 36.1 | 3502 | 2231 | 218 | 172 | 222 | 181 | |
3×95 SM | 11.0 | 1.1 | 2.0 | 2.2 | 39.4 | 4392 | 2632 | 269 | 218 | 267 | 222 | |
3×120 SM | 12.4 | 1.2 | 2.0 | 2.3 | 42.4 | 5258 | 3033 | 313 | 269 | 305 | 267 | |
3×150 SM | 13.8 | 1.4 | 2.5 | 2.4 | 46.9 | 6706 | 3972 | 359 | 313 | 344 | 305 | |
3×185 SM | 15.4 | 1.6 | 2.5 | 2.6 | 51.5 | 8104 | 4671 | 405 | 359 | 383 | 344 | |
3×240 SM | 17.5 | 1.7 | 2.5 | 2.7 | 56.1 | 10062 | 5557 | 451 | 405 | 442 | 383 | |
3×300 SM | 19.6 | 1.8 | 2.5 | 2.9 | 60.6 | 12082 | 6451 | 497 | 451 | 461 | 422 |