China High Voltage Gas & Vacuum Insulated Electrical Metal-Clad Cabinet/ Switchgear, Find details about China Switchgear, Sf6 Switchgear from High Voltage Gas & Vacuum Insulated Electrical Metal-Clad Cabinet/ Switchgear
No | Item | Unit | Parameter | ||||
1 | Rated voltage | kV | 12 | 24 | 36 | ||
2 | Rated current | A | 630/800 | ||||
3 | Rated frequency | Hz | 50/60 | ||||
4 | 1min Power frequency withstand voltage | wet | kV | 38 | 50 | 70 | |
dry | kV | 48 | 60 | 80 | |||
5 | Lightning impulse withstand voltage Common value | kV | 75 | 125/150 | 125 | ||
6 | Rated transfer current | A | 1700 | 1200 | 800 | ||
7 | Rated active load and close circuit breaking current | A | 63 | 50 | 50/40 | ||
8 | Rated cable charge breaking current | A | 50 and 10 | ||||
9 | Rated short circuit breaking current | kA | 80 | 63 | 50/40 | ||
10 | Rated short circuit making current (peak) | kA | 63 | 50 | 63 | 50 | |
11 | Short time (2s) withstand current, load switch/earth | kA | 25/20 | 20/20 | 25/20 | 20/20 | |
12 | Rated withstand current (peak) | kA | 80 | 63 | 50/40 | ||
13 | Mechanism life | Times | 5000 | 2000 | 2000 | ||
Remarks: Rated current of combination of switch and fuse decided by the fuse current. |