R290 Amitime Carton box 8kW China EN14825 Air Source with ISO9001, Find details about China Heat Pump, Air to Water from R290 Amitime Carton box 8kW China EN14825 Air Source with ISO9001
Model | PAVH-08V1GMA | PAVH-12V1GMA | ||
Power Supply / Refrigerant | V/Hz/Ph | 220-240/50/1 - R290 | 220-240/50/1 - R290 | |
Max. Heating Capacity (1) | kW | 9.41 | 12.32 | |
C.O.P (1) | W/W | 4.51 | 4 | |
Heating Capacity Min./Max.(1) | kW | 4.39 / 9.41 | 6.01 / 12.32 | |
Heating Power Input Min./Max.(1) | W | 877 / 2089 | 1200 / 3094 | |
C.O.P Min./Max.(1) | W/W | 4.51 / 5.0 | 4.0 / 5.0 | |
Max. Heating Capacity(2) | kW | 8.84 | 11.4 | |
C.O.P (2) | W/W | 3.66 | 3.3 | |
Heating Capacity Min./Max.(2) | kW | 3.87 / 8.84 | 5.4 / 11.4 | |
Heating power input Min./Max.(2) | W | 1042 / 2418 | 1450 / 3511 | |
C.O.P Min./Max.(2) | W/W | 3.66 / 3.72 | 3.3 / 3.8 | |
Max. Cooling Capacity (3) | kW | 5.92 | 10.05 | |
E.E.R (3) | W/W | 3.83 | 3.65 | |
Cooling Capacity Min./Max.(3) | kW | 2.04 / 5.92 | 4.04 / 10.05 | |
Cooling Power Input Min./Max.(3) | W | 510 / 1540 | 1010 / 1726 | |
E.E.R Min./Max.(3) | W/W | 3.83 / 4.0 | 3.83 / 4.0 | |
Max. Cooling Capacity (4) | kW | 5.29 | 8.03 | |
E.E.R (4) | W/W | 2.72 | 2.7 | |
Cooling Capacity Min./Max.(4) | kW | 2.1 / 5.29 | 4.1 / 8.03 | |
Cooling Power Input Min./Max.(4) | W | 700 / 1945 | 1460 / 1945 | |
E.E.R Min./Max.(4) | W/W | 2.72 / 3.0 | 2.70 / 3.0 | |
Workable Ambient Temperature Range | ºC | -20~45 | -20~45 | |
Max. System Water Temperature (Heating / Cooling) | ºC | 20 / 7 | 20 / 7 | |
Min. System Water Temperature (Heating / Cooling) | ºC | 20 / 7 | 20 / 7 | |
Max. Operation High Pressure | MPa | 3.6 | 3.6 | |
Max. Operation Low Pressure | MPa | 1.2 | 1.2 | |
Compressor | Type - Quantity/System | Twin Rotary - 1 | Twin Rotary - 1 | |
Refrigerant | Type / Amount | - / kg | R290 / 1kg | R290 / 1.1kg |
Fan | Quantity | 1 | 1 | |
Airflow | m3/h | 3200 | 3650 | |
Rated power | W | 54 | 75 | |
Noise Level (sound power) | Indoor/Outdoor | dB(A) | 44/52 | 44/53 |
Water Side Heat Exchanger | Type | Plate Heat Exchanger | Plate Heat Exchanger | |
Water Pressure Drop | kPa | 26 | 26 | |
Piping Connection | Inch | G1" | G1" | |
Allowable Water Flow | Min./Rated./Max. | L/S | 0.21/0.29/0.35 | 0.34/0.57/0.68 |
Net Dimension(L×D×H) | Indoor Unit | mm | 570x550x255 | 570x550x255 |
Outdoor Unit | mm | 1165x370x850 | 1165x370x950 | |
Net Weight | Indoor Unit | Kg | 25 | 25 |