Type | Name |
VV VLV | Copper(aluminum)Conductor,PVC insulated and Sheathed Power Cable |
VY VLY | Copper(aluminum)Conductor,PVC insulated,PE Sheathed Power Cable |
VV22VLV22 | Copper(aluminum)Conductor,PVC insulated,Steel-tape Armoured,PVC Sheathed Power Cable |
VV23VLV23 | Copper(aluminum)Conductor,PVC insulated,Steel-tape Armoured,PE Sheathed Power Cable |
VV32 VLV32 | Copper(aluminum)Conductor,PVC insulated,Fine Steel-wire Armoured,PVC Sheathed Power Cable |
VV33VLV33 | Copper(aluminum)Conductor,PVC insulated,PE Sheathed Power Cable |
VV42VLV42 | Copper(aluminum)Conductor,PVC insulated,Thick Steel-wire Armoured,PVC Sheathed Power Cable |
VV43VLV43 | Copper(aluminum)Conductor,PVC insulated,Thick Steel-wire Armoured,PE Sheathed Power Cable |
| 1 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000 | |||
0.6/1 | 0.8 0.8 0.8 1 1 1 1 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4 2.6 2.8 2.8 2.8 3.0 | |||
3.6/6 | 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 |
Nominal Cross Section (mm2) | at 20ºC,DC resistance is not more than (Ω/km) | Nominal Cross Section (mm2) | at 20ºC,DC resistance is not more than (Ω/km) | Nominal Cross Section (mm2) | at 20ºC,DC resistance is not more than (Ω/km) | |||
Copper Core | Aluminum Core | Copper Core | Aluminum Core | Copper Core | Aluminum Core | |||
1.5 | 12.1 | 18.1 | 35 | 0.524 | 0.868 | 240 | 0.0754 | 0.125 |
2.5 | 7.41 | 12.1 | 50 | 0.387 | 0.641 | 300 | 0.0601 | 0.100 |
4 | 4.61 | 7.41 | 70 | 0.268 | 0.443 | 400 | 0.0470 | 0.0778 |
6 | 3.08 | 4.61 | 95 | 0.193 | 0.320 | 500 | 0.0366 | 0.0605 |
10 | 1.83 | 3.08 | 120 | 0.153 | 0.253 | 630 | 0.0283 | 0.0469 |
16 | 1.15 | 1.91 | 150 | 0.124 | 0.206 | 800 | 0.0221 | 0.0369 |
25 | 0.727 | 1.20 | 185 | 0.0991 | 0.164 | 1000 | 0.0176 | 0.0291 |
Test item | PVC insulated Cable | XLPE insulated Power Cable | |
0.6/1KV | 3.6/6KV | ||
volume resistivity (ρΩ.cm) min.at 20ºC at top rated temperature min. | 1013 1010 | 1014 1011 | - 1012 |
Ki insulation resistivity constant(MΩ.km) min.at 20ºC at top rated temperature min. | 36.7 0.037 | 367 0.37 | - 3.67 |
UO/U(KV) | Us(KV) | T(min) |
0.6/1 | 3.5 | 5 |
3.6/6 | 12.5 | 5 |