China Sq3 Dual Power Automatic Transfer Switch ATS, Find details about China ATS, Generator ATS from Sq3 Dual Power Automatic Transfer Switch ATS
1.Item name: SUQ3-63A / XXQ3-63A(XX: Company code)
2.Rated working voltage:400VAC
3.Rated current(A): 16,20,25,32,40,50,63,80,100
4.Frame class:100
5.Protection function: short-circuit,overland,phase failure,under-voltage
One outlet choices for frame class:100
Frame class | 100 | 250 | 630 | 1600 | 3200 | |||||||||||||||||
Agreed heating current Ith(A) | 63 | 100 | 160 ~ 3200 | |||||||||||||||||||
Rated current In(A) | 16 | 20 | 25 | 32 | 40 | 50 | 63 | 80 | 100 | 125 | 160 | 250 | 400 | 630 | 800 | 1000 | 1250 | 1600 | 2000 | 2500 | 3200 | |
Rated Insulation voltage(Ui) | 690V | 800V | ||||||||||||||||||||
Rated concussion withstand voltage(Uimp) | 8KV | |||||||||||||||||||||
Rated working voltage(Ue) | AC400V | |||||||||||||||||||||
Using Category | AC-33B | AC-33iB | ||||||||||||||||||||
Rated short-circuit connection capacity | 8KA | 17KA | 26KA | 67KA | ||||||||||||||||||
Rated short-time withstand current(Icw) | 5kA / 30ms | 10kA / 60ms | 12.6kA / 60ms | 32kA / 60ms | ||||||||||||||||||
Transfer time I-II or II-I | 2.5s | 0.6s | 1.2s | 1.8s | 2.4s | |||||||||||||||||
Control voltage | AC220V, DC24V,48V,110V | |||||||||||||||||||||
Rated frequency | Start | 20W | 325W | 355W | 400W | 440W | 600W | |||||||||||||||
Normal | 62W | 74W | 90W | 98W | 120W | |||||||||||||||||
Weight(kg) 4pole | 3.4 | 6.0 | 7.6 | 15.8 | 16.8 | 36 | 36 | 37 | 38.6 | 55 | 61 | 67 |