High Efficiency Refrigerated Air Dryer & Desiccant Air Dryer

China High Efficiency Refrigerated Air Dryer & Desiccant Air Dryer, Find details about China Compressed Air Dryer, Desiccant Dryer from High Efficiency Refrigerated Air Dryer & Desiccant Air Dryer

Model NO.
HLX010
Cooling Way
Air Cooling
Type
Medium
Evaporator
Aluminum
Power
220V 50 Hz
Connection
RC3/4"
Dew Point
Option Negative 20/40/70 ºC
Flow Rate
1.2m³/Min
Air Compressor Brand
LG/Panasonic/Danfoss
Expansion
Danfoss
with Dt Air Filter Inside
Grade PF/Ao/AA/Ax
Filter Dryer
Eco
Option Function
Particle Detector
Input Power
0.5kw
Color
Red
Trademark
YUKA
Transport Package
Wooden Cardboard
Specification
120X66X100cm
Origin
China
HS Code
8419399090
Model NO.
HLX010
Cooling Way
Air Cooling
Type
Medium
Evaporator
Aluminum
Power
220V 50 Hz
Connection
RC3/4"
Dew Point
Option Negative 20/40/70 ºC
Flow Rate
1.2m³/Min
Air Compressor Brand
LG/Panasonic/Danfoss
Expansion
Danfoss
with Dt Air Filter Inside
Grade PF/Ao/AA/Ax
Filter Dryer
Eco
Option Function
Particle Detector
Input Power
0.5kw
Color
Red
Trademark
YUKA
Transport Package
Wooden Cardboard
Specification
120X66X100cm
Origin
China
HS Code
8419399090
High Efficiency Refrigerated Air Dryer & Desiccant Air Dryer
 
High Efficiency Refrigerated Air Dryer & Desiccant Air Dryer
High Efficiency Refrigerated Air Dryer & Desiccant Air Dryer


Space saving:
Integrated design of dryer, filter, gas-water separator and suction dryer, saving space;

Energy saving:
The design of three-in-one aluminum alloy heat exchanger minimizes the process loss of cooling capacity and improves the recycling of cooling capacity. Under the same processing capacity, the total red and green input of the modified model will be reduced by 15-30

High efficiency: 
The integrated heat exchanger is equipped with diversion fins, which is the uniform heat exchange of compressed air inside, and the built-in gas-water separation device is equipped with a stainless steel filter screen to separate the moisture more thoroughly.
Intelligent: Multi-channel temperature and pressure monitoring, real-time display of dew point temperature, automatic recording of accumulated running time, self-diagnosis function, display of corresponding alarm codes, and automatic protection of equipment.


Environmental protection: 
Corresponding to the international Montreal agreement, this series of models all use R134a, R410a, R407c environmentally friendly refrigerants, and the degree of damage to the atmosphere is zero, adapting to international market needs;

Stability:
Standard configuration constant pressure expansion valve, standard configuration intelligent temperature control, laboratory test when the temperature reaches 65 ºC, ambient temperature reaches 42 ºC, flammable and stable operation, at the same time with temperature and pressure dual anti-freeze protection When the time is low, the output of the compressor is automatically stopped, and the aluminum plate is used to exchange the stored cooling capacity to provide heat exchange and energy saving, while extending the service life of the equipment.

Technical Specification
The following products are suitable for use at 220V 50HZ, 380V 50Hz voltage, other voltages can be customize:
ModelFlow Rate m³/minDew Point ºCPowerInput power KWConnectionMaxi.Pressure Loss  MpaNoiseG.W.(KG)Dimension(MM)
HLX010-201.2-20220V50Hz0.5RC3/4"≤0.035≤ 75 dB(A)1001200*660*1000
HLX020-202.2-20220V50Hz0.65RC3/4"≤0.035≤ 75 dB(A)1281200*800*1100
HLX030-203.6-20220V50Hz0.86RC1"≤0.035≤ 75 dB(A)1861200*800*1100
HLX060-206.5-20220V50Hz1.39RC1-1/2" ≤0.035≤ 75 dB(A)2651500*1000*1100
HLX080-208.5-20220V50Hz2RC2"≤0.035≤ 75 dB(A)2881500*1000*1600
HLX100-2011-20220V50Hz2.56RC2"≤0.035≤ 75 dB(A)3681500*1000*1600
HLX120-2013.5-20220V50Hz2.76RC2"≤0.035≤ 75 dB(A)4501500*1000*1700
HLX150-2017-20380V50Hz3.13DN50 Flange≤0.035≤ 75 dB(A)5502200*1700*1700
HLX200-2022-20380V50Hz3.83DN65 Flange≤0.035≤ 75 dB(A)10502200*1700*1800
HLX010-401.15-40220V50Hz0.5RC3/4"≤0.035≤ 75 dB(A)1001200*660*1000
HLX020-402-40220V50Hz0.65RC3/4"≤0.035≤ 75 dB(A)1281200*800*1100
HLX030-403.3-40220V50Hz0.86RC1"≤0.035≤ 75 dB(A)1861200*800*1100
HLX060-406.2-40220V50Hz1.39RC1-1/2" ≤0.035≤ 75 dB(A)2651500*1000*1100
HLX080-408-40220V50Hz2RC2"≤0.035≤ 75 dB(A)2881500*1000*1600
HLX100-4011-40220V50Hz2.56RC2"≤0.035≤ 75 dB(A)3681500*1000*1600
HLX120-4012-40220V50Hz2.76RC2"≤0.035≤ 75 dB(A)4501500*1000*1700
HLX150-4016-40380V50Hz3.13DN50 Flange≤0.035≤ 75 dB(A)5502200*1700*1700
HLX200-4020-40380V50Hz3.83DN65 Flange≤0.035≤ 75 dB(A)10502200*1700*1800
HLX010-701.15-70220V50Hz0.5RC3/4"≤0.035≤ 75 dB(A)1001200*660*1000
HLX020-702.3-70220V50Hz0.65RC3/4"≤0.035≤ 75 dB(A)1281200*800*1100
HLX030-703.6-70220V50Hz0.86RC1"≤0.035≤ 75 dB(A)1861200*800*1100
HLX060-705.6-70220V50Hz1.39RC1-1/2" ≤0.035≤ 75 dB(A)2651500*1000*1100
HLX080-708.5-70220V50Hz2RC2"≤0.035≤ 75 dB(A)2881500*1000*1600
HLX100-7011-70220V50Hz2.56RC2"≤0.035≤ 75 dB(A)3681500*1000*1600
HLX120-7013.8-70220V50Hz2.76RC2"≤0.035≤ 75 dB(A)4501500*1000*1700
HLX150-7017-70380V50Hz3.13DN50 Flange≤0.035≤ 75 dB(A)5502200*1700*1700
HLX200-7020-70380V50Hz3.83DN65 Flange≤0.035≤ 75 dB(A)10502200*1700*1800


Working conditions & technical requirements
Rated ambient temperature: 38 ° C, max.42 ° C.
Rated inlet temperature: 38 ° C, max. 65 ° C.
Rated air pressure: 0.7Mpa, max. 1.6Mpa.
Pressure dew point under rated conditions: 2 ° C ~ 10 ° C (atmospheric dew point: -23 ° C ~-17 ° C).
Assembly environment: no sun, no rain, and good ventilation, installed in a horizontal hard foundation, no obvious dust and flying flour.