China 12 Volt 15W DIN Rail Mount Single Output 12V 1.25A AC DC Switching Power Supply for Access Control System, Find details about China Switching Power Supply, AC DC Power Supply from 12 Volt 15W DIN Rail Mount Single Output 12V 1.25A AC DC Switching Power Supply for Access Control System
SPECIFICATIONS | ||||
OUTPUT | ||||
Model | HDR-15-5 | HDR-15-12 | HDR-15-15 | HDR-15-24 |
DC Voltage | 5V | 12V | 15V | 24V |
Rated Current | 2.4A | 1.25A | 1A | 0.63A |
Current Range | 0-2.4A | 0-1.25A | 0-1A | 0-0.63A |
Rated Power | 12W | 15W | 15W | 15.2W |
Ripple & Noise | 80mVp-p | 120mVp-p | 120mVp-p | 150mVp-p |
Voltage Adj. Range | 4.75-5.5V | 10.8-13.2V | 13.5-16.5V | 21.6-26.4V |
Voltage Tolerance | ±2% | ±1% | ±1% | ±1% |
Line regulation | ±1% | ±1% | ±1% | ±1% |
Load regulation | ±1% | ±1% | ±1% | ±1% |
Setup, Rise, Hold Up Time | 1000ms, 50ms/230VAC 1000ms, 50ms/115VAC at full load 70ms/230VAC 16ms/115VAC at full load | |||
INPUT | ||||
Voltage Range | 85 ~ 264VAC 120 ~ 370VDC | |||
AC Current | 0.88A/115VAC 0.48A/230VAC | |||
Efficiency | 77% | 84% | 83.5% | 85% |
Inrush Current | COLD START 35A/115VAC 65A/230VAC | |||
PROTECTION | ||||
Over Load | 105%~160% rated output power | |||
Protection type: Constant current limiting, recovers automatically after fault condition is removed | ||||
Over Voltage | 5.75-6.75V | 13.8-16.2V | 17.25-20.25V | 27.6-32.4V |
Protection type: Shut off o/p voltage, clamping by zener diode | ||||
ENVIRONMENT | ||||
Working Temp., Humidity | -20ºC~+60ºC; 20%~90% RH non-condensing | |||
Storage Temp., Humidity | -40ºC~+85ºC; 10%~95%RH | |||
Temp. Coefficient | ±0.03%/ºC(0~50ºC) | |||
Vibration | 10~500Hz, 2G 10min./1cycle, period for 60min, each along X, Y, Z axes, Mounting: Compliance to IE60068-2-6 | |||
SAFETY | ||||
Withstand Voltage | I/P-O/P: 3KVAC | |||
Isolation Resistance | I/P-O/P: 100M Ohms / 500VDC/ 25ºC/ 70%RH | |||
STANDARD | ||||
Safety Standard | Design refer to UL60950-1,TUV EN60950-1,EN50178 | |||
EMC Standard | Design refer to EN55011,EN55022,EN61000-3-2,-3,EN61000-4-2,3,4,5,6,8,11,EN55024,EN61000-6-2,EN61204-3, heavy industry level, criteria A | |||
OTHERS | ||||
Dimension | 93*18*56mm | |||
Weight | 0.1Kg | |||
Packing | 140pcs/15KG/0.92CUFT |