China 12kv High Voltage Vacuum Interrupter for Vacuum Circuit Breaker, Find details about China Vacuum Interrupter, 12kv Vacuum Interrupter from 12kv High Voltage Vacuum Interrupter for Vacuum Circuit Breaker
Parameter item | Unit | Data |
Rated voltage | kV | 12 |
Rated current | A | 1250 |
Rated frequency | Hz | 50 |
Rated short-time power frequency withstand voltage(1 min) | kV | 42 |
Rated lightning impulse withstand voltage | kV | 75 |
Rated short-circuit breaking current | kA | 25/31.5 |
Rated peak withstand current | kA | 63/80 |
Rated short-circuit making current | kA | 63/80 |
Rated short-time withstand current | kA | 25/31.5 |
Rated short-circuit duration | s | 4 |
Rated single capacitor bank breaking current | A | 630 |
Rated back to back capacitor bank breaking current | A | 400 |
Breaking operation of rated short circuit breaking current | times | 30 |
Mechanical life | times | 10000 |
Contact closing force due to bellows and atomsphere | N | 100±40 |
Force required to hold contact open at full stroke | N | 160±50 |
Circuit resistance at lowest rated contact force | μΩ | ≤20 |
Contact limit erosion | mm | 3 |
Internal gas pressure | Pa | ≤1.33×10-3 |
Weight of moving parts | kg | 1.1 |
Storage life | year | 20 |
Parameter item | Unit | Data |
Rated clearance between open contacts | mm | 11±1 |
Average opening speed | m/s | 1.1±0.2 |
Average closing speed | m/s | 0.6±0.2 |
Rated contact pressure | N | 2500±200 3100±200 |
Contact bouncing duration at closing operation | ms | ≤2 |
Closing and opening non-simultaneity of contacts | ms | ≤2 |
Maximum rebound during opening | mm | ≤2 |
Rated contact stroke | mm | 3.5±0.5 |