China Class III 230V Three Phase in 5ka AC DIN Rail Voltage Surge Lightning Protector with Red and Green LED Indicator, Find details about China Surge Lightning Protector, Lightning Protector from Class III 230V Three Phase in 5ka AC DIN Rail Voltage Surge Lightning Protector with Red and Green LED Indicator
Product Description:
For installation at LPZ 1-2 or higher, protecting electronic equipment from surge damages. Applied in SPD Class III (Class D) for three-phase various power supply system. Designed according to IEC 61643-11 / GB 18802.1.
Main character:
1. High discharge capacity, quick response
2. Green light indicates normal and red light indicates fault
3. Three-phase protection and disconnector
4. Remote signaling connector for fault indication
Technical data:
Type | BT D 230 3N RM | |||
Nominal voltage [UN] | 230V AC | |||
Rated voltage (max. continuous voltage) [Uc] | 320V AC | |||
Nominal load current IL | 16A | |||
Nominal discharge current (8/20) [In] L-N | 3kA | |||
Max. discharge current (8/20) In N-PE | 5kA | |||
Voltage protection level [Up] L-N | ≤ 1.15kV | |||
Response time [tA] | ≤ 25ns | |||
Max. back up fuse [F] | 16A gL/gG | |||
Operating temperature range [Tu] | -40°C...+80°C | |||
Cross-sectional area | 1.5mm2 ~ 25mm2 solid /35mm2 flexible | |||
Mounting on | 35mm DIN rail | |||
Enclosure material | Purple thermoplastic, UL94-V0 | |||
Dimension | 1.5 mods | |||
Test standards | IEC 61643-11; EN 61643-11; GB18802.11 | |||
Certification | CE (LVD, EMC) | |||
Type of remote signalling contact | Break contact | |||
Switching capacity | AC:250V/0.5A; DC:250V/0.1A;150V/0.2A;750V/0.5A | |||
Cross-sectional area for remote signalling contact | Max. 1.5mm2 solid / flexible | |||
Ordering information | ||||
Type | BT D 230 3N RM | |||
Art.-No. | 820 330 | |||
Packing unit | 1pc(s) |