China Supplier High Voltage Tester DC Porable Hipot Withstand Voltage Tester DC Direct Current Generator for Zinc Oxide Surge Arrester, Cables, Find details about China DC Hipot Tester, High Voltage DC Generator from China Supplier High Voltage Tester DC Porable Hipot Withstand Voltage Tester DC Direct Current Generator for Zinc Oxide Surge Arrester, Cables
1) MOA lightning-arrester HVDC hi-pot
2) HVDC hi-pot and leak current measurement for HV electrical equipment, such as transformer, switchgear, and oil-type power cable
3) Leak current measurement for water-cooling DC power generators
4) High-stability DC HV generators with high-precision DC voltage-divider for DC HV standardization
Specification Technical Parameter | 60/5 | 120/5 | 100/10 | 160/2 | 180/2 | 200/2 | 250/2 | 100/200 3/2 | 200/300 3/2 | Others |
Output voltage (kV) | 60 | 120 | 100 | 160 | 180 | 200 | 250 | 100/200 | 200/300 | 600~800kV Produce according to the contract |
Output current (mA) | 5 | 5 | 10 | 2 | 2 | 2 | 2 | 3/2 | 3/2 | |
Output power (W) | 300 | 600 | 1000 | 320 | 360 | 400 | 500 | 400 | 600 | |
Charging current (mA) | 5.0 | 5.0 | 12.0 | 3.0 | 3.0 | 3.0 | 3.0 | 4.5/3.0 | 4.5/3.0 | |
Case weight (kg) | 4.5 | 7 | 5.3 | 4.3 | 4.3 | 4.4 | 4.5 | 4.5 | 8.1 | |
Dimension of multivoltage tube (mm) | Φ80 ×500 | Φ80 ×770 | Φ80 ×770 | Φ80 ×770 | Φ110 ×770 | Φ110 ×770 | Φ110 ×820 | Φ110 ×800 | Φ110 ×1350 | |
Height of multivoltage tube (kg) | 7.3 | 9 | 7.5 | 7.2 | 7.2 | 7.2 | 7.6 | 7.5 | 12.6 | |
HV polarity | Polarity of negative volt, zero voltage start, continuous adjustable | |||||||||
Work power | AC 220V±10%;50Hz | |||||||||
Voltage measuring accuracy | 1.0%(full scale)±1character, max resolution 0.1%kV | |||||||||
Current measuring accuracy | 1.0%(full scale)±1character, max resolution 0.1%uA | |||||||||
Over voltage rectify accuracy | ≤1.0% | |||||||||
0.75 switch over accuracy | ≤0.5% | |||||||||
Ripple factor | ≤1.0% | |||||||||
Voltage stability | Random fluctuation, when voltage change of power supply±10% ≤0.5% | |||||||||
Work manner | Intermittent service; 30min of rated load;1.1 times of rated voltage use:10min | |||||||||
Temperature | -15ºC~50ºC | |||||||||
Relative humidity | When at 25ºC,no more than 90%(no condensation) | |||||||||
Altitude | Below 2500m |