12kv High Voltage Pre-Paid Control Circuit Breaker on Pole ( YZD )

China 12kv High Voltage Pre-Paid Control Circuit Breaker on Pole (YZD), Find details about China Circuit Breaker, Pre-Paid Control Circuit Breaker from 12kv High Voltage Pre-Paid Control Circuit Breaker on Pole (YZD)

Model NO.
Yzd-12
Poles Number
3
Type
Circuit Breaker
Function
Conventional Circuit Breaker
Certification
ISO9001-2000, CE, CCC
Rated Short-Time Withstand Current
20ka
Opening Distance Between Contacts
10-12mm
Rated Operating Voltage
~220V
Mechanical Life
10000 Times
Weight
210kg
Trademark
VACEM
Origin
Wenzhou, China
Model NO.
Yzd-12
Poles Number
3
Type
Circuit Breaker
Function
Conventional Circuit Breaker
Certification
ISO9001-2000, CE, CCC
Rated Short-Time Withstand Current
20ka
Opening Distance Between Contacts
10-12mm
Rated Operating Voltage
~220V
Mechanical Life
10000 Times
Weight
210kg
Trademark
VACEM
Origin
Wenzhou, China
YZD-12Pre-paid Control Circuit Breaker
1.General description
    To fulfill the necessary of power usage management, to use technique way to solve the difficulty on power cost
recycling especially hard to control the big power user we researched this YZD-12 type outdoor H.V. pre-paid control device. It is used in electric system of AC 50 Hz, voltage 7 .2~12kV as the automatic recloser under pre-paid H.V. measurement or distribution network automation project. The host machine includes ZW8-12 vacuum circuit breaker, dry type voltage transformer and current transformer, integrated installation, the top of case is vacuum circuit breaker, the bottom is transformer apartment, matches with handle opening and closing spring mechanism outside, the control case is installed separately, it could extra install pre-paid ammeter as pre-paid measurement according to user' s requirement, or install it by user. 
    H.V. vacuum circuit breaker is with spring mechanism, mechanical locking, inside case with switching apartment and transformer apartment. It is made of two sets dry type voltage transformers and two sets dry type current transformers of the transformer apartment, meanwhile, the voltage transformer sets dedicated core as the power of opening-closing mechanism, it is small outfit and easy installation. With V/V wire connecting for VT, the current transformer could be done with multi-ratio structure, to fulfill different load requirement. 
The control device is composed with pre-paid ammeter and control circuit, the connection between control device and vacuum switch is by metal-clad cable, achieves the function of using after purchasing, avoids the defaulting of electric cost in valid. 
2.Function and characteristic
a. This system is composed of H.V. measurement control device and vacuum circuit breaker, as a set with disconnecting switch and arrester to fulfill the electric measurement and power pre-purchasing for users.
b.  Adopt electricity meter for measurement and clearing.
c.  Through buying electricity power card for using the electricity, each measurement case matches with one dedicate electricity power card and non-exchange.
d. Data valid for purchasing once, data out automatically after insert card, function with anti-magnetic, anti-static and encryption indecipherability.
e. Pulling out the card and preservation, reserve it for next time using. If damage or loss, compensation could be
available at the sale power department according to user's record.
f. Balanced electricity, used electricity or other power using parameter could be checked from the display screen of the device. 
g. Sound and light alarm when balanced electricity reach the alarming threshold, reminding users to buy electricity in time.
h. It is reliable to break the load current when the purchasing electricity goes into zero, so that get the solution for the worrying about defaulting electricity charge. 
i. Function with anti-stealing electricity. Due to this device adopts outdoor transformer for the measurement, the meter is installed inside the measurement case, so it solves electricity stealing problem radically. 
3.Mechanical property parameter
ItemUnitData
Opening distance between contactsmm11±1
Contact travelmm3+1(-0.3)
Average opening timem/s1.1±0.3
Average closing timem/s0.7±0.15
Contact closing bounce time ms≤2
Tri-phase opening asynchronousms≤2
Closing timems25~50
Opening timems15~50
Full-breaking timems≤100
Arcing timems≤20
Each-phase conductive circuit resistance-B phaseμΩ≤150
Each-phase conductive circuit resistance-A,C phaseμΩ≤350
4.Main technical parameter
ItemUnitData
Rated voltagekV12
1 min P.F. withstand voltage-Phase to phase, to earthkV42
1 min P.F. withstand voltage-FracturekV48
Lightning impulse withstand voltage-Phase to phase, to earthkV75
Lightning impulse withstand voltage-FracturekV85
Rated frequencyHz50
Rated short-circuit current breaking timestime30
Secondary circuit 1min P.F. withstand voltage kV2
Rated currentA630,1250
Rated short-circuit breaking currentkA20
Rated short circuit making current (peak value)kA50
Rated short-time withstand currentkA20
Rated peak withstand currentkA50
Rated operating sequence O-0.3s-CO-180s-CO
Rated operating voltageV~220
Operation current of over current releaseA5
Current accuracy of over current release%±10
Mechanical life timetime10000
Weightkg210
5.International fairs
12kv High Voltage Pre-Paid Control Circuit Breaker on Pole (YZD)

6. Company show
12kv High Voltage Pre-Paid Control Circuit Breaker on Pole (YZD)12kv High Voltage Pre-Paid Control Circuit Breaker on Pole (YZD)12kv High Voltage Pre-Paid Control Circuit Breaker on Pole (YZD)12kv High Voltage Pre-Paid Control Circuit Breaker on Pole (YZD)12kv High Voltage Pre-Paid Control Circuit Breaker on Pole (YZD)