China Zw7-40.5 Series Outdoor High Voltage Vacuum Circuit Breaker, Find details about China Vacuum Circuit Breaker, MCCB from Zw7-40.5 Series Outdoor High Voltage Vacuum Circuit Breaker
rated voltage | 40.5kV |
rated current | 1250A 1600A 2000A |
rated short-circuit breaking current | 20 25 31.5kA |
rated frequency | 50Hz |
closing time | ≤90ms |
rated operating sequence | 0-0.3s-CO-180s-CO |
rated short-circuit closed current | 50 63 80kA |
rated peak withstand current | 50 63 80kA |
rated short time withstand current | 20 25 31.5kA |
rated short-circuit duration | 4s |
mechanical life | 10000times |
average opening speed | 1.5±0.3ms |
average closing speed | 0.6±0.3ms |
contact closing bounce duration | ≤5ms |
three phase closing and opening synchronism | ≤2ms |
opening time | ≤60ms |
weight | 800kg |
NO | Item | Unit | Technical Data |
1 | Rated voltage | KV | 12 |
2 | 1 min power frequency withstand voltage | 42 | |
Lighting impulse withstand voltage(peak value) | 75 | ||
3 | Rated Frequency | Hz | 50 |
4 | Rated current | A | 630, 1250, 1600, 2000, 2500, 3150, 4000 |
5 | Rated short time withstand current | KA | 20, 25, 31.5, 40 |
6 | Rated withstand current(peak) | 50, 63, 80, 100 | |
7 | Rated short-circuit opening current | 20, 25, 31.5, 420 | |
8 | Rated short-circuit closing current | 50, 63, 80, 100 | |
9 | Rated duration of short-circuit | S | 4 |
10 | Contact's clearance | 3.5±0.5 | |
11 | Contact's travel | 9±1/11±1 | |
12 | Average opening speed | M/s | 1.1±0.2 |
13 | Average closing speed | M/s | 0.6±0.2 |
14 | Opening time | Ms | 35-60 |
15 | Closing time | Ms | 20-45 |
16 | Mechanical life | Times | 30000 |
17 | Rated operating order | O-0.3S-CO-180S-CO(<40KA) O-180S-CO-180S-CO(≥40KA) |