China 11kv 5MW 6.25mva Load Bank for Generator Testing, Find details about China Load Bank, 11kv Load Bank from 11kv 5MW 6.25mva Load Bank for Generator Testing
Introduction
(1) According to the special requirements of users on site, in the agreement the technical standards of 11KV 5MW 6.25MVA Load Bank for Generator Testing (hereinafter referred to as "system") and its accessories are proposed including their function, performance, usage, structure, installation and test to provide users with a high efficient and reliable choice, in order to meet the need for generator load test.
(2) 11KV 5MW 6.25MVA Load Bank for Generator Testing consists of 1 sets of 2000kw load bank. The system is made up of two parts of measurement & control and load, mainly including the high voltage dry type AC load bank, automatic data acquisition system, automatically loading and unloading control system, the cooling device, auxiliary control, remote control box and PC software and so on.
(3) 11KV 5MW 6.25MVA Load Bank for Generator Testing , which is of independent research and development of electricity load test equipment by our technology, combining high voltage dry type load module with the automatic measurement and control module, with excellent insulation protection performance, itcan directly detect high voltage generator output power and load capacity (no need a step down transformer), full load and overload test.
The system can be used with a computer to realize the intelligent control, automatically completing the special test to all electrical parameters of generating set and generating tables, graphs, and supporting the print, release from the cumbersome manual operation to provide scientific and efficient detection means for the large power high voltage generating sets.
(4) All the schematic diagrams of this agreement are for reference only please in kind prevail.
11KV 5MW 6.25MVA Load Bank for Generator Testing | |
Rating Voltage/Frequency | 11KV /60Hz |
Rated Load Power | Resistive load: 5MW Reactive load: 3.75MVAR |
Installed Capacity | Resistive load: 5MW Reactive load: 3.75MVAR |
Load Step | Resistive load: 3 steps, 1000kw,2000kw,2000kw0 min step: 1000kW Reactive Load: 3 steps, 750KVAR, 1000KVAR, 2000KVAR |
PF(Power Factor) | 0.8 |
Load Tolerance (each step) | ±5% |
Load Tolerance(overall) | ±3% |
Display Precision | 0.5 class |
Control Power | 3 phase 4 wire 380V,60Hz |
Wire Connection | Load power supply input--Copper bar (star coupling) Control power supply input--Connector-bar |
Insulation | F |
Max Protection Grade | IP54 |
Duty Cycle | Continuous |
Cooling | Forced air cooling,Horizontal inlet air,Vertical cooling |
Aeration | About 160,000 cubic meters per hour |
Casing Structure | Container, with a ladder, air inlet and outlet with mesh enclosure and protection door |
Transportation | Hoisting, there are lifting lug in top of casing |
Casing Color | Grey(RAL7035)or as per customer's requirement |
Dimension | About 12000mm×2438mm×2591mm(length*width*height) |
Weight | About 15000kg |
Operating Environment Parameter | |
Workplace | Outdoor |
Ambient Temperature | -10ºC~+50ºC |
Relative Humidity | ≤95% |
Altitude | ≤2500 meter |
Atmospheric Pressure | 86~106kPa |
Space Required | About 14.77 square meter |
Ground load-bearing requirements | About 406kg/square meter |
Aeration Distance | 3-5meters no obstacle from air inlet, more than 3meters no obstacle from air outlet |
Safe Working Distance | For the convenience of personnel to enter, there should no obstacles 3 meters in front of control room and no obstacles 2 meters in front of maintenance room |
Brands of Main Components | |
Contactor | Imported brand or Chinese brand |
Fuse | Chuantai |
Alloy Resistance | Kaixiang(self-developed) |
Data Processing Software | Kaixiang(self-developed) |