Rlc Load Bank 1000kVA AC Load Bank for Generator Testing

China Rlc Load Bank 1000kVA AC Load Bank for Generator Testing, Find details about China Rlc Load Bank 1000kVA, AC Load Bank from Rlc Load Bank 1000kVA AC Load Bank for Generator Testing

Model NO.
RLC Load Bank 1000kVA
Loading Method
Static Load
Display
Digital
Control
Computer Control
Weight
1000-2000Kg
Power Source
AC380V
Oil Cylinder Position
No
Color
Variety
Dimension
About 2440 mm*1400mm*1680mm
Load Tolerance
5%
Trademark
triumph load
Transport Package
Plywood Cases
Specification
1000KVA
Origin
China
HS Code
90303390
Model NO.
RLC Load Bank 1000kVA
Loading Method
Static Load
Display
Digital
Control
Computer Control
Weight
1000-2000Kg
Power Source
AC380V
Oil Cylinder Position
No
Color
Variety
Dimension
About 2440 mm*1400mm*1680mm
Load Tolerance
5%
Trademark
triumph load
Transport Package
Plywood Cases
Specification
1000KVA
Origin
China
HS Code
90303390
Product introduction
RLC Load Bank 1000kVA AC Load Bank for Generator Testing
Main functions:

Introduction:
Resistance/inductance/capacity/Portable Intelligent load bank 
Intelligent AC load bank main used to test the capability and aging degree for high-power ups on-line, inverter, switch power and diesel generator set for electric power, telecom department and manufacturer. It can ensure the reliability of constant power charge that adopts uniformly stepped power input, energy consumption work model and forced air-cooling model. It is of high power density, no red hot phenomenon and automatic protection function overheated. It can't be overheated and broken when the fans stop working. The complete machine can be operated simply and maintain convenient that adopts module design. It can test voltage and current according to client's request, and provide scientific test measures for high-power AC equipment.
Main functions of  Regenerative Power Load Banks 
1. Users can set adjustable discharge power according to capability parameter and test request.
2. Voltage and current value can be displayed with multi-functional digital meter.
3. AC load bank is of all kinds of specifications and series, and include resistance, inductive and capacitive load.
4. Two or more Intelligent AC Load Bank can operate in parallel.
5. It can make stable state test. 
6. Remote control by software.
7. Testing data can be saved or transferred by RS485, data can form curve, to be printed. 
Function options of  Regenerative Power Load Banks 
Intelligent AC Load Bank has two control patterns: position machine software control and local panel control
Intelligent AC load bank (LED): multi-function digital special meter of 0.5 step can be test and display: AC voltage, current, active power, power factor and frequency. It can communicate with PC via RS485 interface.
Intelligent AC load bank (LCD): Special LCD meter display: AC voltage, current, active power, power factor and voltage frequency. It is of the harmonic analysis function of 1-40 times, and can communicate with PC via RS485 interface.

Specification
System Parameter
Rating voltage/frequency400V, 3 phase 4 wire 50Hz
Max Load PowerApparent Power: 1000KVA 
Resistive Load: 800kW
Inductive Load: 600KVAR
Load ResolutionResistive Load: 12 steps 1kW,2kW,2kW,5kW,10kW,10kW,20kW,50kW,100k,200kW,200kW,200kW 
Inductive Load: 11 steps  
1KVAR,2 KVAR, 2KVAR, 5KVAR, 10KVAR, 10KVAR, 20KVAR, 50KVAR, 100KVAR,200KVAR,200KVAR 
Power Factor0.8(lag)
Load Tolerance (each step)±5%
Load Tolerance (overall)±3%
Fan &Control VoltageExternal AC 3 phase 4 line, 380V/50Hz  
Wire Connection Load bank input--Copper bar (star coupling "Y")
Control power input--Connector-bar
Communication InterfaceRS485,RS232
InsulationF
Max Protection GradeIP21
Duty CycleContinuous  
CoolingForced air cooling, by Fan; horizontal inlet air, horizontal exhaust cooling
TransportationHoisting, there are lifting lug in top of casing
ColorGrey RAL7035 or as required
DimensionAbout 2units* 2440 mm×1400mm×1680mm(L×W×H)(
Operating Environment Parameter
Workplace Indoor
Ambient Temperature-10ºC~+50ºC
Relative Humidity≤95%
Atmospheric Pressure86~106kPa
Brands of Main Components
Contactor  Schneider
Fuse Miro
PLC Siemens
Alloy Resistor  Kaixiang
Data Processing Software Kaixiang
Why Choosing Us?
1. Hebei Kaixiang Electrical Technology Co., Ltd is the largest and earliest load bank manufacturer in China, we have 20 years experience. Our factory has 25,000 square meters. We are the leader in domestic market.
2. The sole company that draft the enterprise standard "dry-type load bank".
3. China Power Industry Top Ten Famous Products.
4.  China Power Supply Recommend Products.
5.  Our Intelligent High Power Marine Use Gensets Dry Type Load Bank wins International advanced level by Science and Technology Department of Hebei Province.
6. Certified with China Classification Society (CCS) and ISO9001:2008 Quality Certificate.
7.  Certified by SGS.

certificate
Rlc Load Bank 1000kVA AC Load Bank for Generator Testing
Rlc Load Bank 1000kVA AC Load Bank for Generator Testing

Rlc Load Bank 1000kVA AC Load Bank for Generator Testing

Rlc Load Bank 1000kVA AC Load Bank for Generator Testing
Rlc Load Bank 1000kVA AC Load Bank for Generator Testing
Rlc Load Bank 1000kVA AC Load Bank for Generator Testing