Indoor Type High Voltage Zn63[Vs1]-12 Vacuum Circuit Breaker

China Indoor Type High Voltage Zn63[Vs1]-12 Vacuum Circuit Breaker, Find details about China Circuit Breaker, Breaker from Indoor Type High Voltage Zn63[Vs1]-12 Vacuum Circuit Breaker

Model NO.
ZN63[VS1]-12
Poles Number
3
Type
Circuit Breaker
Function
Conventional Circuit Breaker, Circuit-Breaker Failure Protection, Overcurrent Protection
Certification
VDE, ISO9001-2000, CE, CB, CCC
Rated Voltage
12kv
Trademark
WEHOPE
Transport Package
Standard Export Package
Specification
Standard
Origin
China
HS Code
9107000000
Model NO.
ZN63[VS1]-12
Poles Number
3
Type
Circuit Breaker
Function
Conventional Circuit Breaker, Circuit-Breaker Failure Protection, Overcurrent Protection
Certification
VDE, ISO9001-2000, CE, CB, CCC
Rated Voltage
12kv
Trademark
WEHOPE
Transport Package
Standard Export Package
Specification
Standard
Origin
China
HS Code
9107000000
General Introduction

VSI(650MM) series Vacuum Circuit Breaker is an indoor type high voltage equipment with GB/T 1984,JB3855 and related IEC Standards.It can be frequently operated and has function of more times breaking capacity and fast reclosing.The Circuit Breaker is designed as front and backside structure,it can be used as fixed type and also can be used with withdraw truck.

Main Technical Parameters(12KV)
sl.NoItemUnitData
1Rated voltageKV12
2Maximum working voltageKV12
3Rated CurrentA630~1250630~1600630~1600
4Rated short circuit breaking currentKA202531.5
5Rated short-circuit switching currentKA506380
6Rated peak withstand currentKA506380
74S rated short-circuit withstand currentKA202531.5
8Rated insulation level1min power frequency withstand voltage(rated breaking before and after)KV42(fracture 48)
impulse withstand voltage(rated breaking before and after)75(fracture 84)
9Rated operating sequence O-0.3S-CO-180S-CO
10Mechanical lifeTimes 10000
11Rated short-curcuit current breaking timesTimes50
12Rated Operating Mechanism Closing Voltage(DC)VAC,DC 110,220
13Rated Operating Mechanism Opening Voltage(DC)VAC,DC 110,220
14Contact opening distancemm11 ±1
15Overtravel(the length of contact spring compression)mm3.5±0.5
16Closing/Opening Time Difference Among Three Phasems≤2
17Contact closing bounce timems≤2
18Average opening speedm/s0.9-1.2
19Average closing speedm/s0.5-0.8
20Tripping Time Maximum operating voltages≤0.05
Minimum operating voltage≤0.08
21Closing times0.1
22The main circuit resistance of each phase 630≤50 1250≤45 1600≤40
23Allowed Consumpted thickness of Contactsmm3