Hot Dip Galvanized
Guy Hook is used to prevent guy wire strand
from slipping on the pole. The half oval side of clamp
prevents damage to the guy stand.
Tension Clamp For Aluminium Conductor TECHNICAL SPECIFICATION 4 | Connector name | | Compression connector grounding pin for cable # 2 |
5 | Raw material | | Body: Electrolytic copper manufactured by extrusion, high resistance- With inhibitor |
6 | Driver to press | | Copper |
7 | Driver to connect on the pike grounding | AWG | 2 |
8 | Applied standards | | ANSI C 119.4, IEEE837 |
9 | Quality certificate | | ANSI C 119.4, IEEE837 |
10 | Main admissible diameter | inch(mm) | 5/8 (15.8) |
11 | Permissible diameter | inch(mm) | 0.29 to 0.23 (7.4 to 5.8) |
12 | DN-DS certificate | | Attach acceptance certificate and homologation |
13 | Identification mark | | Each connector should be marked on the body with the manufacturer symbol, catalog number, application driver ranges and die number to occupy with the hydraulic tool for installation |
14 | Packing | | The connectors should be in a package that indicates in its exterior the range of application and prevent external agents from damaging it and causing premature oxidation |
1. SCOPE
This specification covers the design and construction of Tension of Tension Clamps to be used for the termination of aluminium-conductors at terminal poles and section poles.
The Clamps are suitable for used in Tropical zone, with a maximum ambient temperature of approximately 40
ºC and a mean annual temperature of approximately 28
ºC with high humidity and heavy rainfall.
2. STANDARD
this specification is make reference to and comply with the requirements of following standard:
BS 3288:1973 - Insulator and Conductor fitting for
Overhead Power Lines
BS 729 - Hot dip Galvanised
3. ELECTRICAL SYSTEM
The Clamps will be designed for use on a 3 phase
,3 wires
, 33/22/11/6.6kv
,50 Hz
, primary distribution system with the star-point of the source-end transformer earthed through an Earthing Resistor.
4. DESIGN AND CONSTRUCTION
The Clamps are manufactured from material which is not cause chemical corrosion when in constant contact with aluminium conductor. They are have a tensile strength that the breaking strength that are not less than the breaking strength of the conductors to be connected.
The Clamps are properly designed such that will not cause any unnecessary strain and abrasion on the surface of conductors.
5. SIZE OF CLAMPS
The Clamps aredesigned to accommodate the following sizes of Aluminium conductors:
a. 50mm
2 Alu. Conductor
b. 100 - 150mm
2 Alu. Conductor
6. MARKINGS
The Tension Clamps will be indelibly marked as Customer Requirment.
7. INSPECTION AND TESTS
For evaluation purposes, we will supply the following items to our cusotmer
a. A sample of the Tension Clamp complete with all accessories.
b. A copy of the test report on tests conducted in accordance to BS 3288 and BS 729