China Electrical Testing Portable Power Meter Energy Meter Calibration Test Equipment, Find details about China Energy Meter Calibration Equipment, Energy Meter Calibrator from Electrical Testing Portable Power Meter Energy Meter Calibration Test Equipment
Details : | |
² Accuracy classes: 0.05%, 0.1% ² Measurement of energy meter errors, display of voltage, current, power, power factor, frequency etc. ² Measurement of harmonics of 2nd to 51st ² Measurement of clock error (of energy meter) ² Measurement of transformation ratio for CT ² Communication examination for energy meters ² Measurement for register ² Detection of wiring failures and calculation of electricity compensation ² USB and communication ports available ² Self adjusted clamp-on CT's (KHPEC's patent) provided ² Double of power supply via lithium battery or PT |
General | |||
Power supply | AC57~450V, 50~60Hz | ||
Power consumption | About 10VA | ||
Ambient temperature | -20ºC--+40ºC (accuracyassured) | ||
Relative humidity (not condensing) | 40%-95% | ||
Dimension(L×W×H, mm) | 249×154×58 | ||
Weight | 1.8Kg | ||
Warm-up time | < 3 minutes | ||
Battery endurance | 4 hours | ||
LCD color display | 5.7", 320×240 TFT | ||
Communication port | RS 232 | ||
Safety | |||
Declaration of conformity | CE conformed | ||
Operation reference | |||
Measuring ranges | |||
Voltage | AC 30~480V | ||
Current: | Direct connection-1A, 5A Via clamp-on CT's: 5A, 20A(±0.2%, self adjusted), 100A, 500A, 1000A(±0.5%) | ||
Frequency | 45~65Hz | ||
Phase | -180 º ~+180º | ||
Constant of pulse | 5A: FL=3.6×104P/KWh FH=3.6×107P/KWh Others:FL=36000×5/rated current (P/KWh) FH=3.6×107×5/ rated current (P/KWh) | ||
Harmonic measurement | Range: 2nd ~51st Accuracy: ±0.01% (compared to 100% fundamental wave) | ||
Transformation ratio deviation | < ±0.5% | ||
Voltage deviation | < ±0.01% | ||
Frequency deviation | < ±0.01%(45-55Hz) | ||
Influence of temperature | < ±5ppm/ ºC(typical) | ||
Variation in 24hrs. | <±0.02% (class 0.1) | <±0.01% (class 0.05) |