General:KYN1-12 drawable type AC metal clad switchgear is used in 10kV, three phases, 50Hz power supply system for
controlling, transmission and distribution. With several year's experiences on improving design, this kind of
switchgear is suitable to be used in frequent operations specially and a new type of reinforced insulation and
busbar with bypass has been developed update.
The design and structure of the switchgear conforms to IEC standards and GB 3906-91 standards. It has
welding and package structure. The protection level of its enclosure is IP2X. It consists of trolley, front cubicle,
back cubicle, instrument room of relay and the small busbar room on its ceiling. The front switchgear and the
back switchgear are connected by bolts, the instrument room of relay and the body are connected by vibration
absorber; Other parts are separated by steel sheets. It has the function of aerial incoming and outgoing line,
cable incoming and outgoing and liaison between left parts and right parts.
Structure:The enclosure of KYN1-12 indoor AC metal-clad draw-out switchgear is welded by bent steel plates. It consists
of four parts: instrument compartment, front compartment, rear compartment and truck compartment. A kind of
bolt connection is used in between the front compartment and the rear compartment. And a kind of shock
absorber is used in between the instrument compartment and the enclosure. Steel plates separate each
compartment. Several schemes could be available, such as overhead incoming and outgoing, cable incoming
and out-going, contact to left or contact to right, etc.
Product feature:KYN1-12 truck type 10KV HV Switchgear is complied with International Standards as well as Nation Standards.
It is a draw out truck trolley cubicle. Both of the enclosure and isolating plate of each functional units is made of
2.5mm cold rolled steel sheet, the surface is treated with phosphatization, anticorrosion, static plastic-pouring;
Each part is connected by bolt of high intensity. It is featured by beautiful looking, easy installation and
maintenance.
The frame of the trolley is made of cold rolled steel sheets in the process of punching and welding. The trolley
has separate exhaust passage to the ceiling. Varieties of trolley have the same height and depth, so truck with
the same specification can be interchanged. There are isolating position, testing position and working position
inside the trolley, each of them has orientation device and position indicator. The trolley can be seen on each
position as well as seen on the position indicator. When the trolley goes into the switchgear, the enclosure can
be connected with earthing system of the switchgear. There are controlling indicator and off and on indicator of
the spring mechanism of the circuit breaker on the panel of the truck.
The guide rails of the circuit breaker room are firm and flat. The truck can run smoothly on the working position
and testing position. The valve is made up of nonmetallic insulating epoxy plates. When the truck is on the
isolating position/ testing position, the static contact and the moving contact of the major loop are isolated by
valve; When the truck enters into the working position, the valve opens automatically. The off and on condition
of the circuit breaker, off and on mechanical position indicators and stored energy/ released energy indicator
can be seen on the panel of the trolley. Only when the isolating plates between the truck room and cable
compartment are pulled out, can the worker get into the switchgear to install or maintain the cable.
On the upper part of the trolley room, busbar room and cable room, there is compression release device. When
the internal fault arc occurs in the circuit breaker or busbar room and cable room, the compression release
metal plates at the ceiling opens automatically.
Ordering notice:Please provide the followings
A. Main wiring scheme code, single line system diagram, pareto diagram and layout plan.
B. Secondary principle diagram, terminal pareto diagram. If without it, conform with the manufacturer's terminal
pareto diagram.
C. The type, specification and quantity of the electrical components of switchgear.
D. Summary table of electrical equipment.
E. Please provide span and height dimensions if busbar bridge(between two ranks of switchgear or between
switchgear and wall) is needed.
F. Please indicate if switchgear shall be on the special condition.
G. Please indicate type and quantity of other accessories, if necessary.
Main Technical Data:Rated Voltage (kV) | 12 |
Rated Current (A) | 630, 1250, , 3150 |
Rated short-circuit breaking current (KA) | 20 ,31.5, 40 |
Rated short-circuit making current (KA) | 50, 80, 100 |
Rated peak withstand current (peak value) (kA) | 50, 80, 100 |
Rated short-time withstand current (r.m.s.) (kA/s) | 20/4, 31.5/4, 40/4 |
Rated 1min power frequency condenstaion withstand voltage (kV) | 42 |
Isolating distance insulation withstand voltage power frequency/lighting impulse (kV) | 48/85 (peak value) |
Phase to phase and phase to earth insulation withstand volatge power frequency/lighting impulse (kV) | 42/75 (peak value) |
Nominal creepage distance (mm/kV) | 20 |
Mechanical endurance | >10000 |
Rated current breaking times | >10000 |
Rated short-current breaking times | 50, 30 |
Opening time (S) | <0.06 |
Closing time (S) | <0.1 |
Degree of protection | IP2X |
Operation mechanism and operation voltage (AC or DC) | DC 110,220 AC220 |
Weight (including packing ) kg | <800 |
Dimensions (Width×Depth×Height) mm | 800×1500×2200 840×1500×2200 880×1500×2200 1000×1650×2200 |
Packing dimensions (Width×Depth×Height) mm | 1000×1750×2500 1040×1750×2500 1080×1900×2500 1200×1900×2500 |
Our Services1. | Pre sale service |
a. | make technical solution |
b. | send quotation, technical data sheet and drawing |
c. | prepare power transmission plan, testing plan,and shipment plan |
2. | In sale service |
a. | supervise the manufacturing schedule totally in accordance with the plan |
b. | send photos to customer during every manufacturing process(hold point) |
c. | inform the customer one week before testinng. |
3. | After sale service |
a. | installation and commissioning, training the workers |
b. | quick response within 12 hours any time |
c. | provide 12 months gurantee period normally. |
FAQ1. Q: | What is your delivery time ? |
A: | Depend on the type of transformer. |
2. Q: | What is your payment term? |
A: | 30% advance by T/T , 70% before delivery by T/T or L/C or we can discuss about it. |
3. Q: | What kind of starndard you follow? |
A: | IEC, ANSI, CSA, GB, etc |
4. Q: | What kind of supporting documentation you can provide normally |
A: | Quotation,outline drawing,manufacturing plan, quality control plan testing plan, financial report, type test report(KEMA, CESI),reference list,etc |
5. Q: | What is your normal wanrranty period? |
A: | 12 months after transformer operation. |
6. Q: | Can u do installation and commissioningin user's site? |
A: | Yes, we can send our installation team to user's country for service. |
7. Q: | Do you have any experience in this kind of transformer? |
A: | Yes, we can provide reference list for check. |
8. Q: | Are you manufacturer or trading company? |
A: | Manufacturer with own import & export company. |
Our advantages:Quality Assurance
--From the very beginning, VILLE ensures quality in every step to achieve the best quality.
Experience Sharing
--With more than 30 years' experience in power industry, VILLE brings you an optimized solution.
Global Service
--Wherever you are, VILLE global network will support and provide you with value.
Quick Response
--In response to your needs without delay, VILLE knows the value of your time.
Thanks for choosing VILLE as your reliable partner and
please trust both of us will create a brilliant future!