China IEC Standard Power Quality Measuring Instrument Power Quality Test Device, Find details about China power quaity measuring instrument, power quality test device from IEC Standard Power Quality Measuring Instrument Power Quality Test Device
Mechanical | Environment | ||
Size | 263*168*65mm | Working condition | 0ºC~+45ºC, <90%RH |
Weight | 2.0kg | Storage condition | -20ºC~+50ºC, <95%RH (no condensing) |
Power supply | Storage | ||
Adapter input | 110V-240V, 50Hz | Type | TF card |
Adapter output | 15V, 3A | Capacity | 8G |
Battery | Rechargeable lithium-ion battery 5000mAh | Standard | |
Working time | ≥5h | Method | IEC 61000-4-30 |
Charging time | Min. 5 hours (ambient temperature 25ºC) | Performance | IEC 61000-4-30 class A |
Power saving function | LCD backlight brightness and standby time are adjustable. | Flicker | IEC 61000-4-15 |
Display | Harmonics | IEC 61000-4-7 | |
Size | 112.8*84.6mm | Power decomposition | IEEE 1459 |
Color | 260K color | Crosstalk | |
Resolution | 640*480 | Between voltage input terminals | -60dB (at nominal frequency) |
Brightness | Max. 350 cd/m²(Typ.), brightness adjustable | Between voltage and current input terminals | -95dB (at nominal frequency) |
Contrast | 500:1 (Typ.) | Common-mode suppression | |
Viewing angle | 70/70/50/70 (Typ.)(CR≥10) (Left/Right/Up/Down) | CMRR | >60dB |
Electromagnetic compatibility | Environment reliability | ||
Standard | Class 4: GB/T 17626.2-2006 Electrostatic Discharge Immunity Test | Standard | GB/T 2423.1-2008: low temperature |
Class 3: GB/T 17626.3-2006 Radiated, Radio Frequency Electromagnetic Field Immunity Test | GB/T 2423.2-2008: high temperature | ||
Class 3: GB/T 17626.4-2008 Electrical Fast Transient/burst Immunity Test | GB/T 2423.4-2008 High and low temperature alternating humidity heat test | ||
Class 3: GB/T 17626.5-2008 Surge Immunity Test | GB/T 2423.5-1995 Shock | ||
Class 3: GB/T 17626.8-2006 Power Frequency Magnetic Field Immunity Test | GB/T 2423.10-2008 Vibration | ||
Class 3: GB/T 17626.9-1998 Pulse Magnetic Field Immunity Test | GB/T 2423.22-2002 Temperature change | ||
Class 3: GB/T 17626.12-1998 Oscillatory Waves Immunity Test | |||
Safety | |||
Standard compliance | GB 4793.1-2007/IEC 61010-1:2001: Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use Part 1: General Requirements Safety class: CATIII 1000V/CATIV 600V | ||
Banana input terminal | CATIII 1000V/CATIV 600V |
Function | Item | Content |
Recorder | Oscilloscope | Real-time voltage waveform of A, B, C and N phase |
Voltage Current Frequency |
| |
Power and electric energy | Active power, reactive power, apparent power, power factor, displacement power factor, active energy, reactive energy, apparent energy. | |
Voltage harmonic | THD, DC, 1st~50th harmonic, 0~49th inter-harmonic, 1st~35th high order harmonic. | |
Current harmonic | THD, DC, KF, 1st~50th harmonic, 0~49th inter-harmonic, 1st~35th high order harmonic. | |
Harmonic power | THD, DC, 1st~50th harmonic power. | |
Flicker | PST (short-term flicker), PLT (long-term flicker) . | |
Imbalance | Positive sequence voltage, positive sequence current, negative sequence voltage, negative sequence current, zero sequence voltage, zero sequence current, imbalance. | |
Energy consumption | Power decomposition of active power, reactive power, apparent power, power of line loss, cost of line loss, pollution evaluation. | |
Demand | Demand | |
Event recording | Voltage swell, voltage sag, voltage interruption, surge current, over limit of PST, over limit of PLT, over upper limit of voltage, over lower limit of voltage, over upper limit of frequency, over lower limit of frequency, fluctuation of steady state voltage, over limit of voltage imbalance, over limit of voltage THD, over limit of 1st~50th voltage harmonic, over limit of 2nd~50th current harmonic. | |
Inverter | DC | DC voltage, DC current, DC power, ripple voltage, content ratio of ripple voltage. |
AC | Frequency, voltage effective value, current effective value, total apparent power, total active power, total power factor, fundamental power, fundamental power factor. | |
Efficiency | Conversion efficiency | |
Transient | Voltage | Voltage effective value, effective value of voltage half-wave, voltage positive peak, voltage negative peak. |
Current | Current effective value, effective value of current half-wave, current positive peak, current negative peak. | |
Frequency | Frequency | |
Event recording | Voltage swell, voltage sag, voltage interruption. | |
Monitor | Monitor | Voltage effective value, 1st~50th voltage harmonic, PLT, voltage swell, voltage sag, voltage interruption, fluctuation of steady state voltage,voltage imbalance |
Parameter | Type | Content |
Frequency | Nominal frequency | 50Hz/60Hz |
Measurement method | Calculation of 10/12 cycles. | |
Resolution | 0.001Hz | |
Width range | 42.5Hz~69Hz | |
Measurement accuracy | ±0.001Hz | |
Voltage effective value | Measurement method | Calculation from mean square value of 10/12 cycles. |
Resolution | 0.001V | |
Measurement range | 1V ~ 1000V | |
Measurement accuracy | 0.1% of nominal voltage | |
Current effective value | Measurement method | Calculation from mean square value of 10/12 cycles. |
Resolution | 0.001A | |
Measurement range | Different CT varies in measurement range. | |
Measurement accuracy | 0.1%+CT accuracy | |
Power | Measurement method | P=(U1*I1)2 (of 10 wave cycles) S=U2*I2 (of 10 wave cycles) U1: instantaneous value of voltage I1: instantaneous value of current U2: effective value of voltage I2: effective value of current P: active power Q: reactive power S: apparent power; Cos φ: power factor |
Resolution | 0.001W | |
Measurement range | It depends on voltage range and range of CT. | |
Measurement accuracy | 0.5%+CT accuracy | |
Voltage and current harmonic | Measurement method | Based on IEC61000-4-7, window amplitude analysis of 10 wave cycles |
Test item | Effective value, content ratio, phase angle | |
Number of times/frequency | 50th /50Hz-2500Hz | |
Measurement accuracy |
| |
Inter-harmonic current and voltage | Measurement method | Based on IEC61000-4-7, window amplitude analysis of 10 wave cycles |
Test item | Effective value, content ratio, phase angle | |
Number of times/frequency | 50th /25Hz~2475Hz | |
Measurement accuracy |
| |
Harmonic power | Measurement method | Based on IEC61000-4-7, window amplitude analysis of 10 wave cycles |
Test item | Effective value, content ratio, phase angle | |
Number of times/frequency | 50th /50Hz~2500Hz | |
Measurement frequency |
|
Parameter | Type | Content |
High order harmonics of voltage and current | Measurement method | Based on IEC61000-4-7, window amplitude analysis of 10 wave cycles |
Measurement type | Effective value, content ratio, phase angle | |
Number of times/frequency | 35th / 2100Hz~8900Hz | |
Measurement accuracy |
| |
Imbalance | Measurement method |
|
Resolution | 0.001% | |
Measurement accuracy | Voltage imbalance: ±0.2% Current imbalance: ±0.5% | |
Flicker | Test item | Short-term flicker (PST), long-term flicker (PLT) |
Measurement method | According to IEC61000-4-15, PST (10 minutes) and PLT (2 hours) are calculated. | |
Measurement range | 0 ~ 20 | |
Measurement accuracy | ±5% |