China 50Hz to 60Hz Shore Frequency Converter Static Frequency Converter 100kVA 300kVA 500kVA 600kVA 800kVA 1000va 1200kVA 1600kVA 2000kVA, Find details about China Shore Power Supply, Shore Power Source from 50Hz to 60Hz Shore Frequency Converter Static Frequency Converter 100kVA 300kVA 500kVA 600kVA 800kVA 1000va 1200kVA 1600kVA 2000kVA
model | 331000 | 331500 | 332000 | 333000 | 334000 | 335000 | 336000 | 338000 | 331600 | |
Capacity(KVA) | 100 | 150 | 200 | 300 | 400 | 500 | 600 | 800 | 1600 | |
Input | Voltage | 400V±15% 3phase 4wires or 3phase 5wires | ||||||||
Frequency | 45-65Hz | |||||||||
Power Factor | ≥0.90 | |||||||||
Output | Voltage | 3phase 3 wires ,voltage(300-500V/690)can be chosen | ||||||||
Frequency | 50Hz/60Hz can be chosen | |||||||||
Frequency Stability | ≤0.01%(0-100% when load are changing,output frequency are not changing ) | |||||||||
Load Stability | ≤3%(100% pure resistance load) | |||||||||
Overload Ability | 110% 1hour ,150% 10minutes | |||||||||
Wave Distortion | Pure sine wave,THD≤3% | |||||||||
Efficiency | ≥90%(100% loads) | |||||||||
Display | Input/output voltage/ frequency,3phase phase voltage/current,active power .working time.history error etc. | |||||||||
Control mode | IGBT/SPWM Pulse width adjustment mode | |||||||||
Protection Class | IP54 | |||||||||
Insulation Reactance | >2MΩ | |||||||||
Pressure endurance Insulation | 1800Vac/5Ma/1minute | |||||||||
Noise Level | 50dBA @1meter | |||||||||
Cooling Model | Converter:heat pipe cooling transformer:Compulsive fan cooling | |||||||||
Protection Function | The output power supply have perfect protection function of over voltage, over current, short circuit, converter overheat . Consider the different control of the ship's electricity load, when the output load capacity reach the set value,will alarm, so as to control the electricity load | |||||||||
Environment | -10ºC~+50ºC and 0~90% | |||||||||
Indoor Dimension (W×L×H)mm | 600* 1320* 1490 | 1450*850*1880 | 1910* 1160* 1880 | 3100*830*2260 | 4100*830*2260 | |||||
Outdoor Dimension (W×L×H)mm | 3300*2400*2600 | 4500*2400*2600 | 6000*2400*2600 |
model | 333000 | 3350000 | 33100000 | |
Capacity(KVA) | 3000 | 5000 | 10000 | |
Input | Voltage | 400V±15% 3phase 4wires or 3phase 5wires | ||
Frequency | 45-65Hz | |||
Power Factor | ≥0.90 | |||
Output | Voltage | 3phase 3 wires ,voltage(300-500V/690)can be chosen | ||
Frequency | 50Hz/60Hz can be chosen | |||
Frequency Stability | ≤0.01%(0-100% when load are changing,output frequency are not changing ) | |||
Load Stability | ≤3%(100% pure resistance load) | |||
Overload Ability | 110% 1hour ,150% 10minutes | |||
Wave Distortion | Pure sine wave,THD≤3% | |||
Efficiency | ≥90%(100% loads) | |||
Display | Input/output voltage/ frequency,3phase phase voltage/current,active power .working time.history error etc. | |||
Control mode | IGBT/SPWM Pulse width adjustment mode | |||
Protection Class | IP54 | |||
Insulation Reactance | >2MΩ | |||
Pressure endurance Insulation | 1800Vac/5Ma/1minute | |||
Noise Level | 50dBA @1meter | |||
Cooling Model | Converter:heat pipe cooling transformer:Compulsive fan cooling | |||
Protection Function | The output power supply have perfect protection function of over voltage, over current, short circuit, converter overheat . Consider the different control of the ship's electricity load, when the output load capacity reach the set value,will alarm, so as to control the electricity load | |||
Environment | -10ºC~+50ºC and 0~90% |