China 0.6/1 Kv LV Aerial Bundled Cable 3 Core Phase 16mm2 AAC 16mm2 Bare AAAC Messenger, Find details about China ABC Cable, Overhead Cable from 0.6/1 Kv LV Aerial Bundled Cable 3 Core Phase 16mm2 AAC 16mm2 Bare AAAC Messenger
Packaging Details: | drum |
---|
Aerial insulation ABC cableDetailed Product DescriptionSingle core aerial cable(overhead cable)conductor: cooper or aluminiuminsulation:XLPE, PE, PVCApplicationOverhead insulated cable may be installed in the streets with dense trees close to the buildings, site of urban construction and lead to transformer. Using this cable, it is unnecessary to prune the branches, so that reduce the across and parallel distance of the cable. It is convenient to install and high mobility. It can reduce accidents of electric shock and power failure causing by circuit troubles. To guarantee supplying of electric power for industry, Single core aerial cable (overhead cable) could make sure residents safety. It is especially suitable for an old city, which has densely buildings, densely population and narrow streets. Our overhead insulated cables have formed a system, such as single core, two-core, three-core and four-core. There are conductors of aluminum, copper or aluminum conductors steel-reinforced.
Ref. No. | Description | Unit | Data |
LV AERIAL BUNDLE CABLE (600/1000V) 3x16+16mm2 | |||
1 | Manufacturer | HENAN JISNHUI CABLE GROUP CO.,LTD | |
2 | Standards | IEC 60502 | |
3 | Nominal voltage (Uo/U) | KV | 0.6/1kv |
4 | Phase conductor | ||
4.1 | Phase conductor material | AAC | |
4.2 | Cross-section of phase conductor. | mm2 | 16 |
4.3 | No. Of strands wires/Single wire diameter | 7/1.7 | |
4.4 | Diameter of phase conductor | mm | 5.1 |
4.5 | Thickness of insulation XLPE | mm | 1.2 |
4.6 | External diameter of individual core | mm | 7.5 |
4.7 | Modulus of elasticity | N/mm2 | 59000 |
5 | Netural conductor | ||
5.1 | Netural conductor material | AAAC | |
5.2 | Cross sectional of neutral wire | mm² | 16 |
5.3 | No. Of strands wires/Single wire diameter | 7/1.7 | |
5.4 | Diameter of neutral wire | mm | 5..1 |
5.5 | Ultimate tensile strength of suspension wire | KN | 4.69 |
5.6 | Thickness of suspension wire covering | mm | Bare |
6 | Overall diameter of bundle | mm | 18 |
7 | Total weight of bundle per km | kg/km | 241 |
8 | Maximum DC resistance / km at 20°C - Phase conductors - Neutral conductor |
Ω /km Ω /km |
1.91 2.217 |
9 | Working inductance | MH/km | 0.23 |
10 | Working capacitance | mF/km | 0.60*10-3 |
11 | 1 sec. Thermal short circuit current (maximum conductor temperature 130°C, final conductor temperature. |
KA |
0.9 |
12 | Maximum continuous current at 35°C ambient temperature 0.6m/sec wind and 90°C conductor temperature. - Phase conductors - Neutral conductor |
A A |
110 105 |
13 | Zero sequence impedance | Ω/km | N/A |
14 | Modulus of elasticity | N |