No.DESCRIPTION TION UNID.VALUE REQUIRED VALUE OFFERED
     
1.0.0GENERAL DATA    
1.1.0Maker   ABB/SAC
1.2.0Model  RET650
1.3.0Country of manufacture  Sweden/China
     
2.0.0CONSTRUCTIVE ASPECTS    
2.1.0FrequencyHz6050/60Hz
2.2.0WeightKgIndicate300
2.3.0Approximate Dimensions (Height, Width, Depth) (,,)MmIndicate2260*800*600mm(H*W*D)
2.4.0Mounting  YesYes
2.5.0Operating temperature ° C-10 to +55-25 to +55ºC
2.6.0Storage temperature° C-40 to +70-40 to +85ºC
2.7.0Relative Humidity Range%10 to 90<93%
3.0.0TENSION AND CURRENT ANALOGUE INPUTS   
 Number of analog inputs  2412
3.1.0Voltage inputs   
 - Number of entries Referring to Fig.  
 - Rated voltage (Vn) Vac110110V
 - Operating marginVac0 - 340 
 - Maximum permanent voltage Vac420420V rms
 - Maximum tension for 10 seconds Vac450450V rms
 Burden GOES<.02 To 110 Vac<0.05 VA
3.2.0Current Inputs    
 - Number of entries  fifteen6
 - Rated current (In)
(IN)
Amp.11/5A
 - Operating margin Amp.(0-100) x In 
 - Maximum permanent current Amp.4 In20A
 - Maximum current for 1 sec. Amp.100 In500A
 BurdenGOES<0.02 to 1A<0.05 VA
 
4.0.0DEPARTURES AND BINARY ENTRIES  YesYes
4.1.0Programmable Trip and Signaling Outputs    
 - Number of contacts (minimum)
-()
No.2424
 - Maximum operating voltage
-
Vac / Vdc250 Vac, Vdc250 Vac, Vdc
 - Test voltage at the open contact, for 1 min.
-,1.
Vrms1000Meet
 - Permanent current carrying capacity
-
TOReferring to Fig.5A
 - Current carrying capacity for 1 sec
- 1s
TO1010A (3s)
10A (0.5s)
 - Cutting capacity TO110 V / 0.4 A48V / 0.5 A
110V / 0.1 A
220V / 0.04 A
125V / 0.35A
 - Closing capacityTO30 A (for 0.2 s) 10 A (per 1.0 s)Meet
4.2.0Inputs    
 - Programmable input contacts  YesYes
 - Number of input contacts (minimum)
()
No.32Max.50
 - Voltage range V24 - 25024...250 V DC
 - Power consumption per input W0.2 W to 125 V<0.3 W
4.3.0LED's of signaling  YesYes
 - relay status  3Meet
 - the performance of the protection functions
-
 15 (6 red and 9 yellow)
15(69)
15
4.5.0Interfaces    
 - Large HMI on the relay front panel
HMI
 YesYes
 - Front Ethernet port, PC connection
-,PC
 1 port, RJ451 port, RJ45
 - Ethernet optical port for remote communication  1 port, STMeet
4.6.0Remote Communication    
 - Communication protocol  IEC 61850IEC 61850
 - Communication speed MBps100100 MBits/s
5.0.0AUXILIARY SUPPLY    
5.1.0Auxiliary Rated Voltage Vcc90 to 25088...300 V DC
5.2.0Tolerance %± 20%15%
5.3.0Typical Consumption    
 - In normal operating condition
-
Wfifty30W
5.4.0Auxiliary insertion power TO<5 A, for 0.1 sec<5 A, for 0.1 sec
6.0.0SPECIAL TESTS    
6.1.0EMC Immunity (IEC 60255-22; 22-1; 22-2; 22-3; 22-4)
(IEC 60255-22;22-1;22-2;22-3;22-4)
 YesYes
6.2.0EMC Emission (IEC 60255-22, IEC 61000-4, IEEE / ANSI C37.90)
(IEC 60255-22,IEC 61000-4,IEEE / ANSI c37.90)
 YesYes
6.3.0Insulation (IEC 255-5)
(IEC 255-5)
 YesYes
6.4.0Mechanical Efforts IEC255-21, IEC68-2
iec255-21,iec68-2
 YesYes
6.5.0Environmental Testing IEC60068, IEC68-2
iec60068,iec68-2
 YesYes
7.0.0PROTECTION FUNCTIONS    
7.1.0List of included functions    
 Transformer Differential (87T)  YesYes
 Distance between phases and ground phase (21 / 21N)
(21/21 n)
 Do notNo
 Phase overcurrent and ground phase (50/51, 50 / 51N)  YesYes
 Directional phase and ground phase overcurrent (67 / 67N)  YesYes
 Minimum and maximum voltage (27/59)
(27 / 59)
 YesYes
 Bay controller up to 30 devices (6 switches)
30(6)
 Do notDo not
 Switch failure (50BF)
(50bf)
 YesYes
 Overexcitation (24)
(24)
 YesYes
 Synchronization check (25)
(25)
 YesYes
 Thermal Overload (49)
(49)
 YesYes
 Frequency (81)
(81)
 YesYes
 Fault Recording and Oscillographs (RF / RO)  YesYes
7.2.0Transformer Differential (87T) (87t)   
 - Operation characteristic
-
 Adaptable Yes
 - Precision In± 2.0%, for I <Ir± 1.0% of Irr for I < Ir
± 1.0% of I for I > Ir
 - Sensitive base function In10-60%(4.0-100.0)% of IBase
 - Unrestricted differential current limit In100-500090-6000
 - Second Harmonica Restrictionfundamental5.0 - 100% 
 - Fifth Harmonica Restriction fundamental5.0 - 100% 
 - Connection type of each winding  Y, star or D, DeltaY
 - Phase shifting between the High Dev W1 and each of the W2, and W3 windings
 
notation 0 - 11 
Time
 - Operating time, restricted function Ms25, t Ipeak of 0 to 2 x Id25 ms typically at 0 to 10 x IdMin
7.3.0Phase and ground phase instantaneous overcurrent (50 / 50N) (50/50N)   
 - Adjustment steps (minimum)  1 
 - Operating current range Ibase(1 to 2500)% Ibase 
 - Operation time Ms25 ms (0 to 2 Iset) 
10 ms (0 to 10 Iset) 
 - Replacement time
 
Ms25 ms (0 to 2 Iset) 
35 ms (0 to 10 Iset) 
7.4.0Phase overcurrent phase (51/67) and ground phase (51N / 67N) (51 / 67)(51n / 67n)   
 - Adjustment steps
 
 4 
 - Operating current range % In(1 to 2500)% Ibase(5-2500)% of lBase
 - Minimum operating current  (1-100)% IbaseMeet
 - Characteristic angle of relay 51/67 Degrees-70 to -50Meet
 - Maximum forward angle Degrees40-70Meet
 - Minimum forward angle Degrees75 to 90Meet
 - Characteristic angle of the relay 51N / 67N Degrees-180 to 180Meet
 - Blocking per second harmonic%(5-100%) of the fundamentalMeet
 - Timing Sec0 to 600 to 60
 ANSI timing curves
ANSI
 ANSI (Extremely Inverse, Very Inverse, Normal Inverse, Moderately Inverse, Extremely Inverse of Long Time, Very Inverse of Long Time, Inverse of Long Time)
ANSI(,,,,,,)
Meet
 IEC Timing Curves
IEC
 IEC (Normal Inverse, Very Inverse, Inverse, Extremely Inverse, Extr. Inverse Long time Inverse Short Time, Inverse Long Time)
IEC(,,,,.,)
Meet
 - Operating time, start function
-,
Ms25 (from 0 to 2 Iset)20 ms typically at 0 to 2 x Iset
 - Reset time, start function
-,
Ms25 (2 to 0 Iset)35 ms typically at 2 to 0 x Iset
7.5.0Minimum voltage (27)    
 - Number of adjustment steps
 
 2Meet
 - Low and high setting range for operating voltage UBASE1 -100(1-100)% of UBase
 - Setting range for absolute hysteresis UBASE0 -1000 -100
 - Low and high setting range for internal lock level UBASE1 -1001 -100
 - Timing

 
SDefinite Time (0-60) sec (0.00 - 6000.00) s
Programmable Curves Yes
 - Operating time for start-up function
 
Ms25, t Ipeak 2 to 0 x Uset30 ms typically at 2 to 0.5 x Uset
 - Reset time for start-up function
 
Ms25, t Ipeak from 0 to 2 x Uset40 ms typically at 0.5 to 2 x Uset
7.6.0Maximum voltage (59) and Maximum residual voltage  YesYes
 - Number of adjustment steps
-
 22
 - Low and high setting range for operating voltage
-
% U base1 - 200(1-200)% of UBase
 - Setting range for absolute hysteresis
 
UBASE0 - 1000 - 100
 - Timing
 
 Definite Time (0-60) sec (0.00 - 6000.00) s
Programmable Curves Yes
 - Operating time for start-up function
 
Ms25, t Ipeak from 0 to 2 x Uset30 ms typically at 0 to 2 x Uset
 - Reset time for start-up function
 
Ms25, t Ipeak 2 to 0 x Uset40 ms typically at 2 to 0 x Uset
7.7.0Switch failure (50BF)    
 - Phase current adjustment range %(5-200)% Ibase(5-200)% of lBase
 - Residual current adjustment range %(2-200)% Ibase(2-200)% of lBase
 - Timers Sec0 to 60(0.000-60.000) s
 - Operating time for current detection (typical)
()
Ms1035 ms typically
 - Reset time for current detection (maximum)
()
Msfifteen10 ms maximum
7.8.0Overexcitation (24) (24)   
 - Operating setting range for start up UBase / fn(100-180)%(100-180)% of (Ubase/frated)
 - Setting range of operation for alarm Ubase(0-100)%(50-120)% of start level
 - Operating setting range for high level
-
UBase / fn(100-200)%(100-200)% of (Ubase/frated)
 - Alarm timing S(0.000 - 60.000)(0.000-60.000) s
7.9.0Synchronization check (25) (25) YesYes
 - Bar angle offset and line degrees-180 to 180-180 to 180
 - Ubarra / Uline tension ratio %(0.40 - 5.00)% of UBASE(0.40 - 5.00)% of UBASE
 - Setting range of the line-to-line frequency difference limit Hz0.003 - 10.003 - 1
 - Range adjustment of the line angle difference limit bar-line degrees(5.0 to 90.0)(5.0 to 90.0)
 - Bar-line voltage difference limit adjustment range %(2.0 - 50.0)% of UBASE(2.0 - 50.0)% of UBASE
 - Output timing for synchronization S(0.000 - 60.000)(0.000 - 60.000)
 - High voltage limit setting range %(50-120)% of UBASE(50-120)% of UBASE
7.10.0Thermal Overload (49) (49)   
 - Base Current Setting Range I base(30-250)%(30-250)% of IBase
 - Alarm setting % I shot(50-99)%(50-99)% of heat content trip value
 - Operating current adjustment range I base(50-250)%(50-250)% of IBase
7.11.0Frequency (81) (81)   
 - Number of steps
 
 6Meet
 - Frequency Functions
 
 M INIMA Frequency  
About Frecuencia  
Derived from Frequency  
 - Adjustment range
-
Hz(35.00 - 75.00)(35.00-75.00) Hz
 CONSTRUCTIVE ASPECTS Hz / s(-10,000 - 10.00) steps 0.01Meet
 Frequency Ms100Meet
 Weight S(0.000 - 60.000)300kg
 Approximate Dimensions (Height, Width, Depth)
(,,)
SYes 
 Mounting  Yes 
7.12.0Operating temperature  Yes 
 Storage temperature S0.05 - 1-40...+85ºC
 Relative Humidity Range S0.1 - 10<93%
 TENSION AND CURRENT ANALOGUE INPUTS
 
S0.5 - 101A/5A
 Number of analog inputs No.9610~20
 Voltage inputs No.40 
 - Number of entries
-
Sample / cycle twenty 
 - Rated voltage (Vn)
(V)
Hz5 - 300 
 - Operating margin No.100 
8.0.0- Maximum permanent voltage    
8.1.0- Maximum tension for 10 seconds    
 Burden  Yes 
 Current Inputs  Yes 
8.2.0- Number of entries
-
   
 - Rated current (In)
(IN)
 Yes 
 - Operating margin  Yes 
8.3.0- Maximum permanent current    
 - Maximum current for 1 sec.  1000 
 Burden  Yes 
 DEPARTURES AND BINARY ENTRIES No.96 
 Programmable Trip and Signaling Outputs No.40 
 - Number of contacts (minimum)
-()
Ms1 
8.4.0- Maximum operating voltage
-
 YES 
8.4.1- Test voltage at the open contact, for 1 min.
-,1.
   
 - Permanent current carrying capacity
-
 Yes 
 
No.DESCRIPTION TIONUNID.VALUE REQUIREDVALUE OFFERED
1GENERAL DATA    
1.1Country of manufacture   Sweden/China
1.2Maker   ABB/SAC
1.3Model   REC650
1.4.Kind  multifunction ng NGmultifunction
1.5Internal processing unit  Microprocessors Microprocessors
1.6Installation height (m) () 1000 
1.7Rule  IEC 60255Meet
   IEC 61000Meet
   IEC 60297Meet
   ENV 50204Meet
1.8Working temperature range ° C-10 to +50-25...+55oC (continuous)
1.9RH%90<93%, non-condensing
1.1Mounting HorizontalHorizontal
1.1Phases 03 phases + earth3 
1.1Dimensions and weight    
 * WidthMm 220 mm
 * DepthMm 265.9 mm (6U)
 * HeightMm 249.5 mm
 * WeightKg <10 kg (6U)
1.1ConsumptionGOES 35W
1.1Digital programming ---YesYes
1.2Modular architecture ---YesYes
1.2Oscillographs ---YesYes
1.2Sensitivity MA1Meet
1.2Degree of protection IP52Front side:IP40
Rear side, connection terminals:IP20
Front and side:IP42
1.2Test voltage at 60Hz (1min)KV2Meet
1.2Immunity to electrical and electromagnetic interference ---YesYes
1.2Special Tests    
 EMC Immunity IEC 255-22; 22-1; 22-2; 22-3; 22-4)---YesYes
 EMC Emission EN50081-2; EN55011 class A---YesYes
 Insulation (IEC 255-5) (IEC 255-5)---YesYes
 Mechanical Efforts IEC255-21 IEC68-2---YesYes
     
2NOMINAL DATA    
 Frequency Hz6050/60Hz
 Rated current TO1 and 51A/5A
 Change of CT signal polarity via software
CT
---YesYes
 Nominal voltage (between phases) autorang
()autorang
Vca100 to 120 ± 15%100,110,120,220,240 V AC
 Maximum permanent voltage Vca2Vn420 V rms
 Maximum voltage for 1 minute
1
Vca3.5Vn420 V(10s) rms
 Overload capacity for current circuit (ms)  4 x In continuous  
   100 x In for 1sec 
 Auxiliary voltage, autorang
,autorang
Vcc110-250 ± 20% 88...300 V DC
3PROTECTION FUNCTIONS    
3.1AVAILABILITY OF PROTECTION    
 * Neutral Isolated
*
 YesYes
 *Neutral Grounded Rigorously  YesYes
 * Neutral Artificial using a ZIG-ZAG transformer
ZIG-ZAG
 YesYes
3.2PROTECTION CLOSURE ON FAILURE    
 Dead Line Detection Voltage Range V(1 to 100)% Vn(1 to 100)% Vn
 Dead Line Detection Current Range TO(1 to 100)% In(1 to 100)% In
 Enablement time Msg<200<200
3.3TIMER OVERLOADING (51 / 51N)   
 Number of stages for function 51No.ínimo 24
 Number of stages for function 51N No.ínimo 24
 Setting current range % In10 to 2500Meet
 Inverse Characteristic Curves, defined
,
---IEC, ANSI and User DefinedIEC, ANSI
3.4INSTANTANEOUS OVERLOADING
(50 / 50N)
   
 Number of stages for function 50No.ínimo 24
 Number of stages for the 50N functionNo.ínimo 24
 Setting current range% In10 to 4000Meet
 Delay time rangeSeconds0.02 to 15Meet
3.5DIRECTIONAL OVERCURRENT (67 / 67N)
(67 / 67n)
   
 Number of stages for function 67No.ínimo 24
 Number of stages for function 67NNo.ínimo 24
 Polarization by zero / negative sequence---Specify 
 Polarization angleºSpecify 
 Setting current range% In10 to 3000Meet
 Inverse Characteristic Curves, defined---IEC, ANSI and User DefinedIEC, ANSI
3.6TENSION PROTECTION (59/27)    
 Number of stepsNo.ínimo 359:2 steps;
27:2steps
 Maximum voltage rangeVn80 to 150Meet
 Minimum voltage rangeVn10 to 100Meet
 Delay time rangeSeconds0 to 600 to 60
3.7PROTECTION FAULT SWITCH    
 Operating CurrentTO(5-500)% In(5-500)% In
 Delay Time TriggerSeconds0 to 600 to 60
 Current detection for operating timemsec. <10Meet
3.8OTHER PROTECTIONS AND FUNCTIONS    
 Negative Sequence (46)
(46)
---YesYes
 Trip Circuit Supervision ---ínimo 22
 Monitoring of the current circuit ---YesYes
 Voltage circuit supervision ---YesYes
 Switch Condition Monitoring ---YesYes
 Number of adjustment groups ---44
     
4CONTROL    
4.1AUTOMATIC RECEPTION    
 Number of steps No.ínimo 55
 Criteria for initiation ---Configurable Configurable
 Blocking / Inhibition Criteria
/
---ConfigurableConfigurable
 Dead time setting Seconds0.20 to 1000.20 to 100
 (Steps of 0.01 s)0.01s
 Synchronism check capability at recloser ---YESYes
 Discrimination time Seconds0 to 10.000 to 10.00
 (Steps of 0.01)(Steps of 0.01)
4.2SINCROCHECK   
 Angle Range°(-180 to 180)(-180 to 180)
 Bar-line voltage limit rangeV(0.5-5.0)% Vn(0.5-5.0)% Vn
 Frequency difference limit rangeHz(0.003-1.000)(0.003-1.000)
 Angle difference limit range°(5-90)(5-90)
 Voltage difference limit rangeV(2-50)% Vn(2-50)% Vn
 Function evaluation timeSeconds(0.0 - 60.0)0~60s
 Function operation timeMsg200Meet
4.3EQUIPMENT CONTROL FUNCTIONS    
 Control and control via the LCD display with position indication LCDNo.ínimo: 2 switches, 3 disconnectors8
 Status indication of non-controllable equipment No.Specify According to the requirement.
 Local / remote front button
/
---YesYes
 Alternative selection of Local / Remote via binary input
/
---YESYes
 Automation and Control Buttons No.ínimo 5According to the requirement.
5PLC CONFIGURATION AND PROGRAMMING ---YesYes
 Programming via matrix logic ---YESYes
 Programming through block diagram (graph)
()
---YESYes
6AUXILIARY CONTACTS    
6.1OUTPUT    
 Shooting Contacts   
 Number of contacts (minimum)No.Referring to Fig.According to the requirement.
 Operating VoltageYou125 ± 20%Meet
 Permanent IntensityTOReferring to Fig.Meet
 Intensity 3 secTOfifteenMeet
 Intensity at 0.5 secTO30Meet
 Programmable output contacts---YESYes
 Number of contacts (minimum)No.Referring to Fig.According to the requirement.
 Operating VoltageYou125 ± 20%Meet
 Permanent IntensityTO5Meet
 Intensity 3 secTO10Meet
 Intensity at 0.5 secTOfifteenMeet
6.2INPUT    
 Programmable Input Contacts---YESYes
 Number of input contacts (minimum)No.2. 3According to the requirement.
 Voltage rangeYou24-25024-250
7MONITORING AND REGISTRATION    
7.1MEASUREMENTS    
 Instantaneous values ---YesYes
 Voltages, currents, frequency, power and power factor
,,,
---YESYes
 Primary and secondary voltages and currents (phase and angle)
()
---YESYes
 Positive, negative and zero sequence currents and voltages
,
---YESYes
 Active and reactive power ---YESYes
 Real-time monitoring of measurement parameters ---YesYes
 Voltage signal input for calculation of measurement parameters ---YesYes
 Status of controlled equipment (open, closed, undefined)
(,,)
---YESYes
7.2OSCILOGRAPHY RECORDER   
 Number of binary signals No.64Meet
 Number of physical analog signals No.30Meet
 Number of analogue signals calculated No.10Meet
 Sample Rate Sample / cl4,8,16,32 or 64Meet
 Bandwidth Cycles600600
 Pre-fault time Ms10 to 300010 to 3000
 Post-failure time Ms100 to 10000100 to 10000
 Number of registered oscillographs No.ínimo 100Meet
 Total recorder capacity Cycles1 Mbyte1 Mbyte
 Drive by internal and external signals ---YesYes
 Real-time monitoring of relay inputs and outputs ---YesYes
 File format  COMTRADEYes
 In case of power interruption, the events will be Stored in the volatile memory, YesYes
7.3EVENT RECORDER    
 Registered event numbers (available for extraction)
()
No.10001000
 Stores sequentially, with date, time, second and millisecond indication ,,,---YESYes
7.4FAULT RECORDER    
 Number of records No.100100
 Pre-fault and current and voltage failure value---YESYes
7.5TROUBLESHOOTING ---YESYes
8LOCAL AND REMOTE COMMUNICATION    
8.1Open communication protocol    
 * IEC 61850---YesYes
 Native (no mappings or converters)
()
---YesYes
 KEMA Certification
KEMA
---YesYes
 Messaging Goose   Yes
 Digital Signs ---YesYes
 Analog Signals ---YesYes
 Class  P1 
 Kind  A1 
 Signal Transfer Speed Ms<2.5Meet
 * DNP 3.0 TCP / IP---YesNo
 * Modbus---Optional Optional
8.2Ports of communication    
 * RJ-45 Ethernet---YES, FrontYes
 * RJ-45 Ethernet---Yes, LaterYes
 * Ethernet Fiber Optic
*
---Yes, LaterYes
 * Stand-alone port for synchronization ---Yes, (IRIG B)IRIG-B
9OPERATION INTERFACE    
9.1LOCAL INTERFACE    
 Front display and keypad ---YesYes
 Interface with control systems ---YesYes
 Remote communication ---YesYes
 Input and outputs for telemetering ---YesYes
 Self-diagnosis or self-supervision ---YesYes
 Phase indication triggered ---YesYes
 Signal sending signal ---YesYes
 Signal reception ---YesYes
9.2WEB-BASED INTERFACE Web   
 Embedded web server ---YesYes
 Changing Web Protection Settings ---YesYes
 Download Oscillographs via web ---YesYes
 Events Download Via web ---YesYes
 Resetting of Indications and Alarms via web ---YesYes
 Security system ---YesYes
10LED SIGNALING    
 * Visual indicator ---YesYes
 * Minimum number of configurable LEDs No.Four. Five15
 * Shooting start ---YesYes
 * Shooting ---YesYes
 * Relay Status ---YesYes
 * Activated by external contact or internal function ---YesYes
 * Activation by protection function ---YesYes
9SOFTWARE    
 *Configuration software (with license) ---YesYes
 * Environment  WindowsWindows 7
 * Security level (Password) ---YesYes
 * Download information ---YesYes
 * Oscillograph analysis software ---YesYes
 * Local programming ---YesYes
 * Remote programming ---YesYes
 * Relay communication cables - computer ---YesYes
 * Operation and configuration manual:
:
---YesOnly English
Spanish, English (original printed and in magnetic file pdf)
,(PDF)
 * Factory Certified Trainers ---YesYes
 * One Relay Simulator Module per person ---YesMeet
 * Assistants No.10According to the requirement.
 * Level Operator Duration days11
 * Duration Level Programmer days22
 * Factory Certification for attendees ---YesYes
 * Printed and digital documentation ---YesYes
 
TECHNICAL DATA TABLE DIGITAL TYPE ALARM ANNOUNCER
°DESCRIPTION TIONUNID.VALUE REQUIREDVALUE OFFERED
1Digital Alarm Announcer   
2For application in monitoring of alarms and signaling of Power Substations   
3QuantityUnd11
4SignalingDigital TypeYesYes
5Identification of failures and alarms in form Visual and audible Visual
6FeedingYouRange 18 to 80 VdcMeet
7Control voltage for identification circuits and alarm reset, obtaining from the power supply,You Meet
Referring to Fig. Internal You48 Vdc +/- 20%.Meet
Referring to Fig.Internal contact voltage 48 Vdc +/- 20%.Meet
10Internal contact current: MAmA +/- 20%.Meet
elevenAlarm Channel Capacity :Und16 units.Min. 16
12Activating channels using contacts
 
 NO (normally open) or NC (normally closed)NO
13Reset Delay Times
:
 ms, 20 ms, 100 ms, 1 s, 5 s, 20 s, 60 s or 160 s.Meet
14Manufacturing standard: IEC 660255-5, IEC 60255-6, IEC 60068-2-3 IEC 660255-5, IEC 60255-6, IEC 60068-2-3Meet
fifteenFor front panel mounting  YesYes
16Selection and configuration of parameters from front panel or via serial interface.
.
 YesYes
17Self-monitoring system that allows system availability and reliability
.
 YesYes
18Code ASCII transmission mode, 4800 or 9600 Bd transfe
ASCII,48009600BDr.
 YesYes
19Operating Temperature:° Cto 55 ° CMeet
twentyDegree of protection: IP 54. IP 54Meet
twenty-oneIncludes Equipment Manual and accessories for front panel mounting. . YesYes
 
TABLE OF TECHNICAL DATA MULTIFUNCTION METER
°DESCRIPTION TIONUNID.VALUE REQUIREDVALUE OFFERED
     
1MULTIFUNCTION METER    
1Maker  Alster
1Team model  AC1700
1Operating Temperature: : -20 ° C - + 70-40ºC~+70ºC
1Number of Threads:4 4 threads3-phase 3-wire,3-phase 4-wire
1.1Rated currentTO1 to 55-6A, 5-10A, 1-2A, 1-1.2A
1.1Voltage: AutorangoV (ln)57V to 347V57.5 - 240V (3 ph 4 wire)
100 - 415V (3 ph 3 wire)
1.1Power Supply  85-240 Vac ± 10%70~265V AC/DC
1.1FrequencyHz6050Hz or 60Hz
1.1Class of Metrology  IEC600687 0.2s or 02.S IEC62053-22IEC 62053 - 22
1.1Four Squares yes 
1.1Information preservation without auxiliary power
 
 Minimum 30 d ies30Meet
1.1Circular mass memory Minimum 60 d iesMeet
1.1Load Profile Option  yesMeet
1.1Number of Recording Channels, Minimum , Referring to Fig.According to the requirement.
1.2Number of Recording Channels, optimal , or 88 channels
1.2Digital Inputs  yesYes
1.2Outputs for relays and control functions yesYes
1.2Analog I / O Option  yesYes
1.2Programming of any parameter or condition for control and alarm functions  yesYes
1.2Instant Instrumentation Values  V, I, kW, kVAr, kVA, kWh, kVarh, frequency, FPV, I, kW, kVAr, kVA, kWh, kVarh, frequency, FP
1.2Bidirectionality  yesYes
1.2Frozen readings option  yesYes
1.2Phasor diagram generation  yesYes
1.2External communication RS485, switchable with RS232 RS485RS232, yesYes
1.3Communication protocol  DNP 3.0 / Modbus Serial DNP3.O, Modbus and IEC 61850 thernetFlag IEC 62056-21 (formerly 61107)
1.3Internal Modem Option  yesYes
1.3Event Logging and Handling  yesYes
1.3Power and Demand Channels  yesYes
1.3Redundant Font  yesYes
1.3RTC (Real Time Clock)
RTC()
 Upgradable GPSRTC
1.3POWER AND ENERGY DEMAND    
 Voltage and current unbalance  yesPls.refer to AC1700 manual.
 Frequency, power factor, apparent power, reactive and real power ,,,, yesYes
 Export and import of bidirectional energy  yesYes
1.3PQ ANALYSIS    
 SAG / SWELL wave monitoring / yesPls.refer to AC1700 manual.
 Symmetrical components: Zero, Positive and Negative :,, yesPls.refer to AC1700 manual.
 Individual harmonics and total harmonic distortion greater than the 63rd 63 yesPls.refer to AC1700 manual.
 Detection of transients greater than 17 us
17
 yesPls.refer to AC1700 manual.
 Sequence of Events  yesPls.refer to AC1700 manual.
 Samples per cycle, above 1.0241024 yes 
 Registry of Flicker and Harmonics of voltage according to NTCSE Peruana ntcse yesPls.refer to AC1700 manual.
1.3DATA AND RECORDS OF WAVES    
 Waveform recording of up to 214,000 continuous cycles with 16 samples per cycle.
214000,16.
 yesPls.refer to AC1700 manual.
 Point-driven: external signal and programs
:
 yesPls.refer to AC1700 manual.
 Maximum / minimum records for any parameter
/
 yesPls.refer to AC1700 manual.
 Historic records, maximum number of characters
,
 32Pls.refer to AC1700 manual.
 Resolution in seconds Samples per cycle, up to 1,024
,1024
 yesPls.refer to AC1700 manual.
 Time Synchronization with GPS
GPS
 yesPls.refer to AC1700 manual.
1.3COMMON PORTS AND EXPANDABLE ENTRY / DEPARTURE /   
 Ports RS-232/485 switchable RS-232/485 1Meet
 RJ 45 port
RJ 45
 1Meet
 Slave Ports Modbus RTU Serial, Ethernet, Modem, I / R
Modbus RTU,,,I/R
 yesYes
 Ports DNP 3.0, Modem and I / R
DNP 3.0,I/R
   
 Data transfer gateway modem / direct Ethernet network for RS-485
RS-485
 yesYes
 Analog outputs with expandable input / output
/
 4 inputs / 4 outputsPls.refer to AC1700 manual.
 Digital status, input counter
,
 Referring to Fig.Pls.refer to AC1700 manual.
 Digital relay outputs (control / pulse)
(/)
 7 m ínimoPls.refer to AC1700 manual.
 Sync port  If (IRIG B or NTP SERVER)Yes
1.4.SEVEN POINTS FOR CONTROL AND ALARM    
 Setting, mínimum response time  sec or 1/2 cyclesec
 Linearization of mathematical, logical and logarithmic formulas
,
 yesYes
 Simple and multi - alarm alarms  yesYes
 Remote Alarm Notification  yesYes
1.4.INCOME OF MEASUREMENTS    
 Standards for accuracy: ANSI C12,60 yesYes
 ANSI standard C12,20 0.2 yesYes
 Standard IEC 60687 0,2 S yesIEC 60687
 IEC 60687 standard, accuracy class 0,2 S yesYes
 Line Loss and Transformer Compensation  yesYes
 Multiple annual scheduling, Hourly activity profiles , yesYes
 software  yesYes