No. | DESCRIPTION TION | UNID. | VALUE REQUIRED | VALUE OFFERED |
1.0.0 | GENERAL DATA | |||
1.1.0 | Maker | ABB/SAC | ||
1.2.0 | Model | RET650 | ||
1.3.0 | Country of manufacture | Sweden/China | ||
2.0.0 | CONSTRUCTIVE ASPECTS | |||
2.1.0 | Frequency | Hz | 60 | 50/60Hz |
2.2.0 | Weight | Kg | Indicate | 300 |
2.3.0 | Approximate Dimensions (Height, Width, Depth) (,,) | Mm | Indicate | 2260*800*600mm(H*W*D) |
2.4.0 | Mounting | Yes | Yes | |
2.5.0 | Operating temperature | ° C | -10 to +55 | -25 to +55ºC |
2.6.0 | Storage temperature | ° C | -40 to +70 | -40 to +85ºC |
2.7.0 | Relative Humidity Range | % | 10 to 90 | <93% |
3.0.0 | TENSION AND CURRENT ANALOGUE INPUTS | |||
Number of analog inputs | 24 | 12 | ||
3.1.0 | Voltage inputs | |||
- Number of entries | Referring to Fig. | |||
- Rated voltage (Vn) | Vac | 110 | 110V | |
- Operating margin | Vac | 0 - 340 | ||
- Maximum permanent voltage | Vac | 420 | 420V rms | |
- Maximum tension for 10 seconds | Vac | 450 | 450V rms | |
Burden | GOES | <.02 To 110 Vac | <0.05 VA | |
3.2.0 | Current Inputs | |||
- Number of entries | fifteen | 6 | ||
- Rated current (In) (IN) | Amp. | 1 | 1/5A | |
- Operating margin | Amp. | (0-100) x In | ||
- Maximum permanent current | Amp. | 4 In | 20A | |
- Maximum current for 1 sec. | Amp. | 100 In | 500A | |
Burden | GOES | <0.02 to 1A | <0.05 VA | |
4.0.0 | DEPARTURES AND BINARY ENTRIES | Yes | Yes | |
4.1.0 | Programmable Trip and Signaling Outputs | |||
- Number of contacts (minimum) -() | No. | 24 | 24 | |
- Maximum operating voltage - | Vac / Vdc | 250 Vac, Vdc | 250 Vac, Vdc | |
- Test voltage at the open contact, for 1 min. -,1. | Vrms | 1000 | Meet | |
- Permanent current carrying capacity - | TO | Referring to Fig. | 5A | |
- Current carrying capacity for 1 sec - 1s | TO | 10 | 10A (3s) 10A (0.5s) | |
- Cutting capacity | TO | 110 V / 0.4 A | 48V / ≤0.5 A 110V / ≤0.1 A 220V / ≤0.04 A | |
125V / 0.35A | ||||
- Closing capacity | TO | 30 A (for 0.2 s) 10 A (per 1.0 s) | Meet | |
4.2.0 | Inputs | |||
- Programmable input contacts | Yes | Yes | ||
- Number of input contacts (minimum) () | No. | 32 | Max.50 | |
- Voltage range | V | 24 - 250 | 24...250 V DC | |
- Power consumption per input | W | 0.2 W to 125 V | <0.3 W | |
4.3.0 | LED's of signaling | Yes | Yes | |
- relay status | 3 | Meet | ||
- the performance of the protection functions - | 15 (6 red and 9 yellow) 15(69) | 15 | ||
4.5.0 | Interfaces | |||
- Large HMI on the relay front panel HMI | Yes | Yes | ||
- Front Ethernet port, PC connection -,PC | 1 port, RJ45 | 1 port, RJ45 | ||
- Ethernet optical port for remote communication | 1 port, ST | Meet | ||
4.6.0 | Remote Communication | |||
- Communication protocol | IEC 61850 | IEC 61850 | ||
- Communication speed | MBps | 100 | 100 MBits/s | |
5.0.0 | AUXILIARY SUPPLY | |||
5.1.0 | Auxiliary Rated Voltage | Vcc | 90 to 250 | 88...300 V DC |
5.2.0 | Tolerance | % | ± 20% | 15% |
5.3.0 | Typical Consumption | |||
- In normal operating condition - | W | fifty | 30W | |
5.4.0 | Auxiliary insertion power | TO | <5 A, for 0.1 sec | <5 A, for 0.1 sec |
6.0.0 | SPECIAL TESTS | |||
6.1.0 | EMC Immunity (IEC 60255-22; 22-1; 22-2; 22-3; 22-4) (IEC 60255-22;22-1;22-2;22-3;22-4) | Yes | Yes | |
6.2.0 | EMC Emission (IEC 60255-22, IEC 61000-4, IEEE / ANSI C37.90) (IEC 60255-22,IEC 61000-4,IEEE / ANSI c37.90) | Yes | Yes | |
6.3.0 | Insulation (IEC 255-5) (IEC 255-5) | Yes | Yes | |
6.4.0 | Mechanical Efforts IEC255-21, IEC68-2 iec255-21,iec68-2 | Yes | Yes | |
6.5.0 | Environmental Testing IEC60068, IEC68-2 iec60068,iec68-2 | Yes | Yes | |
7.0.0 | PROTECTION FUNCTIONS | |||
7.1.0 | List of included functions | |||
Transformer Differential (87T) | Yes | Yes | ||
Distance between phases and ground phase (21 / 21N) (21/21 n) | Do not | No | ||
Phase overcurrent and ground phase (50/51, 50 / 51N) | Yes | Yes | ||
Directional phase and ground phase overcurrent (67 / 67N) | Yes | Yes | ||
Minimum and maximum voltage (27/59) (27 / 59) | Yes | Yes | ||
Bay controller up to 30 devices (6 switches) 30(6) | Do not | Do not | ||
Switch failure (50BF) (50bf) | Yes | Yes | ||
Overexcitation (24) (24) | Yes | Yes | ||
Synchronization check (25) (25) | Yes | Yes | ||
Thermal Overload (49) (49) | Yes | Yes | ||
Frequency (81) (81) | Yes | Yes | ||
Fault Recording and Oscillographs (RF / RO) | Yes | Yes | ||
7.2.0 | Transformer Differential (87T) (87t) | |||
- Operation characteristic - | Adaptable | Yes | ||
- Precision | In | ± 2.0%, for I <Ir | ± 1.0% of Irr for I < Ir ± 1.0% of I for I > Ir | |
- Sensitive base function | In | 10-60% | (4.0-100.0)% of IBase | |
- Unrestricted differential current limit | In | 100-5000 | 90-6000 | |
- Second Harmonica Restriction | fundamental | 5.0 - 100% | ||
- Fifth Harmonica Restriction | fundamental | 5.0 - 100% | ||
- Connection type of each winding | Y, star or D, Delta | Y | ||
- Phase shifting between the High Dev W1 and each of the W2, and W3 windings | notation | 0 - 11 | ||
Time | ||||
- Operating time, restricted function | Ms | 25, t Ipeak of 0 to 2 x Id | 25 ms typically at 0 to 10 x IdMin | |
7.3.0 | Phase and ground phase instantaneous overcurrent (50 / 50N) (50/50N) | |||
- Adjustment steps (minimum) | 1 | |||
- Operating current range | % Ibase | (1 to 2500)% Ibase | ||
- Operation time | Ms | 25 ms (0 to 2 Iset) | ||
10 ms (0 to 10 Iset) | ||||
- Replacement time | Ms | 25 ms (0 to 2 Iset) | ||
35 ms (0 to 10 Iset) | ||||
7.4.0 | Phase overcurrent phase (51/67) and ground phase (51N / 67N) (51 / 67)(51n / 67n) | |||
- Adjustment steps | 4 | |||
- Operating current range | % In | (1 to 2500)% Ibase | (5-2500)% of lBase | |
- Minimum operating current | (1-100)% Ibase | Meet | ||
- Characteristic angle of relay 51/67 | Degrees | -70 to -50 | Meet | |
- Maximum forward angle | Degrees | 40-70 | Meet | |
- Minimum forward angle | Degrees | 75 to 90 | Meet | |
- Characteristic angle of the relay 51N / 67N | Degrees | -180 to 180 | Meet | |
- Blocking per second harmonic | % | (5-100%) of the fundamental | Meet | |
- Timing | Sec | 0 to 60 | 0 to 60 | |
ANSI timing curves ANSI | ANSI (Extremely Inverse, Very Inverse, Normal Inverse, Moderately Inverse, Extremely Inverse of Long Time, Very Inverse of Long Time, Inverse of Long Time) ANSI(,,,,,,) | Meet | ||
IEC Timing Curves IEC | IEC (Normal Inverse, Very Inverse, Inverse, Extremely Inverse, Extr. Inverse Long time Inverse Short Time, Inverse Long Time) IEC(,,,,.,) | Meet | ||
- Operating time, start function -, | Ms | 25 (from 0 to 2 Iset) | 20 ms typically at 0 to 2 x Iset | |
- Reset time, start function -, | Ms | 25 (2 to 0 Iset) | 35 ms typically at 2 to 0 x Iset | |
7.5.0 | Minimum voltage (27) | |||
- Number of adjustment steps | 2 | Meet | ||
- Low and high setting range for operating voltage | % UBASE | 1 -100 | (1-100)% of UBase | |
- Setting range for absolute hysteresis | % UBASE | 0 -100 | 0 -100 | |
- Low and high setting range for internal lock level | % UBASE | 1 -100 | 1 -100 | |
- Timing | S | Definite Time (0-60) sec | (0.00 - 6000.00) s | |
Programmable Curves | Yes | |||
- Operating time for start-up function | Ms | 25, t Ipeak 2 to 0 x Uset | 30 ms typically at 2 to 0.5 x Uset | |
- Reset time for start-up function | Ms | 25, t Ipeak from 0 to 2 x Uset | 40 ms typically at 0.5 to 2 x Uset | |
7.6.0 | Maximum voltage (59) and Maximum residual voltage | Yes | Yes | |
- Number of adjustment steps - | 2 | 2 | ||
- Low and high setting range for operating voltage - | % U base | 1 - 200 | (1-200)% of UBase | |
- Setting range for absolute hysteresis | % UBASE | 0 - 100 | 0 - 100 | |
- Timing | Definite Time (0-60) sec | (0.00 - 6000.00) s | ||
Programmable Curves | Yes | |||
- Operating time for start-up function | Ms | 25, t Ipeak from 0 to 2 x Uset | 30 ms typically at 0 to 2 x Uset | |
- Reset time for start-up function | Ms | 25, t Ipeak 2 to 0 x Uset | 40 ms typically at 2 to 0 x Uset | |
7.7.0 | Switch failure (50BF) | |||
- Phase current adjustment range | % | (5-200)% Ibase | (5-200)% of lBase | |
- Residual current adjustment range | % | (2-200)% Ibase | (2-200)% of lBase | |
- Timers | Sec | 0 to 60 | (0.000-60.000) s | |
- Operating time for current detection (typical) () | Ms | 10 | 35 ms typically | |
- Reset time for current detection (maximum) () | Ms | fifteen | 10 ms maximum | |
7.8.0 | Overexcitation (24) (24) | |||
- Operating setting range for start up | UBase / fn | (100-180)% | (100-180)% of (Ubase/frated) | |
- Setting range of operation for alarm | Ubase | (0-100)% | (50-120)% of start level | |
- Operating setting range for high level - | UBase / fn | (100-200)% | (100-200)% of (Ubase/frated) | |
- Alarm timing | S | (0.000 - 60.000) | (0.000-60.000) s | |
7.9.0 | Synchronization check (25) (25) | Yes | Yes | |
- Bar angle offset and line | degrees | -180 to 180 | -180 to 180 | |
- Ubarra / Uline tension ratio | % | (0.40 - 5.00)% of UBASE | (0.40 - 5.00)% of UBASE | |
- Setting range of the line-to-line frequency difference limit | Hz | 0.003 - 1 | 0.003 - 1 | |
- Range adjustment of the line angle difference limit bar-line | degrees | (5.0 to 90.0) | (5.0 to 90.0) | |
- Bar-line voltage difference limit adjustment range | % | (2.0 - 50.0)% of UBASE | (2.0 - 50.0)% of UBASE | |
- Output timing for synchronization | S | (0.000 - 60.000) | (0.000 - 60.000) | |
- High voltage limit setting range | % | (50-120)% of UBASE | (50-120)% of UBASE | |
7.10.0 | Thermal Overload (49) (49) | |||
- Base Current Setting Range | I base | (30-250)% | (30-250)% of IBase | |
- Alarm setting | % I shot | (50-99)% | (50-99)% of heat content trip value | |
- Operating current adjustment range | I base | (50-250)% | (50-250)% of IBase | |
7.11.0 | Frequency (81) (81) | |||
- Number of steps | 6 | Meet | ||
- Frequency Functions | M INIMA Frequency | |||
About Frecuencia | ||||
Derived from Frequency | ||||
- Adjustment range - | Hz | (35.00 - 75.00) | (35.00-75.00) Hz | |
CONSTRUCTIVE ASPECTS | Hz / s | (-10,000 - 10.00) steps 0.01 | Meet | |
Frequency | Ms | 100 | Meet | |
Weight | S | (0.000 - 60.000) | 300kg | |
Approximate Dimensions (Height, Width, Depth) (,,) | S | Yes | ||
Mounting | Yes | |||
7.12.0 | Operating temperature | Yes | ||
Storage temperature | S | 0.05 - 1 | -40...+85ºC | |
Relative Humidity Range | S | 0.1 - 10 | <93% | |
TENSION AND CURRENT ANALOGUE INPUTS | S | 0.5 - 10 | 1A/5A | |
Number of analog inputs | No. | 96 | 10~20 | |
Voltage inputs | No. | 40 | ||
- Number of entries - | Sample / cycle | twenty | ||
- Rated voltage (Vn) (V) | Hz | 5 - 300 | ||
- Operating margin | No. | 100 | ||
8.0.0 | - Maximum permanent voltage | |||
8.1.0 | - Maximum tension for 10 seconds | |||
Burden | Yes | |||
Current Inputs | Yes | |||
8.2.0 | - Number of entries - | |||
- Rated current (In) (IN) | Yes | |||
- Operating margin | Yes | |||
8.3.0 | - Maximum permanent current | |||
- Maximum current for 1 sec. | 1000 | |||
Burden | Yes | |||
DEPARTURES AND BINARY ENTRIES | No. | 96 | ||
Programmable Trip and Signaling Outputs | No. | 40 | ||
- Number of contacts (minimum) -() | Ms | 1 | ||
8.4.0 | - Maximum operating voltage - | YES | ||
8.4.1 | - Test voltage at the open contact, for 1 min. -,1. | |||
- Permanent current carrying capacity - | Yes |
No. | DESCRIPTION TION | UNID. | VALUE REQUIRED | VALUE OFFERED |
1 | GENERAL DATA | |||
1.1 | Country of manufacture | Sweden/China | ||
1.2 | Maker | ABB/SAC | ||
1.3 | Model | REC650 | ||
1.4. | Kind | multifunction ng NG | multifunction | |
1.5 | Internal processing unit | Microprocessors | Microprocessors | |
1.6 | Installation height (m) () | 1000 | ||
1.7 | Rule | IEC 60255 | Meet | |
IEC 61000 | Meet | |||
IEC 60297 | Meet | |||
ENV 50204 | Meet | |||
1.8 | Working temperature range | ° C | -10 to +50 | -25...+55oC (continuous) |
1.9 | RH | % | 90 | <93%, non-condensing |
1.1 | Mounting | Horizontal | Horizontal | |
1.1 | Phases | 03 phases + earth3 | ||
1.1 | Dimensions and weight | |||
* Width | Mm | 220 mm | ||
* Depth | Mm | 265.9 mm (6U) | ||
* Height | Mm | 249.5 mm | ||
* Weight | Kg | <10 kg (6U) | ||
1.1 | Consumption | GOES | 35W | |
1.1 | Digital programming | --- | Yes | Yes |
1.2 | Modular architecture | --- | Yes | Yes |
1.2 | Oscillographs | --- | Yes | Yes |
1.2 | Sensitivity | MA | 1 | Meet |
1.2 | Degree of protection | IP52 | Front side:IP40 Rear side, connection terminals:IP20 Front and side:IP42 | |
1.2 | Test voltage at 60Hz (1min) | KV | 2 | Meet |
1.2 | Immunity to electrical and electromagnetic interference | --- | Yes | Yes |
1.2 | Special Tests | |||
EMC Immunity IEC 255-22; 22-1; 22-2; 22-3; 22-4) | --- | Yes | Yes | |
EMC Emission EN50081-2; EN55011 class A | --- | Yes | Yes | |
Insulation (IEC 255-5) (IEC 255-5) | --- | Yes | Yes | |
Mechanical Efforts IEC255-21 IEC68-2 | --- | Yes | Yes | |
2 | NOMINAL DATA | |||
Frequency | Hz | 60 | 50/60Hz | |
Rated current | TO | 1 and 5 | 1A/5A | |
Change of CT signal polarity via software CT | --- | Yes | Yes | |
Nominal voltage (between phases) autorang ()autorang | Vca | 100 to 120 ± 15% | 100,110,120,220,240 V AC | |
Maximum permanent voltage | Vca | 2Vn | 420 V rms | |
Maximum voltage for 1 minute 1 | Vca | 3.5Vn | 420 V(10s) rms | |
Overload capacity for current circuit (ms) | 4 x In continuous | |||
100 x In for 1sec | ||||
Auxiliary voltage, autorang ,autorang | Vcc | 110-250 ± 20% | 88...300 V DC | |
3 | PROTECTION FUNCTIONS | |||
3.1 | AVAILABILITY OF PROTECTION | |||
* Neutral Isolated * | Yes | Yes | ||
*Neutral Grounded Rigorously | Yes | Yes | ||
* Neutral Artificial using a ZIG-ZAG transformer ZIG-ZAG | Yes | Yes | ||
3.2 | PROTECTION CLOSURE ON FAILURE | |||
Dead Line Detection Voltage Range | V | (1 to 100)% Vn | (1 to 100)% Vn | |
Dead Line Detection Current Range | TO | (1 to 100)% In | (1 to 100)% In | |
Enablement time | Msg | <200 | <200 | |
3.3 | TIMER OVERLOADING (51 / 51N) | |||
Number of stages for function 51 | No. | M ínimo 2 | 4 | |
Number of stages for function 51N | No. | M ínimo 2 | 4 | |
Setting current range | % In | 10 to 2500 | Meet | |
Inverse Characteristic Curves, defined , | --- | IEC, ANSI and User Defined | IEC, ANSI | |
3.4 | INSTANTANEOUS OVERLOADING (50 / 50N) | |||
Number of stages for function 50 | No. | M ínimo 2 | 4 | |
Number of stages for the 50N function | No. | M ínimo 2 | 4 | |
Setting current range | % In | 10 to 4000 | Meet | |
Delay time range | Seconds | 0.02 to 15 | Meet | |
3.5 | DIRECTIONAL OVERCURRENT (67 / 67N) (67 / 67n) | |||
Number of stages for function 67 | No. | M ínimo 2 | 4 | |
Number of stages for function 67N | No. | M ínimo 2 | 4 | |
Polarization by zero / negative sequence | --- | Specify | ||
Polarization angle | º | Specify | ||
Setting current range | % In | 10 to 3000 | Meet | |
Inverse Characteristic Curves, defined | --- | IEC, ANSI and User Defined | IEC, ANSI | |
3.6 | TENSION PROTECTION (59/27) | |||
Number of steps | No. | M ínimo 3 | 59:2 steps; 27:2steps | |
Maximum voltage range | % Vn | 80 to 150 | Meet | |
Minimum voltage range | % Vn | 10 to 100 | Meet | |
Delay time range | Seconds | 0 to 60 | 0 to 60 | |
3.7 | PROTECTION FAULT SWITCH | |||
Operating Current | TO | (5-500)% In | (5-500)% In | |
Delay Time Trigger | Seconds | 0 to 60 | 0 to 60 | |
Current detection for operating time | msec. | <10 | Meet | |
3.8 | OTHER PROTECTIONS AND FUNCTIONS | |||
Negative Sequence (46) (46) | --- | Yes | Yes | |
Trip Circuit Supervision | --- | M ínimo 2 | 2 | |
Monitoring of the current circuit | --- | Yes | Yes | |
Voltage circuit supervision | --- | Yes | Yes | |
Switch Condition Monitoring | --- | Yes | Yes | |
Number of adjustment groups | --- | 4 | 4 | |
4 | CONTROL | |||
4.1 | AUTOMATIC RECEPTION | |||
Number of steps | No. | M ínimo 5 | 5 | |
Criteria for initiation | --- | Configurable | Configurable | |
Blocking / Inhibition Criteria / | --- | Configurable | Configurable | |
Dead time setting | Seconds | 0.20 to 100 | 0.20 to 100 | |
(Steps of 0.01 s) | 0.01s | |||
Synchronism check capability at recloser | --- | YES | Yes | |
Discrimination time | Seconds | 0 to 10.00 | 0 to 10.00 | |
(Steps of 0.01) | (Steps of 0.01) | |||
4.2 | SINCROCHECK | |||
Angle Range | ° | (-180 to 180) | (-180 to 180) | |
Bar-line voltage limit range | V | (0.5-5.0)% Vn | (0.5-5.0)% Vn | |
Frequency difference limit range | Hz | (0.003-1.000) | (0.003-1.000) | |
Angle difference limit range | ° | (5-90) | (5-90) | |
Voltage difference limit range | V | (2-50)% Vn | (2-50)% Vn | |
Function evaluation time | Seconds | (0.0 - 60.0) | 0~60s | |
Function operation time | Msg | 200 | Meet | |
4.3 | EQUIPMENT CONTROL FUNCTIONS | |||
Control and control via the LCD display with position indication LCD | No. | M ínimo: 2 switches, 3 disconnectors | 8 | |
Status indication of non-controllable equipment | No. | Specify | According to the requirement. | |
Local / remote front button / | --- | Yes | Yes | |
Alternative selection of Local / Remote via binary input / | --- | YES | Yes | |
Automation and Control Buttons | No. | M ínimo 5 | According to the requirement. | |
5 | PLC CONFIGURATION AND PROGRAMMING | --- | Yes | Yes |
Programming via matrix logic | --- | YES | Yes | |
Programming through block diagram (graph) () | --- | YES | Yes | |
6 | AUXILIARY CONTACTS | |||
6.1 | OUTPUT | |||
Shooting Contacts | ||||
Number of contacts (minimum) | No. | Referring to Fig. | According to the requirement. | |
Operating Voltage | You | 125 ± 20% | Meet | |
Permanent Intensity | TO | Referring to Fig. | Meet | |
Intensity 3 sec | TO | fifteen | Meet | |
Intensity at 0.5 sec | TO | 30 | Meet | |
Programmable output contacts | --- | YES | Yes | |
Number of contacts (minimum) | No. | Referring to Fig. | According to the requirement. | |
Operating Voltage | You | 125 ± 20% | Meet | |
Permanent Intensity | TO | 5 | Meet | |
Intensity 3 sec | TO | 10 | Meet | |
Intensity at 0.5 sec | TO | fifteen | Meet | |
6.2 | INPUT | |||
Programmable Input Contacts | --- | YES | Yes | |
Number of input contacts (minimum) | No. | 2. 3 | According to the requirement. | |
Voltage range | You | 24-250 | 24-250 | |
7 | MONITORING AND REGISTRATION | |||
7.1 | MEASUREMENTS | |||
Instantaneous values | --- | Yes | Yes | |
Voltages, currents, frequency, power and power factor ,,, | --- | YES | Yes | |
Primary and secondary voltages and currents (phase and angle) () | --- | YES | Yes | |
Positive, negative and zero sequence currents and voltages , | --- | YES | Yes | |
Active and reactive power | --- | YES | Yes | |
Real-time monitoring of measurement parameters | --- | Yes | Yes | |
Voltage signal input for calculation of measurement parameters | --- | Yes | Yes | |
Status of controlled equipment (open, closed, undefined) (,,) | --- | YES | Yes | |
7.2 | OSCILOGRAPHY RECORDER | |||
Number of binary signals | No. | 64 | Meet | |
Number of physical analog signals | No. | 30 | Meet | |
Number of analogue signals calculated | No. | 10 | Meet | |
Sample Rate | Sample / cl | 4,8,16,32 or 64 | Meet | |
Bandwidth | Cycles | 600 | 600 | |
Pre-fault time | Ms | 10 to 3000 | 10 to 3000 | |
Post-failure time | Ms | 100 to 10000 | 100 to 10000 | |
Number of registered oscillographs | No. | M ínimo 100 | Meet | |
Total recorder capacity | Cycles | 1 Mbyte | 1 Mbyte | |
Drive by internal and external signals | --- | Yes | Yes | |
Real-time monitoring of relay inputs and outputs | --- | Yes | Yes | |
File format | COMTRADE | Yes | ||
In case of power interruption, the events will be Stored in the volatile memory, | Yes | Yes | ||
7.3 | EVENT RECORDER | |||
Registered event numbers (available for extraction) () | No. | 1000 | 1000 | |
Stores sequentially, with date, time, second and millisecond indication ,,, | --- | YES | Yes | |
7.4 | FAULT RECORDER | |||
Number of records | No. | 100 | 100 | |
Pre-fault and current and voltage failure value | --- | YES | Yes | |
7.5 | TROUBLESHOOTING | --- | YES | Yes |
8 | LOCAL AND REMOTE COMMUNICATION | |||
8.1 | Open communication protocol | |||
* IEC 61850 | --- | Yes | Yes | |
Native (no mappings or converters) () | --- | Yes | Yes | |
KEMA Certification KEMA | --- | Yes | Yes | |
Messaging Goose | Yes | |||
Digital Signs | --- | Yes | Yes | |
Analog Signals | --- | Yes | Yes | |
Class | P1 | |||
Kind | A1 | |||
Signal Transfer Speed | Ms | <2.5 | Meet | |
* DNP 3.0 TCP / IP | --- | Yes | No | |
* Modbus | --- | Optional | Optional | |
8.2 | Ports of communication | |||
* RJ-45 Ethernet | --- | YES, Front | Yes | |
* RJ-45 Ethernet | --- | Yes, Later | Yes | |
* Ethernet Fiber Optic * | --- | Yes, Later | Yes | |
* Stand-alone port for synchronization | --- | Yes, (IRIG B) | IRIG-B | |
9 | OPERATION INTERFACE | |||
9.1 | LOCAL INTERFACE | |||
Front display and keypad | --- | Yes | Yes | |
Interface with control systems | --- | Yes | Yes | |
Remote communication | --- | Yes | Yes | |
Input and outputs for telemetering | --- | Yes | Yes | |
Self-diagnosis or self-supervision | --- | Yes | Yes | |
Phase indication triggered | --- | Yes | Yes | |
Signal sending signal | --- | Yes | Yes | |
Signal reception | --- | Yes | Yes | |
9.2 | WEB-BASED INTERFACE Web | |||
Embedded web server | --- | Yes | Yes | |
Changing Web Protection Settings | --- | Yes | Yes | |
Download Oscillographs via web | --- | Yes | Yes | |
Events Download Via web | --- | Yes | Yes | |
Resetting of Indications and Alarms via web | --- | Yes | Yes | |
Security system | --- | Yes | Yes | |
10 | LED SIGNALING | |||
* Visual indicator | --- | Yes | Yes | |
* Minimum number of configurable LEDs | No. | Four. Five | 15 | |
* Shooting start | --- | Yes | Yes | |
* Shooting | --- | Yes | Yes | |
* Relay Status | --- | Yes | Yes | |
* Activated by external contact or internal function | --- | Yes | Yes | |
* Activation by protection function | --- | Yes | Yes | |
9 | SOFTWARE | |||
*Configuration software (with license) | --- | Yes | Yes | |
* Environment | Windows | Windows 7 | ||
* Security level (Password) | --- | Yes | Yes | |
* Download information | --- | Yes | Yes | |
* Oscillograph analysis software | --- | Yes | Yes | |
* Local programming | --- | Yes | Yes | |
* Remote programming | --- | Yes | Yes | |
* Relay communication cables - computer | --- | Yes | Yes | |
* Operation and configuration manual: : | --- | Yes | Only English | |
Spanish, English (original printed and in magnetic file pdf) ,(PDF) | ||||
* Factory Certified Trainers | --- | Yes | Yes | |
* One Relay Simulator Module per person | --- | Yes | Meet | |
* Assistants | No. | 10 | According to the requirement. | |
* Level Operator Duration | days | 1 | 1 | |
* Duration Level Programmer | days | 2 | 2 | |
* Factory Certification for attendees | --- | Yes | Yes | |
* Printed and digital documentation | --- | Yes | Yes |
° | DESCRIPTION TION | UNID. | VALUE REQUIRED | VALUE OFFERED |
1 | Digital Alarm Announcer | |||
2 | For application in monitoring of alarms and signaling of Power Substations | |||
3 | Quantity | Und | 1 | 1 |
4 | Signaling | Digital Type | Yes | Yes |
5 | Identification of failures and alarms in form | Visual and audible | Visual | |
6 | Feeding | You | Range 18 to 80 Vdc | Meet |
7 | Control voltage for identification circuits and alarm reset, obtaining from the power supply, | You | Meet | |
Referring to Fig. | Internal | You | 48 Vdc +/- 20%. | Meet |
Referring to Fig. | Internal contact voltage | 48 Vdc +/- 20%. | Meet | |
10 | Internal contact current: | MA | 4 mA +/- 20%. | Meet |
eleven | Alarm Channel Capacity : | Und | 16 units. | Min. 16 |
12 | Activating channels using contacts | NO (normally open) or NC (normally closed) | NO | |
13 | Reset Delay Times : | 5 ms, 20 ms, 100 ms, 1 s, 5 s, 20 s, 60 s or 160 s. | Meet | |
14 | Manufacturing standard: IEC 660255-5, IEC 60255-6, IEC 60068-2-3 | IEC 660255-5, IEC 60255-6, IEC 60068-2-3 | Meet | |
fifteen | For front panel mounting | Yes | Yes | |
16 | Selection and configuration of parameters from front panel or via serial interface. . | Yes | Yes | |
17 | Self-monitoring system that allows system availability and reliability . | Yes | Yes | |
18 | Code ASCII transmission mode, 4800 or 9600 Bd transfe ASCII,48009600BDr. | Yes | Yes | |
19 | Operating Temperature: | ° C | to 55 ° C | Meet |
twenty | Degree of protection: IP 54. | IP 54 | Meet | |
twenty-one | Includes Equipment Manual and accessories for front panel mounting. . | Yes | Yes |
° | DESCRIPTION TION | UNID. | VALUE REQUIRED | VALUE OFFERED |
1 | MULTIFUNCTION METER | |||
1 | Maker | Alster | ||
1 | Team model | AC1700 | ||
1 | Operating Temperature: : | -20 ° C - + 70 | -40ºC~+70ºC | |
1 | Number of Threads:4 | 4 threads | 3-phase 3-wire,3-phase 4-wire | |
1.1 | Rated current | TO | 1 to 5 | 5-6A, 5-10A, 1-2A, 1-1.2A |
1.1 | Voltage: Autorango | V (ln) | 57V to 347V | 57.5 - 240V (3 ph 4 wire) 100 - 415V (3 ph 3 wire) |
1.1 | Power Supply | 85-240 Vac ± 10% | 70~265V AC/DC | |
1.1 | Frequency | Hz | 60 | 50Hz or 60Hz |
1.1 | Class of Metrology | IEC600687 0.2s or 02.S IEC62053-22 | IEC 62053 - 22 | |
1.1 | Four Squares | yes | ||
1.1 | Information preservation without auxiliary power | Minimum 30 d ies30 | Meet | |
1.1 | Circular mass memory | Minimum 60 d ies | Meet | |
1.1 | Load Profile Option | yes | Meet | |
1.1 | Number of Recording Channels, Minimum , | Referring to Fig. | According to the requirement. | |
1.2 | Number of Recording Channels, optimal , | 6 or 8 | 8 channels | |
1.2 | Digital Inputs | yes | Yes | |
1.2 | Outputs for relays and control functions | yes | Yes | |
1.2 | Analog I / O Option | yes | Yes | |
1.2 | Programming of any parameter or condition for control and alarm functions | yes | Yes | |
1.2 | Instant Instrumentation Values | V, I, kW, kVAr, kVA, kWh, kVarh, frequency, FP | V, I, kW, kVAr, kVA, kWh, kVarh, frequency, FP | |
1.2 | Bidirectionality | yes | Yes | |
1.2 | Frozen readings option | yes | Yes | |
1.2 | Phasor diagram generation | yes | Yes | |
1.2 | External communication RS485, switchable with RS232 RS485RS232, | yes | Yes | |
1.3 | Communication protocol | DNP 3.0 / Modbus Serial DNP3.O, Modbus and IEC 61850 thernet | Flag IEC 62056-21 (formerly 61107) | |
1.3 | Internal Modem Option | yes | Yes | |
1.3 | Event Logging and Handling | yes | Yes | |
1.3 | Power and Demand Channels | yes | Yes | |
1.3 | Redundant Font | yes | Yes | |
1.3 | RTC (Real Time Clock) RTC() | Upgradable GPS | RTC | |
1.3 | POWER AND ENERGY DEMAND | |||
Voltage and current unbalance | yes | Pls.refer to AC1700 manual. | ||
Frequency, power factor, apparent power, reactive and real power ,,,, | yes | Yes | ||
Export and import of bidirectional energy | yes | Yes | ||
1.3 | PQ ANALYSIS | |||
SAG / SWELL wave monitoring / | yes | Pls.refer to AC1700 manual. | ||
Symmetrical components: Zero, Positive and Negative :,, | yes | Pls.refer to AC1700 manual. | ||
Individual harmonics and total harmonic distortion greater than the 63rd 63 | yes | Pls.refer to AC1700 manual. | ||
Detection of transients greater than 17 us 17 | yes | Pls.refer to AC1700 manual. | ||
Sequence of Events | yes | Pls.refer to AC1700 manual. | ||
Samples per cycle, above 1.0241024 | yes | |||
Registry of Flicker and Harmonics of voltage according to NTCSE Peruana ntcse | yes | Pls.refer to AC1700 manual. | ||
1.3 | DATA AND RECORDS OF WAVES | |||
Waveform recording of up to 214,000 continuous cycles with 16 samples per cycle. 214000,16. | yes | Pls.refer to AC1700 manual. | ||
Point-driven: external signal and programs : | yes | Pls.refer to AC1700 manual. | ||
Maximum / minimum records for any parameter / | yes | Pls.refer to AC1700 manual. | ||
Historic records, maximum number of characters , | 32 | Pls.refer to AC1700 manual. | ||
Resolution in seconds Samples per cycle, up to 1,024 ,1024 | yes | Pls.refer to AC1700 manual. | ||
Time Synchronization with GPS GPS | yes | Pls.refer to AC1700 manual. | ||
1.3 | COMMON PORTS AND EXPANDABLE ENTRY / DEPARTURE / | |||
Ports RS-232/485 switchable RS-232/485 | 1 | Meet | ||
RJ 45 port RJ 45 | 1 | Meet | ||
Slave Ports Modbus RTU Serial, Ethernet, Modem, I / R Modbus RTU,,,I/R | yes | Yes | ||
Ports DNP 3.0, Modem and I / R DNP 3.0,I/R | ||||
Data transfer gateway modem / direct Ethernet network for RS-485 RS-485 | yes | Yes | ||
Analog outputs with expandable input / output / | 4 inputs / 4 outputs | Pls.refer to AC1700 manual. | ||
Digital status, input counter , | Referring to Fig. | Pls.refer to AC1700 manual. | ||
Digital relay outputs (control / pulse) (/) | 7 m ínimo | Pls.refer to AC1700 manual. | ||
Sync port | If (IRIG B or NTP SERVER) | Yes | ||
1.4. | SEVEN POINTS FOR CONTROL AND ALARM | |||
Setting, mínimum response time | 1 sec or 1/2 cycle | 1 sec | ||
Linearization of mathematical, logical and logarithmic formulas , | yes | Yes | ||
Simple and multi - alarm alarms | yes | Yes | ||
Remote Alarm Notification | yes | Yes | ||
1.4. | INCOME OF MEASUREMENTS | |||
Standards for accuracy: ANSI C12,60 | yes | Yes | ||
ANSI standard C12,20 0.2 | yes | Yes | ||
Standard IEC 60687 0,2 S | yes | IEC 60687 | ||
IEC 60687 standard, accuracy class 0,2 S | yes | Yes | ||
Line Loss and Transformer Compensation | yes | Yes | ||
Multiple annual scheduling, Hourly activity profiles , | yes | Yes | ||
software | yes | Yes |