China Portable Vlf High Voltage AC Hipot Test Set Vlf Hipot Tester, Find details about China Vlf Hipot Tester, Test Equipment from Portable Vlf High Voltage AC Hipot Test Set Vlf Hipot Tester
1). Data of current, voltage, wave form can be directly sampled at high voltage side, so the data is real and accurate.
2). Overvoltage protection: If the output exceeds the set limit of voltage, the instrument will shut-down to protect itself; the actuation time is less than 15ms.
3). Overcorrect protection: it is high-low voltage dual protection in the design, the accurate shut-down protection can be made according to the set value at high voltage side; If the current on low voltage side exceeds the rated current, the instrument will take shut-down protection, the actuation time are both less than 15ms.
4). A high voltage output protective resistor is provided in the voltage boost body in the design and this eliminates the need of additional protective resistor connected outside.
5). As a result of high and low voltage closed-loop negative feedback control circuit, the output without capacitive rise effect.
6). High-voltage control part adopts innovative light control HV switching unit, control is accurate, safe and reliable;
7). With color man-machine interface touch control plus controls modular software operating system, precise and intuitive
8). Multi-purpose, can simultaneously measure tested objects capacitance, insulation resistance, leakage current, and AC withstand voltage test
3 Parameters
Table 1:
Model | Rated Voltage | Load Capacity | Fuse | Reference Weight |
WXVLF-30 (30KV) | 30kV/20mA (Peak) | 0.1Hz,≤1.1µF | 5A | Controller: 4kg Booster:25kg |
0.05Hz,≤2.2µF | ||||
0.02Hz,≤5.5µF | ||||
WXVLF-50 (50KV) | 50kV/30mA (Peak) | 0.1Hz,≤1.1µF | 15A | Controller:4kg Booster: 50kg |
0.05Hz,≤2.2µF | ||||
0.02Hz,≤5.5µF | ||||
WXVLF-80 (80KV) | 80kV/30mA (Peak) | 0.1Hz,≤0.5µF | 20A | Controller:4kg Booster 1(30kV):25kg Booster 2(50kV):50kg |
Output rated voltage | See table 1 | |
Output frequency | 0.1Hz,0.05Hz,0.02Hz | |
Load capacity | See table 1 | 0.1Hz max 1.1 μf |
0.05 Hz max 2.2 μf | ||
0.02 Hz max 5.5 μf | ||
Measurement accuracy | 2.5 % | |
Positive and negative voltage peak errors | ≤2.5% | |
Voltage wave form distortion | ≤3% | |
Insulation resistance measurement error | ≤2.5% | |
Leakage current measurement error | ≤2.5% | |
Power | AC 50 Hz,220V ±5% | |
Power Fuse | See table 1 |
Wuhan WG Hipot Electric Tester Co.,Ltd. (hereafter referred to as WG Hipot) is the professional factory of high voltage testing equipment with over 15 years industry experience.
ISO Certified factory, qualified R&D and after-sales Engineer team, 3000 square meters workshop, our high voltage testers cover full range: High voltage hipot tester, Circuit breaker Switchgear Tester, Transformer tester, Relay Protection Tester, CT/PT Tester, MOA/Insulator Tester, SF6/Insulation Oil Test Equipment, Resistance Tester, etc.
Since 2003, with the support from our investors Wuhan High Voltage Institution and Xi'an High Voltage Institution, WG Hipot established and pioneered in high voltage testing field in domestic market as the designated supplier for State Grid and mainstream power companies.
Meantime, WG Hipot has developed overseas markets across 5 continents worldwide. We gained good feedback from our customers with our high performance, good quality, customized specification and easy-to-operate high voltage testers, which can be widely used in railway, oil and chemical industry, electricity grid, university, big factory etc.
III.Customer Visit:
IV.Filed Test&Service:
V.Certification:
VI.Package & Shipment:
VII. FAQ
1.When can I get the price?
We usually quote within 6hours after we get your inquiry. If you are vey urgent to get price, please call us or tell us in your email so that we will regard your inquiry priority.
2. What about the leading time for production?
Honestly, it depends on the order quantity and the product. Usually our leading time is within 7 working days after order confirmed.
3. What is your payment terms?
We accept EXW,FOB, CFR, CIF, ect. You can choose the one which is the most convenient and cost effective for you.
4. How much will be the Shipping cost and time?
This will depend on the size of your goods and the method of shipping (by sea/ by air/by Express) and your designated port or airport. We will be grateful if you can spare us some minutes to evaluate the cost based on the information provided.
5. Could you please tell me the Warranty Period of your product?
Our warranty period is one year free and lifelong maintenance. If the product is damaged (if not man-made damage), in the first year,we will send free parts for replacement. Over warranty, maintenance is paid service.
6. What kind of Certificate can you provide?
We can provide the CE mark, ISO 9001 quality certificate, third party calibration certificate(CNAS) and factory test report.
7. Do you have Technical Backup to all customers from different countries?
To be sure,our technical support is always available and quick response.
We are manufacturer with much on-site testing experience, thus we know how to deal with your problems. Moreover, our engineers can go to your country to support if need.