2021 New High Voltage Polymer Surge Arrestor

China 2016 New High Voltage Polymer Surge Arrestor, Find details about China Surge Arrestor, Surge Protector from 2016 New High Voltage Polymer Surge Arrestor

Model NO.
YH10W5-18
Creepage Distance
596mm
Certificate
ISO9001:2008, Kema
Mocv
15.3kv
Color
Grey, Brown, Red
Nominal Current
10ka
Trademark
YONGDE
Transport Package
Carton+Wooden Case
Origin
Zhejiang, China (Mainland)
Model NO.
YH10W5-18
Creepage Distance
596mm
Certificate
ISO9001:2008, Kema
Mocv
15.3kv
Color
Grey, Brown, Red
Nominal Current
10ka
Trademark
YONGDE
Transport Package
Carton+Wooden Case
Origin
Zhejiang, China (Mainland)

2016 New High Voltage Polymer Surge Arrestor

0.28kV~500kV Surge Arresters' Characteristics:
1. The Core column applied winding structure, Polymer Housed core pillar molded on the core column, with almost no internal air gap, and outstanding sealing performance Simple in structure, small in size and light in weight.
2. Polymer Housed with silicone rubber, explosion-proof ZnO varistor as the core component is large
in flow capacity.
3. International standard IEC 60099-4 and ANSI 62.22, and with high reliability. With fully insulated tops, the product can be applied to the complete cabinet installation, which can reduce the designing size of cabinet.
4. Products with detachment device can provide signals for quitting operation when failure occurs,
avoiding arrester explosion, and it is maintenance-free.
5. Polymer housed products with a six CTI level, creepage distance meets the requirements of IV level in heavy pollution areas.

 

Surge Arresters' Technical Parameters:

TypeYH10W5-18/49.54/10μS High current impulse kA100
Rated voltage---------kV18Lightning impulse withstand kV150
MOCV ----------------kV15.3Power frequency voltage withstand(dry/wet)kV38
Nominal Current-------kA100.1S TOV--------------kV21.6
Residual voltage of steep impulse----at 5kA(kV)53.31S TOV----------------kV20.7
8/20μS Residual voltage of lightning impulse current kV(Peak value)-----at 5kA(kV)49.410S TOV---------------kV19.8
Residual voltage of switching impulse current kV (peak value)----at 1kA (kV)37.81200S TOV-------------kV18
1mA D.C reference voltage (kV)25.5Creepage distance ----mm596
Line discharge level1Material employed in series non-linear resistorZinc Oxide
2mS long duration impulse current A400Material of housingsilicon rubber