China Hot Selling High Voltage Transformer Impulse Voltage Test System, Find details about China Impulse Voltage Generator, Generator System Testing Equipment from Hot Selling High Voltage Transformer Impulse Voltage Test System
1.CJDV-4000 Impulse voltage generator
• Rated voltage: ±4000kV • Rated energy: 400kJ
• Rated impulse capacitance: 50.0nF • Rated charging voltage each stage: ±200kV
• Number of stage: 20 • Stage energy: 20.0kJ
• Stage capacitance: 1.0F/200kV,2.0F/100kV
• Waveform:
Standard lightening impulse:1.2/50μS Efficiency: 85 ~ 90% (1.2±30%/50±20%μS)
Switch impulse: 250/2500μS Efficiency: 65 ~ 70% (250±20%/2500±60%μS)
Chopping wave: 2 ~ 6μS variable
• Generator dimension and weight(for reference)
Dimension: 3674mm(W)×5500mm(L)×14900mm(H) Weight: 26700kg
2.Environment
• Maximum altitude: 1000 m • Altitude increases 100m, and rated voltage lowers 1%
• Operation temperature for HV component: +10 ~ +45ºC • HV component relative humidity (non-condensing) 95 %
• Temperature for electronic control & measuring: +10 ~ +45ºC
• Anti-seismic: Grade 8
• Relative Humidity of electronic components: 80%
• Grounding resistance: < 0.3
• Components storing and transport temperature: 20 ~ + 60ºC
• No dust
3.Main technical parameter
• Rated voltage: ±100kV ~ 6000kV(and above) • Rated energy: 2.5kJ ~ 240kJ
• Rated charging voltage: ±100kV ±200kV
• Stage capacitance: 1.0μF/200kV 2.0μF/100kV(according to total capacitance)
• Standard lightening impulse: 1.2/50μS efficiency: 85 ~ 90% (1.2±30%/50±20%uS )
• Switch impulse: 250/2500μS efficiency: 65 ~ 70% (250±20%/2500±60%uS )
4.System components
IVG-Impulse generator 1 set LGR-DC charging system 1 set
CR- Low impedance capacitive divider 1 set IGCS-Intelligent control system 1 set
IVMS-Digital measure and analyze system 1 set MCG-Multi-gap chopping device 1 set