GTM2L -250/3N 225A Earth Leakage Circuit Breaker ELCB with IEC60947-2

China GTM2L-250/3N 225A Earth Leakage Circuit Breaker ELCB with IEC60947-2, Find details about China RCCB, Earth Leakage Circuit Breaker from GTM2L-250/3N 225A Earth Leakage Circuit Breaker ELCB with IEC60947-2

Poles Number
3n
Type
Circuit Breaker
Function
Conventional Circuit Breaker, Circuit-Breaker Failure Protection, RCCB
Certification
ISO9001-2000, CCC
Current
16A~630A
Trademark
JUBANG
Specification
Copper
Origin
China
HS Code
8536200000
Poles Number
3n
Type
Circuit Breaker
Function
Conventional Circuit Breaker, Circuit-Breaker Failure Protection, RCCB
Certification
ISO9001-2000, CCC
Current
16A~630A
Trademark
JUBANG
Specification
Copper
Origin
China
HS Code
8536200000
GTM2L series Earth Leakage Circuit Breaker

Application: In distribution network of AC50Hz, ranted voltage 400V
Standard: IEC60947-2
Parameters: Rated current: 16-630A
Rated insulation voltage: 690V
Rated operating voltage: 400V
 
ModelGTM2L-125GTM2L-250GTM2L-400GTM2L-630
IEC60947-2
Shell grade current   Inm(A)125250400630
Operating frequency  (Hz)50505050
Number of poles3N3N3N3N
Rated current   In(A)16~125100~250250~400400~630
Rated insulation voltage   Ui(V)800800800800
Rated impulse withstand voltage   Uimp(KV)8888
Rated working voltage   Ue(V)400400400400
Flashover distance   (mm)≯50≯80≯100≯100
Rated limit short circuit breaking capacity   Icu(kA)35355050
Rated runningshort circuit breaking capacity   Ics(kA)25253535
rated short-circuit turn on capacity   Icm(kA)/1s25%Icu25%Icu25%Icu25%Icu
Rated residual operating current   IΔn(mA)30(Non delay type), 50, 100, 300, 50030(Non delay type), 50, 100, 300, 500100, 300, 500, 1000100, 300, 500, 1000
Limit non driving time   Δt(s)0.1, 0.3, 0.5, 10.1, 0.3, 0.5, 10.1, 0.3, 0.5, 10.1, 0.3, 0.5, 1
Rated residual non operating current   IΔn(mA)IΔno=IΔn/2IΔno=IΔn/2IΔno=IΔn/2IΔno=IΔn/2
Utilization categoryAAAA
Service lifeMechanical life (times)Maintenance free20000200001000010000
With maintenance40000400002000020000
Electrical life(times)400V8000800075007500
Outline dimension(mm)Width120140198280
Length190210258280
Height85108150158
Optional Accessories
Alarm contact08OOOO
Shunt release10OOOO
Auxiliary contact20OOOO
Two sets of auxilisry contact60OOOO

GTM2L-250/3N 225A Earth Leakage Circuit Breaker ELCB with IEC60947-2
GTM2L-250/3N 225A Earth Leakage Circuit Breaker ELCB with IEC60947-2
GTM2L-250/3N 225A Earth Leakage Circuit Breaker ELCB with IEC60947-2
GTM2L-250/3N 225A Earth Leakage Circuit Breaker ELCB with IEC60947-2
GTM2L-250/3N 225A Earth Leakage Circuit Breaker ELCB with IEC60947-2
GTM2L-250/3N 225A Earth Leakage Circuit Breaker ELCB with IEC60947-2